125 
16.5.33  Outdoor Pipe Temperature Sensor Abnormality (F42) 
 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature 
sensor are used to determine sensor error. 
 
Malfunction Caused: 
1.  Faulty connector connection. 
2.  Faulty sensor. 
3.  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
126 
16.5.34  Outdoor Defrost Temperature Sensor Abnormality (F43) 
 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost 
temperature sensor are used to determine sensor error. 
 
Malfunction Caused: 
1.  Faulty connector connection. 
2.  Faulty sensor. 
3.  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
127 
16.5.35  Indoor Water Outlet Temperature Sensor Abnormality (F45) 
 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet 
temperature sensor are used to determine sensor errors. 
 
Malfunction Caused: 
1.  Faulty connector connection. 
2.  Faulty sensor. 
3.  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
128 
16.5.36  Outdoor Current Transformer Open Circuit (F46) 
 
Malfunction Decision Conditions: 
A current transformer (CT) open circuit is detected by checking the compressor running frequency (≥ rated 
frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. 
 
Malfunction Caused: 
1.  CT defective. 
2.  Faulty outdoor unit PCB. 
3.  Compressor defective (low compression). 
 
Abnormality Judgment: 
Continue 3 times in 20 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 