Automatic Fan Speed Mode
Time Graph for cooling Operation
During Cooling Mode Operation, use remote control to select Automatic Fan Speed.
     • 
• 
• 
• Fan speed will be at the point between "high speed" and "medium speed".
     • 
• 
• 
• Deodorization control.
17
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
Time Delay Safety Protection
Anti Freezing Control
Compressor Protection Control
Anti-reverse Control
Automatic Fan Speed
7.2. Soft Dry Mode Operation
     • 
• 
• 
• When selecting Soft Dry mode operation, the operation will be cooling until the room temperature reaches the set temp on the
remote control, and then Soft Dry will be activated. (During Soft Dry Mode the fan of indoor unit will operate at super low speed.)
     • 
• 
• 
• Once soft Dry mode operation is turned off, indoor fan, compressor and outdoor fan will stop for 6 minutes.
     • 
• 
• 
• During cooling mode operation, if the compressor ceased, it will not restart within 3 minutes.
     • 
• 
• 
• Same as the denotation in Cooling Operation. (P.16)
(During Soft Dry Mode Operation, compressor will stop for at least 6 min.)
     • 
• 
• 
• Same as the denotation in Cooling Operation. (P.16)
     • 
• 
• 
• Same as the denotation in Cooling Operation. (P.16)
During Soft Dry Operation, use remote control to select Auto Fan Speed mode.
     • 
• 
• 
• Indoor Fan Speed is at super low.
     • 
• 
• 
• Deodorization control.
18
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
Time Graph for soft dry operation
19
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
Time Delay Safety Protection Control
Overload Protection Control
Compressor Protection Control
Anti-Reversing Protection
4-way Valve Control
Warm booting control
     • 
• 
• 
• When turning on the unit by heating mode operation, indoor
fan will be activated when temperature of indoor heat
exchanger reaches 30°C.
     • 
• 
• 
• Warm booting operation ends when temperature of indoor
heat exchanger reaches 34 °C.
     • 
• 
• 
• During warm booting or within 3 minutes after the ending
the Ry-C will not turn off.
7.3. Heating Mode Operation (For CS-SA7CKP ONLY)
When selecting heating mode operation, the unit will operate according to the setting by the remote control.
     • 
• 
• 
• If the compressor stopped by switching off,turning off by remote control, or power off, it will not restart within 3 minutes.
     • 
• 
• 
• When room temperature reaches the set temperature on the remote control, compressor stops and will not restart within 4
minutes.
     • 
• 
• 
• 3 minutes after the compressor stopped, indoor fan will stop for 1 minute. Then indoor fan will resume operation with the speed
at "super low".
     • 
• 
• 
• When temperature of indoor heat exchanger rises to 51°C, outdoor fan will stop when temperature of indoor heat exchanger
falls to 49°C, outdoor fan will restart.
     • 
• 
• 
• When temperature of indoor heat exchanger rises to 65°C or above, compressor stops, and will restart 4 minutes later.
     • 
• 
• 
• Same as the denotation in Cooling Operation.(P.16)
     • 
• 
• 
• If the compressor has been running for 5 minutes, but the difference of temperature between intake air and indoor heat
exchanger is continuously lower than 5°C for 2 minutes, compressor will stop and resume operation in 4 minutes.
     • 
• 
• 
• During heating mode operation, 4-way valve is at "open" mode.
     • 
• 
• 
• During heating mode operation, if the unit turned off , the 4-way valve will remain at "open" mode for 5 minutes.