DOWNLOAD Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ↓ Size: 16.42 MB | Pages: 127 in PDF or view online for FREE

Model
S-22KA1E5 S-28KA1E5 S-36KA1E5 S-45KA1E5 S-56KA1E5 S-63KA1E5 S-71KA1E5 S-22YA1E5 S-28YA1E5 S-36YA1E5 S-45YA1E5 S-56YA1E5 S-22NA1E5 S-28NA1E5 S-32NA1E5 S-36NA1E5 S-45NA1E5 S-56NA1E5 S-45MA1E5 S-56MA1E5 S-63MA1E5 S-7
Pages
127
Size
16.42 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
s-22ka1e5-s-28ka1e5-s-36ka1e5-s-45ka1e5-s-56ka1e5-.pdf
Date

Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual ▷ View online

121 
11.8.5 
INDOOR UNIT DRAIN PIPING 
x  Drain piping must have down-slope (1/50 to 
1/100); be sure not to provide up-and-down slope 
to prevent reversal flow. 
x  During drain piping connection, be careful not to 
exert extra force on the drain port at the indoor 
unit. 
x  The outside diameter of the drain connection at 
the indoor unit is 16 mm. 
Piping material: Polyvinyl chloride pipe VP-16 and 
pipe fittings.
 
x  Be sure to perform heat insulation on the drain 
piping. 
Heat insulation material: Polyethylene foam with 
thickness more than 8 mm (local supply).
 
 
 
Upward routing
Pipe clamp
Indoor
unit
Trap
Down-slope
11.8.6 HEAT 
INSULATION 
Caution
 
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water 
leakage. 
 
1.  Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C). 
 
Overlap with heat
insulator for piping.
Indoor
unit
Band
(Accessory)
Heat insulator
for piping
(Local supply)
Heat insulator
(Accessory)
Hose clip (Accessory)
Heat insulator (Local
supply) (The thickness
must be at least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
PVC pipe
(O.D. ø16)
(Local supply)
To be glued
It may be required to take off this part for checking
or servicing the drain up motor. Please do not glue.
Make sure that there is no clearance here.
 
 
2.  Precautions in high humidity circumstance. 
This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been 
confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point 
temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according 
to the following procedure: 
x  Heat insulation material to be prepared… 
Adiabatic glass wool with thickness 10 to 20 
mm. 
x  Stick glass wool on all air conditioners that are 
located in ceiling atmosphere. 
x  In addition to the normal heat insulation 
(thickness: more than 8 mm) for refrigerant 
piping (gas piping: thick piping) and drain 
piping, add a further of 10 mm to 30 mm 
thickness material. 
 
Pipe down
Indoor
unit
Pipe
Putty
Trap
Incision
Drain pipe
 
 
ސ Put the incision at the trap part of the heat insulator 
(for water drain)
Wall seal 
x  When the outdoor unit is installed on a higher position than the indoor unit, install the trap so as not to instill 
rain water into the wall by transmitting in piping. 
x  Stuff the space among piping, the electric wire, and the drain hose with “Putty” and seal the penetration wall 
hole. 
Make sure that rain water do not instill into the wall. 
 
 
 
 
 
122 
3.  The duct connection of the air outlet thermal insulation. 
 
Air outlet
Thermal insulation
(Local supply)
 
11.8.7 ELECTRICAL 
WIRING 
As to main power source and cable size of outdoor unit, read the installation manual attached to the outdoor unit. 
 
Warning
 
The units must be installed in accordance with applicable national and local regulations. 
The units installed by a professional installer must be supplied from a dedicated electrical circuit. 
All electric work must be carried out by a qualified technician according to proper technical standards for electrical work and 
according to installation manual for installation work. 
If circuits with insufficient capacity are used, or if electrical work is not carried out properly, electric shocks or fire may result. 
Caution
Be sure to install a current leakage breaker or circuit breaker to the main power supply, otherwise electric shocks may result. 
Caution
Be sure to connect the unit to secure earth connection. (with a earth resistance of 100 
ȍ or less). 
If the earthing work is not carried out properly, electric shocks may result. 
Warning
Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not 
transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc. 
 
1.  Select a power source that is capable of supplying the current required by the air conditioner. 
2.  Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should 
disconnected all poles with a contact separation of at least 3 mm. 
3.  Always ground the air conditioner with a grounding wire and screw to meet the LOCAL REGULATIONS. 
4.  Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires. 
5.  Be sure to turn off the main power before installing and connecting the remote controller. 
 
