8.5. In case of embedded Piping
For the embedded piping
Follow the same procedure for left rear and left piping.
8.5.1. Replace the drain hose
8.5.2. Bend the embedded piping
     • 
• 
• 
• Use a spring bender or equivalent to bend the piping so that
the piping is not crushed.
8.5.3. Install the indoor unit.
8.5.4. Cut and flaring the embedded
piping
     • 
• 
• 
• When determining the dimensions of the piping, slide the
unit all the way to the left on the installation plate.
     • 
• 
• 
• Refer to the section “cut and flaring the piping” in the
directions for the outdoor unit. (see P.33)
8.5.5. Pull the connecting cable into the
indoor unit.
8.5.6. Connecting the piping
     • 
• 
• 
• Refer to the section "connecting the piping" in the directions
for the indoor unit.
(Connecting the piping to the outdoor unit and checking the
gas leakage.)
8.5.7. Connecting the cable to the indoor
unit
     • 
• 
• 
• The cable can be connected without removing the front
grille.
Fig.a
8.5.8. Install the indoor unit fixly.
[REFERENCE Fig.a, Fig.b]
Fig.b
37
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
8.5.9. Connecting piping of the outdoor
unit
     • 
• 
• 
• In case of electronic parts damages caused by water
entering the unit from the piping hole, the piping should be
wrapped by a sponge pad and taped.
     • 
• 
• 
• When connecting the right side piping, cut the heat
insulation layer about 40-50mm, and tape it.
     • 
• 
• 
• When bending the piping, ensure the semi-diameter should
at least be 150-160mm.
     • 
• 
• 
• Seperate the two piping by the length about 30cm.
     • 
• 
• 
• Always use a bender for bending pipings.
38
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
8.6.1. Connecting the piping to outdoor
unit
 1. Align the centre of the piping and sufficiently tighten the
flare nut with fingers.
 2. Finally tighten the flare nut with torque wrench until the
wrench clicks.
" When tightening the flare nut with torque wrench, ensure
the direction for tightening follows the arrow of the wrench.
Model
Piping side
Torque
SA7CKP
Liquid side 1/4"
18N.m
SC7CKP
Gas side 3/8"
42N.m
Caution
When connecting the piping,always use a torque wrench.Other
tools may cause damage to the flare nut because of improper
force.
 3. Ensure not to let the piping exposed to air.
8.6.2. Connecting the cable
 1. Remove the top cover from the unit by loosening the four
screws.
 2. Remove the control board cover by loosening the screw.
 3. Connect the locally approved cable (indicated in the table
below) to the terminals on the control board individually.
 4. Secure the cable onto the control board with the holder
(clamp).
 5. Attach the control board cover and the top cover to the
original position with the screws.
Specification of the connecting cables
Notes:
CS-SA7CKP for example.
For CS-SC7CKP,No plug and terminal 3,4.
8.6. Connecting piping and the cable to outdoor unit
39
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
8.7.1. Checking the drainage
 1. Remove the front grille from the cabinet
When removing the front grille for maintenance purposes,
etc, carry out by the following procedures.
 a. Set the vertical airflow direction louver (1) to the
horizontal position.
 b. Remove the two caps on the front grille as shown in the
illustration at right,and then remove the two mounting
screws.
 c. 
Pull the lower section of the front grille toward you to
remove the front grille.
When reinstalling the front grille,first set the vertical airflow
direction louver to the horizontal position, and then carry out
by steps 3 and 2 in that order. At this time check to sure that
the fixing tabs on the top inside edge of the front grille are
securely inserted into the respective slots.
 2. Checking the drainage
     • 
• 
• 
• Pour a glass of water into the drain traystyroform.
     • 
• 
• 
• Ensure water flows out from drain hose of indoor unit.
 3. Drainage control for outdoor unit(For CS-SA7CKP only)
     • 
• 
• 
• If a drainage plug is applied,the outdoor unit should at
least be 3 centimeters high from the floor.
     • 
• 
• 
• If is better not to use the drainage plug if the
temperature is lower than 0°C, since icing of the
condensed water may block the water flow.
8.7. Checking the drainage and connecting the cable to indoor unit
40
CS-SA7CKP / CU-SA7CKP5 / CS-SC7CKP / CU-SC7CKP5
Page of 70