Panasonic WH-MXC16G9E8 Service Manual ▷ View online
61
12.2 Water
Pump
12.2.1 Water Pump Control
Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes.
However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the
compressor should be OFF immediately and restart delay after 3 minutes.
compressor should be OFF immediately and restart delay after 3 minutes.
The system will start checking on the water flow level after operation start for 9 minutes. If water flow level is
detected low continuously 10 seconds, the water pump and the compressor will be OFF permanently and
OFF/ON control panel LED will blink (H62 error occurs).
OFF/ON control panel LED will blink (H62 error occurs).
When error happens, the power has to be reset to clear the error.
If there is no error indication, the water pump shall be continuously running.
The water pump will remain ON when compressor OFF due to thermostat OFF setting is reached.
Water pump must always operate during heating mode, deice operation and also during heater ON condition.
Water pump will stops 15 seconds after the unit stops operation.
t ≥ 9 min
YES
NO
NO
Flow
S/W
Status
tc < 1min
NG
STOP Water pump
OK
Water Pump Control
ON Water pump
YES
ERROR display at
Control Panel
ERROR reset by
power reset
62
12.2.2 A-class Pump Specification
+
Power for drive
DC280-373V
-
+
Power for control
DC15±10%
Control Signal
DC0V-DC6V
DC0V-DC6V
Feedback Speed
(puls signal)
4puls/rotation
(puls signal)
4puls/rotation
-
Pump
67
5
6
4
2
1
3
VDD
GND
VCC
FG
VSP
Control signal is analog voltage (DC0V-6V) generated by microcomputer PWM port.
Microcomputer can change analog voltage by changing PWM duty.
Microcomputer can change analog voltage by changing PWM duty.
12.2.3 Water Flow Rate Setting
Set water pump speed to adjust the water flow rate.
Depend on the hyraulic system pressure loss and type, the water flow rate can be adjusted by control panel.
Depend on the hyraulic system pressure loss and type, the water flow rate can be adjusted by control panel.
1 Press SERVICE button for 5 seconds.
2 Press
2 Press
▲
button to enter menu S02 and press SET button.
3 Press SELECT button then press
▲
/
▼
button to change SPEED and press SET to confirm.
4 Press OFF/ON button to quit setting.
0
10 13 20
30
40
50
60
70
1
2
3
4
5
6
7
110
120
130
100
90
80
70
60
50
40
30
20
10
80
70
60
50
40
30
20
10
0
WATER FLOW RATE (L/min)
EXTERNAL STAT
IC PRESSURE
(kPa)
N
O
T
AP
PL
IC
AB
LE
R
AN
GE
N
O
T
AP
PL
IC
AB
LE
R
AN
GE
Note:
* Before adjust the water flow rate, make sure that the total water volume in the installation is minimum 50 litres for
heating side.
* Please ensure the minimum flow rate is not less than 13l/min and not more than 50l/min.
63
12.2.4 Water Pump Speed Feedback Error
Basically pump speed feedback is control by micon.
When pump speed is below low limit or over high limit for a few seconds, micon detect pump error and
system is stopped.
Error detection conditions:
Current pump speed < 1000 rpm or
Current pump speed > 6000rpm for 10 seconds.
Control contents:
When error occurs, water pump, heating and heater is stopped for 30 seconds then restart again (Retry
control).
When micon detect error again, system is stopped and error code [H20] is displayed at control panel.
12.2.5 Water Pump Only Operation
Purpose
Circulate and fill the piping with water during installation time
Circulate and fill the piping with water during installation time
Water pump only circulation can be set from the control panel SERVICE S/W when the operation is in
Standby Mode.
Press the SERVICE S/W for continuous 5 sec to enter Service Mode.
In Service Mode, select SR: 02 and press SET S/W to start water pump only operation.
3 way valve turn OFF and 2 way valve turn ON.
Water pump will stop operation when H62 is triggered.
Press the OFF/ON button to stop the water pump only operation.
12.3 Pump Down Operation [Service Mode: 01]
Purpose
Ensure the pump down operation when relocating or disposing of the unit. The pump down operation will extract all
refrigerant from the piping into the outdoor unit.
Controls:
Ensure the pump down operation when relocating or disposing of the unit. The pump down operation will extract all
refrigerant from the piping into the outdoor unit.
Controls:
1 Press the SERVICE S/W for continuous 5 seconds to enter Service Mode.
2 In service mode, select Sr: 01 and press SET S/W to start Pump Down operation.
3 There will be no low pressure error and freeze prevention judgement during Pump Down operation.
4 3 ways valve will shift to room side and 2 ways valve will turn ON.
5 Press OFF/ON button to stop the unit.
2 In service mode, select Sr: 01 and press SET S/W to start Pump Down operation.
3 There will be no low pressure error and freeze prevention judgement during Pump Down operation.
4 3 ways valve will shift to room side and 2 ways valve will turn ON.
5 Press OFF/ON button to stop the unit.
12.4 Flow
Switch
12.4.1 Flow Switch Control
1 The water flow switch serves as an overload protector that shuts down the unit when the water level is
detected to be low.
2 Detection is Lo (0 V) when there is no water flow, and detection is Hi (5 V) when there is water flow.
64
12.5 Indoor Unit Safety
12.5.1 Indoor Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the indoor unit safety control
checking is restarted.
YES
YES
YES
NO to normal mode
10s
Flow SW ON?
Pump ON
Pump OFF
>10 mins
Water In > 80°C for 10s
12.6 Auto
Restart
Control
1 When the power supply is cut off during the operation of Air-to-Water Heatpump, the compressor will re-
operate after power supply resumes.
12.7 Indication
Panel
LED
Operation
Color
Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
If Operation LED is blinking, there is an abnormality operation occurs.
Click on the first or last page to see other WH-MXC16G9E8 service manuals if exist.