Is circulation of air adequate?
Is draining smooth?
Is heat insulation complete (refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is remote controller switch operated?
Is there any faulty wiring?
Are the terminal screws loosened?
M3...69-98 N.cm {7-10 kgf.cm}
M4...157-196 N.cm {16-20 kgf.cm}
M5...196-245 N.cm {20-25 kgf.cm}
 • First, press the OFF/ON ( ) button.
 • Then press the TEST RUN button within 1 minute of pressing the OFF/ON ( )
button.
 • Next, select the operation modes.
 • The temperature of the indoor unit pipes will be shown on the temperature setting
display. (At the start of the test operation, it may take up to 1 minute for air
conditioner number, switching time and other displays to appear.)
 • After operation modes have been selected, stop the compressor for a moment.
 • Press the OFF/ON ( ) button of the TEST RUN button once more to cancel test
operation mode.
NOTE 1
These units are equipped with connection error prevention circuits. If the units do not operate, it is possible that the
connection error prevention circuits have operated. In such cases, check that the power wires (connected to terminals
and
) and the control wires
) are connected correctly. If they are connected incorrectly, connect them correctly. Normal
operation should then commence.
NOTE 2
Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.)
Once the cause of the short is eliminated, normal operation will then be possible.
NOTE 3
When running the units in heating mode during test operation, be sure to run the units in cooling mode first before selecting
this mode. If heating mode is selected first, it may cause problems with operation of the compressor. (Heat pump model only.)
NOTE 4
Test operation should be carried out for a minimum of 5 minutes. (Test operation will be cancelled automatically after 30
minutes.)
NOTE 5
Test operation mode should always be cancelled once test operation itself has been completed.
10.4.11. Check the following items when installation is complete
 • After completing work, be sure to measure and record trial run properties, and store measuring data, etc.
 • Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind
volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, compressive
pressure, airtight pressure.
 • As to the structure and appearance, check the following items .
10.4.12. Hand over
 • Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature
control, etc.)
As to parts to be sold separately
 • With regards to installation of the parts sold separately, follow the installation manual which is provided with the parts sold
separately
As for work specifications of the outdoor unit, read the OUTDOOR UNIT INSTALLATION MANUAL attached to the outdoor
unit.
49
This mark means “Caution” or “Warning”.
This mark means “Earth”.
10.5. Outdoor unit installation
AIR CONDITIONERS OUTDOOR UNIT INSTALLATION INSTRUCTIONS
Precautions in terms of safety
Carry out installation work with reliability after thorough reading of this “Precautions in terms of safety”.
 • Precautions shown here are differentiated between
Warnings
and
Cautions . Those that have much chances for
leading to significant result such as fatality or serious injury if wrong installation would have been carried out are listed compiling
them especially into the column of
Warnings .
However, even in the case of items which are listed in the column of
Cautions , such items also have a chance for leading
to significant result depending on the situations.
In either case, important descriptions regarding the safety are listed, then observe them without fail.
 • As to indications with illustration
 • After installation work has been completed, do not only make sure that the unit is free from any abnormal condition through the
execution of try run but also explain how to use and how to perform maintenance of this unit to the customer according to the
instruction manual.
In addition, request the customer to keep this manual for installation work together with instruction manual.
Warnings
The appliance must be installed by technician, who takes into
account the requirements given by ISO5149 or eventual
equivalent requirements.
If installing inside a small room, measures should be taken to
prevent refrigerant levels from building up to critical
concentrations in the event of a refrigerant leak occurring.
Please discuss with the place of purchase for advice on what
measures may be necessary to prevent critical concentrations
being exceeded. If the refrigerant leaks and reaches critical
concentration levels, there is the danger that death from
suffocation may result.
As to installation, request the distributor or vendor to perform it.
Imperfection in installation caused by that having been carried
out by the customer himself may lead to water leakage, electric
shock, fire, etc.
Securely attach the protective covers for the outdoor unit
connection cables and power cord so that they do not lift up
after installation. If the covers are not properly attached and
installed, the terminal connections may overheat, and fire or
electric shock may result.
Carry out the installation work with reliability according to this
manual for installation work.
Imperfection in installation leads to water leakage, electric
shock, fire, etc.
Switch off all supplies before accessing any electrical part.
Carry out the installation work with reliability on the place that
can bear the weight of this unit sufficiently. Insufficient strength
leads to injury due to falling of the unit.
