Condition 2: Tank Heater OFF (Internal Tank Heater) 
  If tank temperature achieve tank thermo OFF, heat pump turn OFF, water pump turn OFF, room heater OFF and 
3 ways valve switch to room side. 
 
When tank temperature achieve heat pump ON condition, water pump ON, heat pump ON and room heater turn OFF. 
 
Heat pump OFF condition at Tank Mode 
o  Tank temperature > tank water set temperature continuously for 20 seconds after heat pump thermos OFF 
due to water thermo. (Heat pump turn OFF but water pump continue ON and room heater turn ON to achieve 
tank set temperature) OR 
o  Tank temperature > tank set temperature + [1°C] for continuously 20 seconds. (Heat pump OFF, water pump 
OFF, room heater OFF and 3 ways valve switch to room side) 
 
Heat pump ON condition at Tank Mode 
o  Tank temperature < tank water set temperature + R/C setting (Tank re-heat temp) 
(Water pump turn ON OR continue ON, heat pump ON and 3 ways valve switch to tank side or maintain at 
tank side) 
 
Tank heater control 
  Internal heater only operates to tank side if Tank heater ON and backup heater is enable. 
 
Internal heater turn ON condition: 
  Tank temperature < tank set temperature AND 
  Heat pump thermos OFF AND 
  20 minutes from previous heater off AND 
  Internal tank heater selects USE from control panel. 
 
Internal heater turn OFF condition: 
  Tank temperature > tank set temperature for continuously 15 seconds OR 
  Heat pump thermo ON OR 
  Mode change or operation is off by control panel. 
12.1.10  Heat + Tank Mode Operation 
1  3 ways valve control: 
o  3 ways valve switch to room side during room heat-up interval and switch to tank side during tank heat-
up interval. Both modes will switch alternately. Tank mode is the initial running mode of Heat + Tank 
mode. 
 
2  Heat pump operation control: 
o  During room heat-up interval 
  Follow normal heating operation. 
Switching to tank side depends to below cases: 
Case 1:  
 
   
[Previous switch from tank interval to room interval due to thermo OFF] 
  Switch to tank heat-up interval when Tank temp < Tank thermos ON temp (Room heat-up interval 
ends) 
  
 
Case 
2: 
 
   
[If heating operation at room side is less than 30 minutes and switch to tank side 3 times   
  
 
consecutively] 
  Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval 
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND Tank 
temperature < Tank thermo ON temperature. 
  
 
Case 
3: 
 
   
[Previous switch from tank interval to room interval due to tank interval timer is complete] 
  Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval 
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND tank 
temperature < Tank thermo ON temperature. 
o  During Tank heat-up interval 
  Tank interval is the first mode running when heat + tank mode is select. 
  Switch to room interval only when tank achieve tank thermo OFF OR tank heat-up interval timer is 
complete. 
  Heat pump operates according to normal tank mode operation. 
 
106 
3  Room heater control: 
o  During heating heat-up interval 
  Follow normal room heater control operation. 
 
4  Tank heater control: 
o  During heating heat-up interval 
  Internal tank heater will not function under heating heat-up interval. 
o  During tank heat-up interval 
  Internal tank heater will turn ON after heat puMp thermo off to boil tank temperature to tank set 
temperature. 
o  2ways valve control is open 
o  Indoor water pump control: 
  Indoor water pump always turn ON if room heat pump thermo ON OR Tank thermo ON. 
12.1.11  Cool + Tank Mode Operation 
1  3 ways valve control: 
o  3 ways valve switch to room side during room cooling interval and switch to tank side during tank heat-up 
interval. Both mode will switch alternately. Tank mode is the initial mode of cool + tank mode. 
 
2  Heat pump operation control: 
o  During room heat-up interval 
  Follow normal cooling operation. 
 
   
Switching to tank side depends to below cases: 
  
 
Case 
1: 
 
   
[Previous switch from tank interval to room interval due to thermo OFF] 
  Switch to tank heat-up interval when Tank temperature < Tank Thermo ON temperature (Room 
interval will ends) 
 
 
Case 2: 
   
[If cooling operation at room side is less than 30 minutes and switch to tank side for 3 times 
 consecutively] 
  Maintain at room cooling interval regardless of the tank temperature. Switch to tank heat-up interval 
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND Tank 
temperature < Tank thermo ON temperature. 
  
Case 
3: 
   
[Previous switch from tank interval to room interval is due to tank interval timer is complete] 
  Maintain at room cooling interval regardless of the tank temperature. Switch to tank heat-up interval 
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND tank 
temperature < Tank thermo ON temperature. 
 
