DOWNLOAD Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ↓ Size: 16.42 MB | Pages: 127 in PDF or view online for FREE

Model
S-22KA1E5 S-28KA1E5 S-36KA1E5 S-45KA1E5 S-56KA1E5 S-63KA1E5 S-71KA1E5 S-22YA1E5 S-28YA1E5 S-36YA1E5 S-45YA1E5 S-56YA1E5 S-22NA1E5 S-28NA1E5 S-32NA1E5 S-36NA1E5 S-45NA1E5 S-56NA1E5 S-45MA1E5 S-56MA1E5 S-63MA1E5 S-7
Pages
127
Size
16.42 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
s-22ka1e5-s-28ka1e5-s-36ka1e5-s-45ka1e5-s-56ka1e5-.pdf
Date

Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ▷ View online

109 
x  Use the standard power cord for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) 
rating specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66) 
 
Outdoor unit
Branch pipe
Refrigerant pipe
Control cable
To other indoor unit
Indoor unit-A
Wired controller
Earth
Earth
Switch
Infrared remote controller
Receiver
Earth leakage breaker
Power supply
(ex. 1 ~ 230V)
Switch
Power supply
(ex. 1 ~ 230V)
Provide separate power supplies to the indoor and outdoor units.
Earth leakage breaker
 
 
x  Power supply specifications 
 
Power supply cable 
Circuit breaker 
(Minimum capacity) 
 
Model 
name 
Power 
supply 
Minimum power 
cable supply 
cables 
 
 1 
Length 
(m) 
 
Leakage 
current 
breaker 
(A) 
Switch 
(A) 
Fuse 
(A) 
 2 
Control 
Cable 
 
Remote 
Controller 
Cable 
 
Indoor unit 
220V-240V~ 
2 mm
2
 100  15A  15A  15A 
0.75 
mm
2
 
0.5 ~ 2 mm
2
 
 1. The maximum length shows a 2% voltage drop. 
 2. Use an unshielded bus transmission line. 
 
CONNECTING THE WIRES TO THE CONTROL BOX 
x  Remove the mounting screw, remove the control box cover, and then connect the wires by following the 
procedure given in the illustration. 
 
Control box cover
Detail of wire insertion
 
 
 
 
Earth lead wire shall be longer than other lead wires 
as shown in the figure for the electrical safety in case 
of the slipping out of the cord from anchorage. 
 
 
 
 
 
 
 
 
 
110 
11.6.8 SETTINGS 
  The automatic system settings can take up to 1 minute once power is supplied; do not operate the remote 
controller during this time. 
  In the event that 1 remote controller group control is not used, do not set up the group control address (A/C No.). 
The wired remote control will not display when the settings for the A/C No. are set to a value other than “01”. 
  Once the wires are connected to 1 remote controller group control and power is supplied to the indoor unit, the 
A/C No. is automatically set. To stop group control use, follow the directions below and clear the A/C No. that was 
automatically set after disconnecting the wires for group control. If it is not cleared then the wired controller will not 
show any display. 
x  Instructions on clearing the A/C No. after automatic setup 
Turn OFF the indoor unit power supply 
ĺ Using the DIP switch set the A/C No. to “16” ĺ Turn ON the power 
supply of the indoor unit 
ĺ After approximately 1 minute, turn OFF the power supply to the indoor unit ĺ Set 
the DIP switch for the A/C No. to “01”. 
(The next time the power supply is turned ON, the A/C No. will be cleared.) 
 Setting for 1 remote controller group control 
x  A maximum of 16 indoor units can be connected at the time of group control. (Do not connect the heat pump unit 
with the cooling only unit.) 
x  There are 2 methods for setting the group control address (A/C No.); an automatic and a manual setting method. 
x  The A/C No. setting cannot be confirmed when using the automatic method. 
x  To set each indoor unit’s A/C No., use the manual setting method. 
However, if the wall type indoor unit is connected, then manual setting is not possible. 
Ŷ Automatic setting 
x  By switching ON the indoor unit’s power supply with the DIP switch where the A/C No. is set to “01” (factory 
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic 
setting takes approximately one minute.) 
x  Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored. 
To reset the A/C No. setting, follow the instructions for the “group control automatic address reset”. Refer to 
the item “Local setting” in the installation instruction manual that comes with the wired controller for the 
“group control automatic address reset” method. 
* If the indoor unit’s A/C No. DIP switch is not set to “01”, the automatic setting cannot be reset. 
Ŷ Manual setting 
x  The manual setting is performed using each indoor unit’s printed circuit board DIP switch. (Refer to the 
diagram below) 
x  Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is 
turned ON, the stored A/C No. is recalled. 
x  To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch. 
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control. 
* Ensure to set the A/C No. to “01” for 1 indoor unit. 
 
