49
2
Remove the cover of control board and holder
Removal Procedure For Electronic Controller
4. Release the lead wire CN-FM, CN-VF, CN-STM, CN-DISP and
earth wire(Yellow/Green). Take out the sensor from the socket.
Pull out the whole electronic controller.
Removal Procedure For the Discharge Grille
1. Separate the drain hose and the drain plate(Fig.10)
Fig 10
2. Pull out the discharge grille slightly (Fig. 11)
Fig. 11
CS-PC12DKD / CU-PC12DKD / CS-PA12DKD / CU-PA12DKD
3
Break off the earing ,release the holder slightly.
Be sure to avoid cracking of the holder.
1
Remove indicador complete
Afer removing the front grille, loose the screw behind the indicator,
the whole indicator can be released.
5. Remove the whole control board
Loose the screw s of control board,earings slightly, then the whole
control board can be pulled out.
Indicator Complete
Holder
Earing
Fig 6
Fig 7
Fig 8
Fig 9
Removal Procedure For Cross Flow Fan
Remote control reset
If the display is chaotic or can not be adjusted,
Remove the back lid of the remote control
and you will find the resetting terminals and
shorten the two terminals using a screw driver
to reset.
Resetting terminals
Fig 16
50
1.
(Fig. 12)
Release the two fixing screws,disassembly the fixing board from
evaporator on the left side of the evaporator and pull out the whole
evaporator.
2.Loose the fixing screw of the cross flow fan. (Fig. 13)
Fig. 12
Fig. 13
Fixing Screw
3.After removing the bearing (refer to fig14) , indoor fan can be
taken out from the left side.
Bearing
4. Lift up the indoor fan slightly, and then pull the fan motor out.
Fig15
Fig 15
Fan motor
Fig 14
CS-PC12DKD / CU-PC12DKD / CS-PA12DKD / CU-PA12DKD
fixing board
Screw
51
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of compressor or fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
Normal pressure and outlet air temperature(standard)
Cooling mode
Gas side pressure
Mpa
(kg/cm G)
2
0.4~0.6(4~6)
12~16
Outlet air
temperature
(
)
Condition: indoor fan speed: high
outdoor temperature:
35
(Cooling mode)
7
(Heating mode)
Difference in the
intake and outlet
air temperature
More than 8
(15 minutes afte an
operation is started) at the cooling mode
Normal
Measuring electric current
during operation
Measuring gas side
pressure
Less than 14
at the heating mode.
Value of electric
current
during operation
Higher than
specified
Dusty heat exchanger
preventing heat radiation
Excessive amount
of refrigerant
Lower than specified
Gas side pressure
Cooling
mode
High
Low
Low
Inefficient compressor
Insufficient refrigerant
clogged strainer or
capillary tube
12.1. Refrigeration cycle system
12 Troubleshooting Guide
Measuring the air
temperature difference
Heating mode
1.5~2.1(15~21)
36~45
More than 14
(15 minutes afte an
operation is started)
at the heating mode
Less than 8
at the cooling mode.
Inefficient compressor
Insufficient refrigerant
clogged strainer or
capillary tube
Low
Low
Heating
mode
Low
CS-PC12DKD / CU-PC12DKD / CS-PA12DKD / CU-PA12DKD
52
Condition of the air
conditioner
Insufficient refrigerant
(gas leakage)
Clogged capillary
tube
Short circuit in the
indoor unit
Heat radiation deficiency
of the outdoor unit
Insufficient
compression
Cooling mode
Low pressure
High pressure
Electric current
during operation
12.2.
Relationship between the condition of air conditioner and pressrue
and electric current
12.3. Diagnosis methods of a malfunction of a compressor .
Nature of fault
Insufficient compressing
of a compressor
Locked compressor
Symptom
Electric current during operation becomes approximately 80% lower
than the normal level.
The discharge tube of the compressor becomes abnormally hot
(normally 70~90
).
The difference between high pressure and low pressure becomes
almost zero.
Electric current reaches a high level abnormally, and the value exceeds
the limit of an ammeter. In some cases, a breaker turns off.
The compressor has a humming sound.
Inefficient switches of
the 4-way valves
Electric current during operation becomes approximately 20% lower than
the normal valve.
The temperature difference between from the discharge tube to the 4-way
valve and from suction tube to the 4-way valve becomes almost zero.
Low pressure
High pressure
Electric current
during operation
Heating mode