Time Delay Safety Control
Automatic Restarting Control
Anti-freezing Control
•
•
•
• If temperature of evaporator is lower than 2°C continuously
for 4 minutes, the compressor will cease to prevent the
evaporator from freezing. Fan speed setting will not be
changed.
evaporator from freezing. Fan speed setting will not be
changed.
•
•
•
• When
temperature
of
evaporator
reaches
10°C,
compressor will restart.
During Cooling Mode Operation, the Time Delay Safety Control
is available.
is available.
Compressor Protection Control
Anti-reversing Control
7 Operation Details
7.1. Cooling Mode Operation
•
•
•
• When selecting the Cooling Mode Operation, the unit will operate according to the setting by the Remote Control and the
operation is as the following.
•
•
•
• 3 min. ---- The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
•
•
•
• (Protection of compressor).
•
•
•
• 7 min. ---- The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
•
•
•
• If the outdoor fan motor does not run 50 seconds after the compressor starts, the compressor will cease and restart in 3
minutes.(Time Delay Safety Control is effective.)
•
•
•
• If this symptom occurs repeatedly 3 times, the compressor will stop.
•
•
•
• If the operation mode changed or the unit turned off by remote control, Compressor Protection Control will be reset
(for CS-SA7CKP/CU-SA7CKP5 only).
•
•
•
• If the compressor has been continuously running for 5 minutes, and the difference of temperature between intake air and
evaporator is continuously lower than 2.5°C for 2 minutes, the compressor is ceased for 3 minutes then restarts. (Time Delay
Protection Control is effective.)