If refrigerant gas escapes during installation, ventilate the
affected area. If the refrigerant gas comes into contact with
sparks or naked flames, it will cause toxic gases to be
generated.
Carry out predetermined installation work in preparation for
strong wind such as typhoon, earthquake.
Imperfection in installation work may lead to accidents arisen
from overturn, etc.
Once installation work is completed, check that there are no
refrigerant gas in the room that can come into contact with
sparks or flames from a fan heater, stove or kitchen range,
which will cause toxic gases to be generated.
The unit must be installed in accordance with applicable national
and local regulations.
Any electrical work should only be carried out by qualified
technician and use exclusive circuits without fail.
Presence of insufficient capacity in power circuit or imperfection
in execution leads to electric shock, fire, etc.
When performing piping work do not mix air except for specified
refrigerant (R410A) in refrigeration cycle. It causes capacity
down, and risk of explosion and injury due to high tension inside
the refrigerant cycle.
50
Part name
Q’ty
Diagram
Application
Protective
bushing
2
For protecting electrical
wires
Banding
strap
3
For tying electrical wires
together
Heat pump-types only
Part name
Q’ty
Diagram
Application
Drain elbow AS
1
For connecting the drain
pipe (with ring seat)
Warnings
Wiring shall be connected securely using specified cables and
fix them securely so that external force of the cables may not
transfer to the terminal connection section.
Imperfect connection and fixing leads to fire, etc.
Cautions
Carry out Earthing work.
Do not connect the Earth return to the gas pipe,
water line pipe, lightning rod and telephone lines.
Imperfection in Earth return may lead to electric
shock.
Drain piping should be made to ensure secure drainage
according to the manual for installation work and carry out the
thermal insulation to prevent the occurrence of condensation.
Imperfection in piping work leads to water leakage and may
cause the house and property, etc. to become wet
Do not install the unit at the place where the possibility of
inflammable gas leakage exists. If such gas leakages should arise
and the gas builds up around the unit, such situation may lead to
ignition.
Position the indoor unit and outdoor unit, power cords and
indoor/outdoor unit connection cables in a way so that they are
at least 1 meter away from televisions and radios.
This is to avoid problem such as interference with picture and/or
sound. (However, note that depending on the electromagnetic
wave conditions, interference may still occur even if the
separation distance is more than 1 meter.)
Mounting of the earth leakage circuit breaker is required.
Omission in mounting of the earth leakage circuit breaker may
lead to electric shock.
10.5.1. Accessories supplied with outdoor unit
 • The following parts are supplied as accessories with each outdoor unit.
Check that all accessory parts are present before installing the outdoor unit.
10.5.2. Before installation work
 • This product is using new refrigeration (R410A). The basic way of installation work is the same as usual, but water and
impurities should be controlled more strictly than before due to characteristic of refrigerating machine oil. Therefore, selection
of materials to use and processing, storing and brazing need appropriate construction and control.
 1. Tools and materials
There are tools and materials for both new refrigeration and usual refrigeration you can use together and for either two of
them you can use. Use the below for new refrigeration.
 − Vacuum pump (with back flow preventor system)
 − Gas leakage detection warning device
 − Gauge manifold
 − Charge hose
 2. Installation work
 a. Brazing work
Brazing work needs replacing air inside pipe with nitrogen gas in order to prevent oxidation scale from occurring. This
is called nitrogen replacement, and one of very important work in brazing refrigerant piping. (Oxidation preventive is not
possible to use)
51
 b. Prevention measure for refrigerant piping
Prevention measure for refrigerant piping is very important work to prevent water-dust-rubbish from getting in. All piping
terminals needs sealing such as shown below.
Place
Period of work
Method of seal
Outside
More than 1 month
Pinch
Less than 1 month
Pinch or taping
Inside
Not specified
 − How to pinch
Close terminal part of piping with pliers and seal the gap with brazing.
 − How to tape
Seal terminal part of piping with vinyl tape.
 3. Vacuum pumping
The purpose of vacuum pumping work is to remove and dry air inside the piping or nitrogen at air tightness test.
Perform the work carefully.
Caution
Use the vacuum pump with the backflow prevention mechanism to prevent backflow of oil.
Vacuuming time
60 minutes or more
Vacuum pump capacity
60 l/min or more
 4. Refrigerant filling
Refrigerant filling must be done in the state of liquid refrigerant. If this is done in gas refrigerant, the balance of refrigerant
composition will collapse and damage the operation.