5.4-way Valve Control
 1. The 4-way valve will be turned on as the compressor starts to operate and remains on all the time during the heating
operation.
 2. The 4-way valve remains on for less than 3 minutes after heating operation is stopped.
 3. The 4-way valve remains off during cooling and soft dry operation.
 4. If the operation is shifted from cooling or dry to heating mode, the switching of 4-way valve will be delayed for 3 minutes.
 5. Heating Operation Mode
Four minutes after the start of the operation, if the indoor piping temperature detected is lower than 0°C, the operation will
stop.( Restarts in 3 minutes) If this situation happens 4 times within 30 minutes, error code “F11” will be displayed.
 6. Cooling Operation Mode
Four minutes after the start of the operation, if the indoor piping temperature detected is higher than 45°C, the operation will
stop ( Restarts in 3minutes). If this situation happens 4 times within 30 minutes, error code “F11” will be displayed.
29
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
6.Airflow Direction Control
A. Vertical Airflow Direction
Vane Angle
Cool/Dry
Manual Airflow
138°
131°
124°
117°
108°
Auto Airflow
108-138°
Heat
Manual Airflow
138°
123°
107°
91°
75°
Auto
AirflowDirectio
n
A
131°
B
84°
C
138°
ModeJudging
Manual Airflow
Same to Cool/Dry
Auto Airflow
138°
Detecting of Timer-ON Operation
138°
Notes:
Manual Airflow Direction: The vertical airflow vane will be fixed at the angle desired according to the instructions of
remote controller no matter the operation is cooling, soft dry or heating mode.
Auto Airflow Direction:
Cool/Dry: The vertical airflow vane will swing up and down within the range indicated below.
Heat: The vertical airflow vane will change according to indoor piping temperature.
30
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
B.Angular Speed of Vertical Vane
Vertical Airflow Vane
Airflow Direction Changes or Vertical Airflow Vane Closes
22.06/s
Swings Up and Down (Auto Airflow Direction)
2.21~5.52/s
C. Mode Judgement for Auto Operation
Airflow Mode Setting
Auto
Manual
Initializing When Power-On
Upper Limit
Lower Limit
Auto Operation
Upper Limit
Position Previously Set
Shifted to Auto Mode
Same to Cool/Dry/Heat
Same to Cool/Dry/Heat
Note:
When the air-conditioner is turned on, if manual airflow direction is selected and the angle is lower than the lower limit
for heating operation, the airflow direction will be changed to the lower limit for heating mode. If Cooling operation is
determined during the mode judgement, the airflow direction will be shifted to lower limit for cooling operation.
D. About Timer-Setting
During On-Timer operation, the airflow direction can be changed between Manual and Auto.
31
CS-PE9CKE / CU-PE9CKE / CS-PE12CKE / CU-PE12CKE
7.Self Diagnosis
A. About Self Diagnosis
When the air-conditioner is stopped due to malfunction detected by itself, the operation can be restarted using AUTO Switch
on the indoor unit. In forced operation, the frequency for compressor and fan speed can not be changed and the signal
receiving sound is different.
Normal Operation ON: “Pep”
Forced Operation ON: “Pep”, “Pep”, “Pep”, “Pep”
Stop: “Pep”
Note: Refer to the Diagnosis Code Table for the malfunction when forced operation is not available.
B. Display of Error Code
 1. Keeping the CHECK button on the remote controller depressed for 5 seconds, error code ranging from H11 to H99 can
be displayed on the remote controller.
 2. The error code is changed and diagnosis signal is transmitted to the indoor unit by pressing the Temp Up button on the
remote control.
 3. When the malfunction of the air-conditioner matches the error code on the remote control, four beeps can be heard from
the indoor unit and the operation indicator will light up.
 4. Keep the CHECK button depressed continuously for 5 seconds to cancel the diagnosis function.
32