DOWNLOAD Panasonic WH-MXC16G9E8 Service Manual ↓ Size: 10.68 MB | Pages: 127 in PDF or view online for FREE

Model
WH-MXC16G9E8
Pages
127
Size
10.68 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR-TO-WATER HEATPUMP
File
wh-mxc16g9e8.pdf
Date

Panasonic WH-MXC16G9E8 Service Manual ▷ View online

49 
Heat + Tank Mode (Heating priority set) 
Under Solar Priority Set Condition: 
 
 
 
Under Solar Priority Not Set Condition: 
 
 
 
50 
Setting 2: When heating priority is not set by control panel: 
  When Solar Priority is set/not set by control panel: 
 
1.  3 ways valve control: 
o
  3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank 
heat-up interval. Both modes will switch alternatively. Tank mode is the Initial running mode of this heat 
+ tank mode (heating no priority). 
 
2.  Heat pump operation control: 
o
  During heating heat-up interval 
  Follow normal heating operation 
Under solar priority set condition: 
  Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo 
OFF AND solar 3WV OFF AND Tank temperature < THERMO ON TEMP (End Room Interval 
Early) OR  
  Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < 
THERMO ON TEMP AND solar 3WV OFF. 
Under solar priority not set condition: 
  Switch to tank heat interval and start counting tank heat-up timer when External Room Thermo 
OFF AND Tank < THERMO ON TEMP (End Room Interval) OR  
  Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature < 
THERMO ON TEMP. 
* THERMO ON TEMP is defined Tank thermo ON/OFF condition below. 
o
  During tank heat-up interval 
  Heat pump tank target temperature = Tank set temperature or [50°C] whichever lower. 
  Heat pump Water Outlet set temperature is set to [53°C] during tank interval. 
  Initial Tank THERMO ON TEMP = heat pump tank target temperature + [-2°C]. 
 
Tank thermo ON/OFF characteristic: 
o
  THERMO OFF TEMP: 
1.  THERMO OFF TEMP = Heat pump tank target temperature + [0°C]. 
2.  Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due 
to water thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count 
heating heat-up interval. 
3.  Tank temperature > Tank set temperature + [2°C] for continuous 10 seconds, switch 3 way 
valve to room side. End Tank heat up interval and start count heating up interval. 
 
o
  THERMO ON TEMP: 
1.  THERMO ON TEMP = Heat pump tank target temperature + [-2°C]. 
2.  After heating heat-up interval, always detect tank temperature. Switch to next tank heat-up 
interval when tank temperature < THERMO ON TEMP. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
51 
Characteristic of heat pump thermo ON/OFF under tank side condition 
Water Outlet Thermo condition 
o
  Heat pump THERMO OFF TEMP: 
1.  Heat pump THERMO OFF TEMP = 53°C + [+4°C] 
2.  Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, heat pump 
OFF but water pump continue ON. 
 
o
  THERMO ON TEMP: 
1.  THERMO ON TEMP = Water inlet temperature, when heat pump thermo OFF + [-3°C]. 
 
Water Inlet Thermo condition 
o
  Heat pump THERMO OFF TEMP: 
1.  Water inlet temperature > [55°C] for continuous 60 seconds, heat pump OFF. 
 
o
  THERMO ON TEMP: 
1.  THERMO ON TEMP = Water inlet temperature < [55°C] 
 
Solar Operation Condition (Only during solar priority is set condition) 
  When solar pump ON, tank heat-up interval end early and 3 ways valve switch to room side. 
 
o
  THERMO IN TEMP: 
1.  THERMO ON TEMP = Heat pump tank target temperature + [-2°C]. 
2.  After heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval when 
tank temperature < THERMO ON TEMP and solar 3 way valve OFF. 
 
o
  Tank interval will end and start heating interval timer, IF 
1.  Tank interval timer finish AND External Room Thermo ON OR 
  Only when this condition occur at tank side before tank temperature thermo OFF switch to room side 
compulsory and continue until complete room heat-up interval and switch back to tank side. 
2.  Fulfill Tank thermo OFF condition. 
 
3.  Backup heater control: 
o
  During heating heat-up interval. 
  Follow normal back up heater control operation. 
o
  During tank heat-up interval. 
  Back up heater OFF during this interval. 
 
4.  Booster heater control: 
o
  During heating heat up interval. 
  Booster heater ON/OFF according to booster heater operation control. 
o
  During tank heat-up interval. 
  Once switch from heating heat-up interval to tank heat-up interval, turn OFF the booster heater 
and start counting the BOOSTER HEATER DEPLAY TIMER. 
  Booster heater turn ON after BOOSTER HEATER DELAY TIMER fulfill and tank temperature 
lower than tank set temperature. 
  BOOSTER HEATER DELAY TIMER is clear when switch to heating heat-up interval. 
 
5.  Solar 3 way valve 
o
  Solar 3WV operates follow solar operates specification. 
 
* Under solar priority is set condition, when solar 3WV is ON, booster heater turn OFF. 
* Under solar priority is not set condition, solar 3WV only can ON during heating heat-up interval. 
 
6.  2 way valve opens. 
 
 
 
 
 
 
 
 
 
 
 
52 
Heat + Tank Mode (Heating priority not set)                      Tank set Temp. = 60°C 
 
On
Off
On
Off
3 ways valve
ID Water Pump
On
Off
Booster Heater
On
Off
Heat Pump
Interval Timer
Interval Timer
Tank side
Tank side
Room side
Switch to tank side even the heating
 interval timer not yet completed when
 tank temperature drop and tank termo on.
Turn to room heating interval compulsory
 and heat up room for the heating
 interval timer after [xxx] time of short
heating time. After room heating interval
timer, if tank thermo off heat pump will
continue at room side. (Turn to heating
side and run room heating interval
compulsory as well if tank temperature
cannot achieve within tank heat-up interval)
 
Page of 127
Display

Click on the first or last page to see other WH-MXC16G9E8 service manuals if exist.