DOWNLOAD Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ↓ Size: 16.42 MB | Pages: 127 in PDF or view online for FREE

Model
S-22KA1E5 S-28KA1E5 S-36KA1E5 S-45KA1E5 S-56KA1E5 S-63KA1E5 S-71KA1E5 S-22YA1E5 S-28YA1E5 S-36YA1E5 S-45YA1E5 S-56YA1E5 S-22NA1E5 S-28NA1E5 S-32NA1E5 S-36NA1E5 S-45NA1E5 S-56NA1E5 S-45MA1E5 S-56MA1E5 S-63MA1E5 S-7
Pages
127
Size
16.42 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
s-22ka1e5-s-28ka1e5-s-36ka1e5-s-45ka1e5-s-56ka1e5-.pdf
Date

Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ▷ View online

93 
Cautions
 
 
Carry out Earthing work. 
Do not connect the Earth return to the gas pipe, water line pipe, lightning rod and telephone lines. 
Imperfection in Earth return may lead to electric shock. 
 
Do not install the unit at the place where the possibility of inflammable gas leakage exists. If gas leakage should arise and the gas builds 
up around the unit, such situation may lead to ignition. 
 
Mounting of the earth leakage circuit breaker is required. Omission in mounting of the earth leakage circuit breaker may lead to electric 
shock. 
 
Drain piping should be made to ensure secure drainage according to the manual for installation work and carry out the thermal insulation 
to prevent the occurrence of condensation. 
Imperfection in piping work leads to water leakage and may cause the house and property, etc. to become wet. 
 
Position the indoor unit, outdoor unit, power cords and indoor/outdoor unit connection cables in a way so that they are at least 1 meter 
away from televisions and radios. This is to avoid problems such as interference with picture and/or sound. (However, note that 
depending on the electromagnetic wave conditions, interference may still occur even if the separation distance is more than 1 meter.) 
11.5.1 
ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER 
Name Q’ty  Appearance 
Purpose 
Drain hose with a clip 
 
For drain piping 
Heat insulator 
 
For insulating refrigerant pipe joint 
Band 4 
 
For fastening the heat insulator 
Flat washer for M10 
 
For fixing the hanging bolts 
Screw M5 
 
Set screw for paper model and panel fixing 
Installation Instruction 
 
This manual 
11.5.2 
SELECTING THE LOCATION FOR THE INDOOR UNIT 
Provide a check port on the piping side ceiling for repair and maintenance. 
x  Install the indoor unit once the following conditions are satisfied and after receiving the customer approval. 
1.  The indoor unit must be within a maintenance space. 
2.  The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading 
of air throughout the room. 
(Unit: mm)
Obstacles
Floor
(Unit: mm)
1000 or
more
500 or
more
500 or
more
500 or
more
2500 – 
3000
300 or
 les
s
Beam
 
 
ސ If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is 
decreased. 
 
Warnings
 
3.  The installation position must be able to support a load four times the indoor unit weight. 
4.  The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance. 
5.  The indoor unit must allow easy draining. 
6.  The indoor unit must allow easy connection to the outdoor unit. 
7.  Place the indoor unit according to the height from the ceiling shown in the table below. 
8.  The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring 
should be locally decided. 
9.  If the power supply is subject to noise generation, add a suppressor. 
10.  Do not install the indoor unit in a laundry. Electric shocks may result. 
11.  Before installing in quiet room such as a bedroom, please consult with an authorized distributor. 
 
 
 
94 
Note 
Ɣ
   Thoroughly study the following installation locations 
1.  In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo 
fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying, 
dispersing of water drops, drain pump malfunction, etc.  
In these cases, take the following actions: 
x  Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that 
it draws oily steam which should not flow into the suction of the air conditioner. 
x  Make enough distance from the cooking room to install the air conditioner in such place where it may not 
suck in oily steam. 
 
Air conditioner
Cooking table
Ensure ample
distance
 
 
2.  Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially 
in factories, etc. 
3.  Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked. 
4.  Avoid places where sulphurous acid gas or corrosive gas can be generated. 
5.  Avoid places near high frequency generators. 
 
Model name 
Height from the ceiling 
S-22YA1E5 S-28YA1E5 
S-36YA1E5 S-45YA1E5 
S-56YA1E5  
280mm or more 
11.5.3 
INSTALLATION OF INDOOR UNIT 
CEILING OPENING DIMENSIONS AND HANGING BOLT LOCATION 
 
The paper model for installation expand or shrink 
according to temperature and humidity.  
Check on dimensions before using it. 
Caution 
During the installation, care must be taken not to 
damage electric wires. 
x  The dimensions of the paper model for installation 
are the same as those of the ceiling opening 
dimensions. 
x  Be sure to discuss the ceiling drilling work with the 
workers concerned. 
 
