10.4 Automatic operation 
 
Automatic operation can be set using remote control. 
Operation mode is determined by set temperature of remote control, indoor intake temperature. 
This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature. 
After judged the temperature, the operation mode is determined by referring below standard. 
 
 
10.5  Indoor Fan Speed Control 
Indoor fan speed can be set using remote control. 
10.5.1 Fan Speed rotation Chart  
speed 
Model MODE 
Hi/Shi Me Lo 
Lo- Slo 
COOLING/SOFT DRY
1040 
900 
750
710 
500 
CS-YW7MKD(-1) 
HEATING 1060 
680 
540
500 
450 
COOLING/SOFT DRY
1060 
920 
750
710 
500 
CS-YW9MKD(-1) 
HEATING 1080 
740 
590
540 
500 
COOLING/SOFT DRY
1060 
950 
800
760 
500 
CS-YW12MKD(-1) 
HEATING 1080 
840 
680
610 
500 
 
10.5.2 Automatic Fan Speed Control 
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in 
the table. 
 
   
Shi  Hi 
Me 
Lo 
Lo- 
SLo 
SSLo
Auto 
   
  o 
   
   
  o 
   
Cooling 
Manual     
  o 
  o 
 
   
   
Auto 
   
   
   
   
  o 
   
Soft Dry 
Area 
Manual     
   
   
   
  o 
   
Auto 
   
   
  o 
  o 
  o 
  o 
Heating 
Manual    o     
  o 
  o 
   
  o 
 
Auto Fan Speed during cooling operation:- 
1.  At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing 
purpose. 
2.  Indoor fan will rotate alternately between off and on as shown in below diagram. 
 
 
26 
       *1.  Fan speed will be at Hi till the compressors ceases when set temperature is reached. 
        *2. Fan Speed will be at Me when the compressor restarts. 
 
Auto Fan Speed during soft Dry operation. 
1.  Indoor fan will rotate alternately between OFF and Lo-. 
2.  At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for deodorizing 
purpose. 
 
                   
 
 
 
10.5.3 Manual Fan Speed Control 
Manual fan speed can be set with Fan Speed selection button at the remote control 
There are 3 level of fan speed setting : Lo, Me, Hi 
 
10.6  Outdoor Fan Speed Control 
There is only one speed for outdoor fan motor. 
When compressor stops, outdoor fan will continue running for 30 seconds. 
 
10.7  Vertical Airflow Direction Control. 
The louver can be adjusted by pressing the button at remote control to the desired position. 
When operation stops using remote control, the discharge vent is reset, and stop at the closing position.. 
 
Operation mode 
 
   
 
 
   
 
 
   
 
 
   
 
 
   
 
Manual 18
°
 28
°
 37
°
 46
°
 55
°
 
Cooling/ Soft Dry 
Auto 18
°
  ~  55
°
 
Manual 18
°
 34
°
 50
°
 64
°
 79
°
 
Heating 
Auto 18
°
,  79
°
 
Manual 
Depending on remote control setting 
During judgment 
Auto 18
°
 
 
 
10.8  Horizontal Airflow Direction Control 
Horizontal airflow direction louver can be adjusted manually by hand. 
 
10.9 Timer Control 
Timer can be set using remote control (12-hour timer setting). When Timer- ON is set for cooling and Soft Dry 
operation, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable 
environment when reaching the set ON time. 
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time. 
For Heating operation, the operation will start 30 minutes before the set time. 
27 
For Automatic operation, the indoor fan will operate at Slo speed for 25 seconds, 30 minutes before the set time 
to detect the intake air temperature to determine the operation mode. The power LED will blink during detection. 
If main power supply is switched off or encounter power failure, timer setting will be cancel. Timer needs to be 
reset 
The ON timer or OFF timer will be cancel by pressing CANCEL button. 
The ON timer or OFF timer will be cancel is ON/OFF operation button is pressed. 
Each timer setting is effective only once.  
If power failure occurs during timer operation, timer will be canceled. Reset timer when power is resumed. 
 
10.10 Random Auto Restart Control 
If there is a power failure during operation, the air conditioner will automatically restart after 2 minutes when the 
power is resumed. 
It will start with previous operation mode and airflow direction. 
If timer is set, timer setting will be cancel. The timer needs to be reset after the power is resumed. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
28 
 
11.    Protection Control 
11.1    Restart Control (Time Delay Safety Control) 
•  When the thermo-off temperature is reach during Cooling operation, the compressor stops for 3 minutes  
(minimum) before resume operation. 
•  When the thermo-off temperature is reach during Soft Dry operation, the compressor stops for 6 minutes 
(minimum) before resume operation. 
•  This control is not applicable if the power supply is cut off and on again. 
•  This phenomenon is to balance the pressure inside the refrigerant cycle. 
11.2  7 minutes Time Save Control 
The compressor will automatically operate if it has stopped for 7 minutes even if the room temperature Is not 
reached the Thermo-ON point. 
This phenomenon is to prevent the room humidity raising. 
 
11.3  60 seconds Forced Operation 
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in normal operation even if 
the intake air temperature has reached the thermo-off point. However, forced stop by pressing the OFF/ON 
operation button at the remote control is permitted.  
This phenomenon is to allow the refrigerant oil run in a full cycle and return back to the outdoor unit. 
11.4    30 Seconds Forced Operation 
•  Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation 
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the 
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit. 
•  The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a 
full cycle and return back to the outdoor unit. 
11.5 Anti-Freezing Control 
If the temperature of evaporator is lower than 2℃ continuously for 4 minutes, the compressor will cease to 
prevent the evaporator from freezing. Fan Speed setting will not be changed. 
When temperature of evaporator reach 10℃, compressor will restart. 
During Cooling and soft Dry operation, the Time Delay Safety Control will be applied if the recovery time is too 
short. 
 
 
11.6  Compressor Reverse Rotation Protection Control 
z  During Cooling or Soft Dry operation:- 
If the compressor has been continuously running for 5 minutes or longer, and the difference of temperature between 
intake air and evaporator is continuously lower than 2.5℃ or below for 2 minutes, the compressor will stop, and then 
restart 3 minutes later. (Time Delay Safety Control is effective.) 
 
 
 
 
△  T= Intake air temperature – Indoor heat exchanger temperature 
Compressor runs ≥ 5 min 
△T≤ 2.5℃ last for 2 min 
Compressor stops 
Compressor restarts 3 minutes later 