12.8 Base Pan Heater Control (Optional)
To enable the base pan heater function, control panel initial setting has to be manually adjusted by activating
Base Pan Heater menu.
There are 2 optional start condition can be selected, Type A or Type B.
Control
details:
1 Type A: (Default Auto Mode)
Start conditions:
o When outdoor air temperature ≤ 3°C during heating and deice operation is ON.
Control contents:
o Base pan heater is ON during deice operation and continues ON for 10 minutes after deice operation
ends.
Cancel condition:
o When outdoor temperature > 6°C after deice end or
o When operation is not at heating mode or
o Base pan heater ON timer count is completed.
o When operation is not at heating mode or
o Base pan heater ON timer count is completed.
2 Type B: (ON Mode)
Start conditions:
o When outdoor air temperature is ≤ 5°C and operates in heating mode, base pan heater is ON.
Cancel conditions:
o When outdoor air temperature is > 7°C or
o When operation is not at heating mode.
o When operation is not at heating mode.
114
12.9 Force Heater Mode
Purpose of Force Heater Mode
- As a backup heat source when heat pump error. Force heater Mode control backup heater to heat up the
room circuit, and turn ON back up heater or booster heater to boil up tank water base on the tank heater
selection (internal or external)
selection (internal or external)
Force Heater Control start condition:
- Force heater request ON by user OR auto turn ON by remote controller during error AND
(Force Heater mode can be operate regardless of mode selection, remocon will send the lastest mode
selection and force bit to indoor. Indoor will judge to turn ON heater to room side if it is heat mode selected,
and turn ON heater to heat up tank water base on tank heater selection)
selection and force bit to indoor. Indoor will judge to turn ON heater to room side if it is heat mode selected,
and turn ON heater to heat up tank water base on tank heater selection)
- During Error Happen (exclude the error list below)
Error List not allow Force Heater Operation
H12
Capacity Mismatch
H76
Indoor-Remote Controller Communication Error
H20
Abnormal Water Pump
H95
Abnormal Voltage Connection
H62
Abnormal Water Flow
F37
Abnormal Water Inlet sensor
H70
Abnormal Back-up Heater OLP
F45
Abnormal Water Outlet sensor
H74
PCB Communication Error
[ When tank mode operate with external heater selected & tank heater select ON]
H72
Abnormal tank sensor
H91
Abnormal tank heater OLP
Force Heater Control Stop Condition:
- Force Heater request OFF OR
- Operation OFF request OR
- Power
- Operation OFF request OR
- Power
reset
OR
- Error of above list happens during force heater operation.
Control contents:
1) After fulfil start condition, indoor will operate the force heater operation according to below mode condition
Heat mode Only
: Turn ON backup heater to achieve room heat pump target water temperature.
Heat + Tank mode
: Turn ON backup heater to heat up room OR Turn ON Heater to Boil up tank water.
Cool mode Only
: Water pump and backup heater will OFF in force heater mode
Cool + Tank mode
: Operate pump and internal Heater OR External heater to Boil up tank water.
Tank mode Only
: Operate pump and internal Heater OR External heater to Boil up tank water.
* For heat mode condition, backup heater will only turn ON if the backup heater is enable regardless of Room
Heater Selection
* For tank mode condition, If internal heater selected backup heater will turn ON to boil up tank water.
If external heater selected, booster heater will turn ON to boil up tank water regardless of tank heater
selection
Room Side: (Heat Mode)
1) When force heater mode start condition fulfilled, turn ON water pump and turn ON backup heater follow
below control.
2) Operate the 3 ways valve at room side only and turn ON 2 ways valve as heat mode operation.
3) Turn ON the zone pump and mixing valve if system select 2 zone system or Buffer tank connect YES, control
3) Turn ON the zone pump and mixing valve if system select 2 zone system or Buffer tank connect YES, control
according to normal zone pump and mixing valve control.
4) When Force heater mode stop condition fulfilled, turn OFF heater as below condition and turn OFF water
pump after pump delay time.
Backup Heater On Condition:
a) When Force Heater Control start condition fulfill AND
b) After water pump operate 2 minute AND
c) When water outlet temperature < water set temperature + [-4°C] AND
d) 20 minutes since previous Backup heater Off AND
e) Backup Heater Enable
b) After water pump operate 2 minute AND
c) When water outlet temperature < water set temperature + [-4°C] AND
d) 20 minutes since previous Backup heater Off AND
e) Backup Heater Enable
Backup Heater Stop condition
a) Force mode off OR
b) Operation
b) Operation
off
OR
c) When water outlet temperature > water set temperature + [-2°C] for continuous 15 secs OR
* ON/OFF follow normal heater sequence.
115
Tank side (Tank mode)
1) When tank mode select and force heater bit received, turn ON backup heater (INTERNAL) or Booster Heater
(External) depend on the tank heater selection.
2) If tank heater selection is INTERNAL, follow normal thermo judgement to switch 3 ways valve to tank side
and room side.
3) If tank heater selection is EXTERNAL, only turn ON booster heater according to tank thermo.