Note
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off after at least 1 
minute has passed. (For the system’s automatic setting.) 
Turning off the power supply on the way may cause an abnormal operation. 
 
x  Use the standard power cord for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) 
rating specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66) 
 
Outdoor unit
Branch pipe
Refrigerant pipe
Control cable
To other indoor unit
Indoor unit-A
Wired controller
Earth
Earth
Switch
Infrared remote controller
Receiver
Earth leakage breaker
Power supply
(ex. 1 ~ 230V)
Switch
Power supply
(ex. 1 ~ 230V)
Provide separate power supplies to the indoor and outdoor units.
Earth leakage breaker
 
 
 
 
 
 
 
 
 
 
 
 
 
123 
x  Power supply specifications 
 
Power supply cable 
Circuit breaker 
(Minimum capacity) 
 
Model 
name 
Power 
supply 
Minimum power 
cable supply 
cables 
 
 1 
Length 
(m) 
 
Leakage 
current 
breaker 
(A) 
Switch 
(A) 
Fuse 
(A) 
 2 
Control 
Cable 
 
Remote 
Controller 
Cable 
 
Indoor unit 
220V-240V~ 
2 mm
2
 100  15A  15A  15A 
0.75 
mm
2
 
0.5 ~ 2 mm
2
 
 1. The maximum length shows a 2% voltage drop. 
 2. Use an unshielded bus transmission line. 
 
CONNECTING THE WIRES TO THE CONTROL BOX 
x  Remove the mounting screw, remove the control box cover, and then connect the wires by following the 
procedure given in the illustration. 
Screw
Control box cover
Control box
 
 
 
11.8.8 SETTINGS 
  The automatic system settings can take up to 1 minute once power is supplied; do not operate the remote 
controller during this time. 
  In the event that 1 remote controller group control is not used, do not set up the group control address (A/C No.). 
The wired remote control will not display when the settings for the A/C No. are set to a value other than “01”. 
  Once the wires are connected to 1 remote controller group control and power is supplied to the indoor unit, the 
A/C No. is automatically set. To stop group control use, follow the directions below and clear the A/C No. that was 
automatically set after disconnecting the wires for group control. If it is not cleared then the wired controller will not 
show any display. 
x  Instructions on clearing the A/C No. after automatic setup 
Turn OFF the indoor unit power supply 
ĺ Using the DIP switch set the A/C No. to “16” ĺ Turn ON the power 
supply of the indoor unit 
ĺ After approximately 1 minute, turn OFF the power supply to the indoor unit ĺ Set 
the DIP switch for the A/C No. to “01”. 
(The next time the power supply is turned ON, the A/C No. will be cleared.) 
Setting for 1 remote controller group control 
x  A maximum of 16 indoor units can be connected at the time of group control. (Do not connect the heat pump unit 
with the cooling only unit.) 
x  There are 2 methods for setting the group control address (A/C No.); an automatic and a manual setting method. 
x  The A/C No. setting cannot be confirmed when using the automatic method. 
124 
x  To set each indoor unit’s A/C No., use the manual setting method. 
However, if the wall type indoor unit is connected, then manual setting is not possible. 
Ŷ Automatic setting 
x  By switching ON the indoor unit’s power supply with the DIP switch where the A/C No. is set to “01” (factory 
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic 
setting takes approximately one minute.) 
x  Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored. 
To reset the A/C No. setting, follow the instructions for the “group control automatic address reset”. Refer to 
the item “Local setting” in the installation instruction manual that comes with the wired controller for the 
“group control automatic address reset” method. 
* If the indoor unit’s A/C No. DIP switch is not set to “01”, the automatic setting cannot be reset. 
Ŷ Manual setting 
x  The manual setting is performed using each indoor unit’s printed circuit board DIP switch. (Refer to the 
diagram below) 
x  Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is 
turned ON, the stored A/C No. is recalled. 
x  To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch. 
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control. 
* Ensure to set the A/C No. to “01” for 1 indoor unit. 
 
A/C  No.
01
02
03
04
05
06
07
08
Indoor unit
printed circuit
board DIP switch
(SW2)
Unnecessary
operation
1-ON
2-ON
1,2-ON
3-ON
1,3-ON
2,3-ON
1,2,3-ON
A/C  No.
09
10
11
12
13
14
15
16
Indoor unit printed
circuit board DIP
switch (SW2)
4-ON
1,4-ON
2,4-ON
1,2,4-ON
3,4-ON
1,3,4-ON
2,3,4-ON
1,2,3,4-ON
 
 
(Refer to the remote controller’s installation instruction manual for the remote controller settings.) 
11.8.9 
AS FOR TIMER OUTPUT 
x  Connect the timer cord to connector (CN-TIMER) on print circuit board. 
 
Printed
circuit
board
Timer
Contact
Close: RUN
Open: STOP
d.c. 5V
CN-TIMER
2
1
Relay contact
Connector
Timer setting
 
x  The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd. 
x  Wiring must use vinyl code with the sheath or cable line diameter 0.3mm
2
x  The length of wiring should be within 150m and separated from power line in order to prevent malfunction. 
x  The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current 
suitable for this. 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 service manuals if exist.