 
*Tank Thermo ON temperature: 
 
Internal Tank Heater select USE    <Tank set temperature + R/C setting (Tank re-heat temperature) 
Others 
  <Tank water set temperature + R/C setting (Tank re-heat temperature) 
 
o  During tank heat-up interval 
  Tank interval is the first mode running when the cool + tank mode is select. 
  Switch to room interval only when tank achieve tank thermo OFF OR tank heat-up interval timer is 
complete. 
  Heat pump operates according to normal tank mode operation. 
 
3  Room heater control: 
o  During room cooling interval 
  Room heater is OFF and not operates. 
 
4  Tank heater control: 
o  During room cooling interval 
  Internal tank heater will not function under room cooling interval. 
o  During tank heat-up interval 
  Internal tank heater will turn ON after heat pump thermos off to boil tank temperature to tank set 
temperature. 
 
 
107 
5  2 ways vale is close. 
 
6  Indoor water pump control: 
o  Indoor water pump always turn ON if room heat pump thermo ON OR Tank thermo ON. 
12.1.12  Outdoor Fan Motor Operation 
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it 
stops 30 seconds after compressor stops operation. 
 
30 sec
Compressor:
ON
ON
Fan Speed
ON
ON
OFF
OFF
Outdoor Fan:
 
12.2 Water Pump 
12.2.1  Water Pump Control 
  Once the indoor unit is ON, the water pump will be ON immediately and no error judgment for 70 seconds. 
However, during this 70 seconds operation, if there is any abnormality cause at outdoor or malfunction, the 
compressor should be OFF immediately and restart delay after 3 minutes. 
  The system will start checking on the water flow level after operation start for 70 seconds. If water flow level is 
detected low continuously 60 seconds, the water pump and the compressor will be OFF permanently and 
OFF/ON control panel LED will blink (H62 error occurs). 
  When error happens, the power has to be reset to clear the error. 
  If there is no error indication, the water pump shall be continuously running. 
  The water pump will remain ON when compressor OFF due to thermostat OFF setting is reached. 
  Water pump will OFF when room thermo OR tank thermo OR buffer tank thermo OFF. 
  Water pump will delay 15 seconds to turn OFF when request to OFF except during anti-freeze deice activate or 
air purge mode. 
 
Pump ON Request
YES
NO
NO
YES
ON Water Pump
OFF Water Pump
Pump ON Time
≥ 70 Sec?
YES
Water Flowrate Abnormal
> 15 Sec?
H62 Error Display
at Remote Controller
 
 
Maximum pump speed setting on remote control 
  Standard pump speed is automatically controlled to get the designed water temperature different between water 
inlet and outlet (∆T). Instead of setting the standard pump speed, maximum pump speed is manually adjusted by 
the installer according to water circuit pressure drop. 
 
However, the following sequences do not follow maximum pump duty setting by remote control. 
 Pump 
down 
mode 
  Air purge mode 
 Normal 
deice 
108 
1) P-Q graph for different pump HEX duty 
 
Water FlowRate. Q (L/min)
P
res
sure.
P
 (k
pa
)
P - Q
 
12.2.2  Zone Water Pump Control 
Purpose:  
  Water pump install at each zone to circulate the water inside each zone during buffer tank connection selected 
“YES” or 2 zone systems. 
 
 
 
Content: 
  AC type water pump install for this zone water pump control. When optional PCB connected, 230V output will 
drive this zone pump. 
  There are three pump can be connected through Optional PCB. (Zone 1 Pump, Zone 2 Pump, & Pool Pump) 
 
* Zone 1 pump [P1] use to circulate zone 1 water circuit & Zone 1 mixing valve [M1] adjust to control the Zone 1 
target water temperature. 
 
* Zone 2 pump [P2] use to circulate zone 2 water circuit & Zone 2 mixing valve [M2] adjust to control the Zone 2 
target water temperature. 
 
* When Pool Function select as Zone 2 circuit, [P2] use to circulate water to heat exchanger which use to transfer 
heat to pool water. 
 
* Pool pump [P3] circulates the pool water through the heat exchanger to get warm water. 
 
  Zone 1 and Zone 2 water pump start condition: 
o  Zone room request ON 
 
(eg. Zone 1 thermo ON, only zone 1 pump will turn ON) 
  Zone 1 and Zone 2 water pump stop condition: 
o  Zone room request OFF 
  Pool water pump start condition: 
o  Pool Zone request ON AND 
o  Pool function is selected 