Tank Heater selection is INTERNAL:
Backup Heater ON Condition:
a) After water pump operate 2 mins AND
b) When tank temperature < Tank set temperature - [Remocon Set Tank Re-heat Temp] AND
c) 20 minutes since previous backup heater OFF AND
d) Backup heater enable
Backup Heater ON Condition:
a) After water pump operate 2 mins AND
b) When tank temperature < Tank set temperature - [Remocon Set Tank Re-heat Temp] AND
c) 20 minutes since previous backup heater OFF AND
d) Backup heater enable
Backup Heater OFF Condition:
a) Force mode OFF OR
b) When tank temperature > Tank set temperature for continuous 15 secs OR
c) Tank
a) Force mode OFF OR
b) When tank temperature > Tank set temperature for continuous 15 secs OR
c) Tank
Operation
OFF
Tank Heater selection is EXTERNAL:
Backup Heater ON Condition:
a) Force Heater mode ON AND
b) Tank temperature < tank set temperature + [Remocon Set Tank Re-heat Temp] - 1°C, AND
c) 20 minutes since previous heater off.
Backup Heater ON Condition:
a) Force Heater mode ON AND
b) Tank temperature < tank set temperature + [Remocon Set Tank Re-heat Temp] - 1°C, AND
c) 20 minutes since previous heater off.
Backup Heater OFF Condition:
a) Tank temperature > tank set temperature for continuous 15 sec
b) Force mode OFF
c) Tank Mode Operation OFF
a) Tank temperature > tank set temperature for continuous 15 sec
b) Force mode OFF
c) Tank Mode Operation OFF
(During tank interval or tank mode condition, water pump and 3 ways valve will OFF)
12.10 Powerful Operation
Powerful mode is use to increase the capacity of heat pump to achieve higher target temperature. Powerful mode is
applicable when heat mode is operating.
Remote control setting:
On quick menu of remote control, there is 4 options of powerful mode can be select.
applicable when heat mode is operating.
Remote control setting:
On quick menu of remote control, there is 4 options of powerful mode can be select.
OFF
: Cancel powerful mode
30 minutes
: Set powerful for 30 minutes
60 minutes
: Set powerful for 60 minutes
90 minutes
: Set powerful for 90 minutes
Control contents:
During the time set by remote control, powerful will activate according to 2 shift up controls. However, this function is
applicable only for heating. Remote control will transmit the signal to indoor unit once this function is select then
transmit OFF signal to indoor when the timer is complete. Indoor will transmit signal to outdoor for frequency control.
Indoor setting temperature shift
If system is standard system (Optional PCB is not connected)
o Target water temperature will shift up to Wlo or Whi whichever higher.
If system is extension system (Optional PCB is connected)
o Target water Zone 1 and Zone 2 temperature will shift up to Wlo or Whi whichever higher.
* If “Direct Type” temperature control is select, this powerful shift up setting is not effective.
Start condition
o Powerful function is select by remote control.
End Condition
o OFF/ON button is pressed.
o Powerful function is OFF by remote control.
o Powerful function is OFF by remote control.
116
12.11 Quiet Operation
Quiet mode is use to reduce the noise of outdoor unit by reducing the frequency or fan speed.
Quiet level
There are 3 level (Level 1, Level 2, Level 3) to set by quick menu function on remote control.
Control content
Once the quiet function is select, the remote control will transmit the signal to indoor and outdoor unit.
Start condition
Quiet level
There are 3 level (Level 1, Level 2, Level 3) to set by quick menu function on remote control.
Control content
Once the quiet function is select, the remote control will transmit the signal to indoor and outdoor unit.
Start condition
Quiet mode is set on remote control.
Quiet mode is request ON by weekly timer.
Stop condition
If any of below condition is achieve.
Stop condition
If any of below condition is achieve.
OFF/ON button is pressed.
Quiet mode is OFF by remote control.
Quiet mode is request OFF by weekly timer.
12.12 Sterilization Mode
Purpose:
o To sterilize water tank by setting the required boiling temperature.
Remote
control
setting
o Days for sterilization function to start can be select.
o Time of selected day to start sterilization function.
o Boiling temperature (Internal heater is 55°C ~ 65°C)
o Maximum operation time is 5 minutes to 1 hour.
o Time of selected day to start sterilization function.
o Boiling temperature (Internal heater is 55°C ~ 65°C)
o Maximum operation time is 5 minutes to 1 hour.
Start
condition
o Tank connection set to “YES” by remote control
o Sterilization function selects “YES”.
o Sterilization signal received from remote controller by timer.
o Tank mode request ON.
o Sterilization function selects “YES”.
o Sterilization signal received from remote controller by timer.
o Tank mode request ON.
Stop
condition
o When boiling timer is completed. Boiling timer (Remote control set maximum operation time) start counting
once tank achieve boiling set temperature OR
o After 8 hours of operation since sterilization start.
o Tank mode request OFF.
o Tank mode request OFF.
Control
content:
o During sterilization function activation time, target tank set temperature will internally change to boiling set
temperature.
o During sterilization activates, heat pump and heater (external or internal) will operate as normal tank mode to
achieve the boiling set temperature.
o Sterilization operation will end when stop condition is fulfill.
o After sterilization is complete, tank set temperature will resume to normal operation.
o After sterilization is complete, tank set temperature will resume to normal operation.
* Tank temperature may not achieve boiling set temperature if tank heater is select OFF OR external compressor
switch.