C. Diagnosis Code Table
Code
Abnormality/Protection
Judgment
Check
Emergency
Operation
H11
Indoor/Outdoor abnormal
communication
>1minute after
starting
operation
Connecting cable, Indoor /outdoor PCB
O
H14
Indoor intake air temp sensor
abnormality
-
Intake air temperature sensor
( defected or disconnected)
X
H15
Outdoor
compressor
temperature
sensor abnormality
Continue for 5
sec.
Compressor temperature
sensor(defected or disconnected)
X
H16
Outdoor current transformer
open circuit
-
Outdoor PCB, IPM module
X
H19
Indoor fan lock
-
Indoor PCB, fan motor
X
H23
Indoor heat exchanger
temperature A sensor
Continue for 5
sec
Heat exchanger temperature sensor
(defected or disconnected)
O
H24
Indoor heat exchanger
temperature B sensor
Continue for 5
sec
Heat exchanger temperature sensor B
(defected or disconnected)
O
H25
Air filter abnormality
-
O
H27
Outdoor air temperature sensor
abnormality
Continue for 5
sec
Outdoor temperature sensor
(defected or disconnected)
O
H28
Outdoor heat exchanger
temperature sensor
abnormality
Continue for 5
sec.
Outdoor heat exchanger sensor
(defected or disconnected)
O
H30
Discharge temperature sensor
abnormality
Continue for 5
sec.
Discharge temperature sensor
(defected or disconnected)
O
H33
Incorrect connection of
Indoor/Outdoor cable
-
Indoor/outdoor supply voltage
X
H97
Outdoor fan motor lock
Twice within
20 sec.
Outdoor fan motor
X
H98
Indoor high pressure
protection
-
Air filter dirty
Air circulation short circuit
-
H99
Indoor heat exchanger
anti-freezing protection
Indoor heat
exchanger
freezing
Insufficient refrigerant
Air filter dirty
-
F11
Cooling/heating cycle
change over abnormality
4 times occurrence
within 30 minutes
4-way valve
V-coil
X
F16
Cooling/Dry cycle changeover
abnormality
4 times occurrence
within 30 minutes
Indoor PCB
X
F90
PFC control
4 times occurrence
within 20 minutes
Voltage at PFC
X
F91
Refrigeration cycle abnormality
2 times occurrence
within 20 minutes
No refrigerant(3-way valve is closed)
X
F93
Compressor abnormality
4 times occurrence
within 20 minutes
Compressor
X
F95
Cool high pressure protection
4 times occurrence
within 20 minutes
Outdoor refrigeration cycle
X
F96
IPM overheating protection
-
Excessive refrigerantImproper heat radiationIPM X
F97
Outdoor
compressoroverheating
protection
4 times occurrence
within 20 minutes
Insufficient refrigerantCompressor
X
F98
Total running currentprotection
3 times occurrence
within 20 minutes
Excess
refrigerantImproper
radiationOutdoor
PCBIPMCompressor
X
F99
Outdoor
Peak
CurrentProtection
Control
4 times occurrence
continuously
within
30 minutes
X
33
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
8.Internal Setting Temperature
Intake temperature is based on the set temperature of remote control and temperature shifting.
 1. Cool/Dry/Heat
 2. Auto
Once the operation starts, remote controller setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment. The
final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical
power is supplied to the unit.
34
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
Table A Outdoor Temperature Shifting
Table B Fan Speed Shifting
Table C Start-up Shifting
Cool/Dry
60 minutes from start-up
-1.0
Heat
60 minutes from start-up
-2.0
35
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
A. Frequency Shifting
7.4. Cooling Operation
The frequency for compressor is changed every 30 seconds, and the intake air temperature is measured every second.
After the start-up of the compressor, If the difference between the intake temperature and intake set temperature maintains a
specified value for a while, the frequency will change as below.
Maximum and Minimum Frequency For Cool and Dry
PE9CKE
PE12CKE
Normal
Max.
49
64
Min.
17
17
Dry
Max.
27
34
Min.
22
28
Fc
45
58
Minimum Frequency For Cool and Dry
Fan Speed
PE9CKE
PE12CKE
>Hi
30
37
>Me-
28
35
>Me-
27
34
Auto
27
34
36