A/C  No.
01
02
03
04
05
06
07
08
Indoor unit
printed circuit
board DIP switch
(SW2)
Unnecessary
operation
1-ON
2-ON
1,2-ON
3-ON
1,3-ON
2,3-ON
1,2,3-ON
A/C  No.
09
10
11
12
13
14
15
16
Indoor unit printed
circuit board DIP
switch (SW2)
4-ON
1,4-ON
2,4-ON
1,2,4-ON
3,4-ON
1,3,4-ON
2,3,4-ON
1,2,3,4-ON
 
 
(Refer to the remote controller’s installation instruction manual for the remote controller settings.) 
 
 
 
 
 
 
 
 
 
111 
11.6.9 
INSTALLATION OF DECORATIVE PANEL 
The decorative panel has its installation direction. Confirm the direction by displaying the piping side. 
 
1.  Remove the air inlet grill from the decorative panel. 
2.  Remove the corner cover in 4 corner places. 
Pull hook of corner cover as direction 
ƻ
1 ,  at  same 
time remove it by sliding out in direction 
ƻ
2 . 
 
Corner cover
Decorative panel
Hook
1
2
 
 
3.  Fix the hanger (2 pieces) of the decorative panel 
to the indoor unit. 
There is direction information at decorative panel 
[PIPING SIDE] indication meaning the direction of 
piping side. 
4.  Adjust between decorative panel fixing hole and 
indoor unit screw hole. 
5.  Fix decorative panel with 4 screws with already fix 
at paper model for installation. 
Before installing the decorative panel, always remove 
the paper template 
 
Hinge
Air inlet grill
 
 
* Hang the hinge on the hole of decorative panel.  
(The direction of the installation is free.) 
 
 
 
 
Caution
 
Install certainly the decorative panel. 
Cool air leakage causes sweating. 
ĺ Water drops fall. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
112 
Air conditioner unit
Decorative panel
Fit the insulator (this part) and be careful for cool air leakage.
Ceiling
Air
Good example
 
 
Decorative panel
Cool air leakage
(no good)
Air conditioner unit
Air
Bad example
Ceiling
 
6.  Adhere the cosmetic panel and ceiling wall 
together and confirm no gap in between. Readjust 
indoor unit height, if there is a gap between ceiling 
wall and decorative panel although it have been 
fixed by screw. 
If there are no effect to the indoor unit level and 
drain piping etc., the adjustment of indoor unit 
height can be adjusted through the corner cover 
hole. Tighten back firmly the fixing nut of indoor 
unit after adjustment has been made. 
7.  Open the indoor control box cover. (2 pcs) 
8.  Insert firmly the connector of cosmetic louver to 
indoor PCB CN-STM1 and CN-STM2. 
Be caution not to clamp the cord in between 
control board and control board cover. 
9.  After complete, install back removed part follow 
opposite procedure. 
 
Warning
 
Be sure to hook the air inlet grill string, to 
prevent grill from falling and causing injury 
from it. 
 
When using the infrared remote controller, refer to the 
instruction manual supplied with the infrared remote 
controller (option) and the infrared receiver (option) 
 
 
 
CN-STM1
CN-STM2
Clamp the lead wire with a
band here
Louver motor wire
 
 
 
 
 
 
11.6.10  AS FOR TIMER OUTPUT 
x  Connect the timer cord to connector (CN-TIMER) on print circuit board. 
 
Printed
circuit
board
Timer
Contact
Close: RUN
Open: STOP
d.c. 5V
CN-TIMER
2
1
Relay contact
Connector
Timer setting
 
x  The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd. 
x  Wiring must use vinyl code with the sheath or cable line diameter 0.3mm
2
x  The length of wiring should be within 150m and separated from power line in order to prevent malfunction. 
x  The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current 
suitable for this. 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 service manuals if exist.