This air conditioner uses a drain up motor. 
Horizontally install the unit using a level gauge. 
(Hanging bolt)
Drain pipe
(Unit: mm)
650 (
C
e
iling op
ening)
530 (
H
a
nging 
bolt
)
580 (
U
nit
 s
iz
e
)
580 (Unit size)
Refrigerant pipe
530
0
6
0
6
60
60
650 (Ceiling opening)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
95 
POSITIONS OF AIR CONDITIONER BODY AND CEILING SURFACE 
 
Flat washer for M10 (accessory)
Nut
(W3/8 or M10)
Flat washer for M10 (accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
M10 Spring washer
 
 
Warning
  Tighten the nut and bolt to prevent unit from falling
 
HANGING POSITION OF THE AIR CONDITIONER BODY 
 
Keep the length of the bolt
from the bracket to 40 mm
Ceiling
Adjust to the same height
Paper model
for installation
Set screw for
paper model
(4 pieces)
Open the ceiling board along the
other edge of the paper model.
Air conditioner body
113 m
m
2
82 m
m
292 m
m
and abov
e
 
11.5.4 REFRIGERANT 
PIPING 
Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit. (Additional 
charging, etc.) 
 
1. 
Brazing for piping. 
a.  Execute brazing before tightening the flare nut. 
b.  Brazing must be executed while blowing 
nitrogen gas. (This prevents generation of 
oxidized scale in copper pipe.) 
2. 
When there is a lot of brazings for long piping, 
install a strainer midway of the piping. (The 
strainer is locally supplied.) 
3. 
Use clean copper pipe with inner wall surface 
free from mist and dust. Blow nitrogen gas or air 
to blow off dust in the pipe before connection. 
4. 
Form the piping according to its routing. Avoid 
bending and bending back the same piping point 
more than three times. (This will result in 
hardening of the pipe). 
5. 
After deforming the pipe, align centers of the 
union fitting of the indoor unit and the piping, and 
tighten them firmly with wrenches. 
6. 
Connect pipe to the service valve in the outdoor 
unit. 
7. 
After completed the piping connection, be sure to 
check if there is gas leakage in indoor and 
outdoor connection. 
 
Union
round mark
 
 
x  Confirm the round mark of the union (thin side) is 
always at lower direction after connecting piping. 
 
 
 
 
Vacuum drying 
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. 
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves. 
 
CAUTION   Use two wrenches and tighten with regular torque. 
Flare nut fastening torque N•m (kgf•cm) 
 
Liquid side piping 
Gas side piping 
ø6.35mm 18 
(180) ø12.7mm 55 
(560) 
  ø6.35mm 
ø12.7mm 
96 
11.5.5 
INDOOR UNIT DRAIN PIPING 
x  Drain piping must have down-slope (1/50 to 
1/100); be sure not to provide up-and-down slope 
to prevent reversal flow. 
x  During drain piping connection, be careful not to 
exert extra force on the drain port at the indoor 
unit. 
x  The outside diameter of the drain connection at 
the indoor unit is 32 mm. 
Piping material: Polyvinyl chloride pipe VP-25 and 
pipe fittings.
 
x  Be sure to perform heat insulation on the drain 
piping. 
Heat insulation material: Polyethylene foam with 
thickness more than 8 mm (local supply).
 
 
 
Upward routing
Pipe clamp
Indoor
unit
Trap
Down-slope
 
 
x  The height of drain may be possible up to 750 mm. 
 
 
Down-slope (1/50 ~ 1/100)
Drain port
750 m
m
 or
 les
s
Indoor unit
Elbow
Elbow
 
 
x  When drain set piping, install as shown in the 
figure below. 
 
Drain Test 
The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain up motor 
operation. 
x  Connect the main drain pipe to exterior and leave 
it provisionally until the test comes to an end. 
x  Feed water to the flexible drain hose and check 
the piping for leakage. 
x  Be sure to check the drain up motor for normal 
operating and noise when electric wiring is 
complete. 
x  When the test is complete, connect the flexible 
drain hose to the drain port. 
Feed water
Drain hose
Drain up motor
Glue the joint
Drain hose connection
Use the clip (accessory)
Main drain
pipe
Drain
port
11.5.6 HEAT 
INSULATION 
Caution
 
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water 
leakage. 
 
1.  Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C). 
 
Overlap with heat
insulator for piping.
Indoor
unit
Band
(Accessory)
Heat insulator
for piping
(Local supply)
Heat insulator
(Accessory)
Hose clip (Accessory)
Heat insulator (Local
supply) (The thickness
must be at least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
PVC pipe
(O.D. ø25)
(Local supply)
To be glued
It may be required to take off this part for checking
or servicing the drain up motor. Please do not glue.
Make sure that there is no clearance here.
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 service manuals if exist.