9 Operation Control
9.1. Operation mode
 1. Thermostat control
 2. Depend on differences between room temperature and setting temperature, Compressor running frequency will be decided and
start operation.
Temperature differences become same as below table, then thermostat is off.
Temperature Differences
Unit: °C
Indoor type
Cassette
Ceiling
Duct D1
Duct D2
Duct D3
Cool mode
-1.5
-1.5
-2.0
-2.0
-2.0
Dry mode
-2.5
-2.5
-3.0
-3.0
-3.0
Heat mode
3.5
2.5
2.5
2.5
2.5
 3. Select indoor temperature thermostat
When connected to wired remote controller, either indoor unit thermostat or remote controller thermostat is available, using
remote control setting.
9.2. Compressor start control
 • When the compressor start, compressor frequency will be fixed at lower level for certain time, to follow the below table, due to
avoid the compressor oil discharge.
 • Judging from compressor discharge temperature, decide the start condition to select either cool start control, or warm start
control.
Discharge temp. [°C]
>15°C
15°C
Start control
Warm start
Cool start
Warm start : set 1
→ *set 5 → normal control
Cool start : set 1
→ set 2 → set 3 → set 4 → *set 5 → normal control
 • Note
 − Frequency at *set 5 = frequency calculated by normal control
 − In case of frequency at set n (set 1, set 2 or set 3) excess the frequency at set 5 in cool condition, skip from set n (set 1,
set 2 or set 3) to set 4 and transfer to set 5.
9.3. Cooling operation
9.3.1. Cool indoor fan control
 • Fan speed manual
Operation start at hi speed, or medium speed, or low speed set by remote control.
 • Fan speed auto
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, odour cut operation (refer odour
cut operation page for detail), after thermostat ON condition, indoor fan operate as below control.
When 1st thermostat on condition from operation start, fan speed is hi (same as manual fan speed), after 2nd thermostat on
condition, fan speed change to medium speed (same as manual medium fan speed).
29
9.3.2. Odour cut control
 • When cool or dry mode operation start, select odour cut mode or fan auto mode, by remote control, operation start at odour
wash mode when compressor start or shift to thermostat on from thermostat off.
 • Odour cut operation is under below condition.
Operation mode
Cool or dry mode
Odour wash setting
Setting
No setting
Fan setting
Auto
Odour cut
Odour cut
Manual
Odour cut
-
 • Odour cut operation is to remove the odour generated at indoor heat exchanger to use the drain water come out from indoor
heat exchanger.
9.3.3. Cool powerful operation
 • When cool or dry mode operation start, temperature differences between room temperature and setting temperature is more
than 5 K, setting temperature shift to 2 K down.
 • (But when temperature after shifting is less than 16°C, setting temperature is 16°C = no change)
 • Micro computer judge that required indoor load is bigger than calculation base from temperature differences between room
temperature and setting temperature, then increase the compressor frequency compared to normal to cool down indoor side
immediately.
 • Those kind of operation complete after 30 minutes when cool mode operation start.
9.3.4. Freezing prevention control
 • During cool or dry mode operation, if indoor evaporator temperature is going down, freezing prevention control is operated.
 • Detail of Freezing prevention control is as follows;
Indoor evaporator temperature area is divided into 5 zones, which consist of stop zone, down zone, no change zone, up zone,
and recovery zone. When indoor evaporator temperature is going into each zone, compressor frequency change by following
the below table.
Recovery zone
Release freezing prevention operation
Up zone
Fan motor speed step up
No change zone
Operation no change
Down zone
Reduce the compressor frequency
(check for 3 min, max 3 times)
Stop zone
If continue for 6 min, compressor stop
(for 3 min after stop, compressor can be started due to restart delay control)
30
9.4. Heating mode operation
9.3.5. Dew form prevention control
 • During cool or dry operation, if outdoor temperature is less than 30°C, and indoor fan speed is low or auto setting, indoor heat
exchanger temperature become lower, dew form prevention control start to prevention dew form at indoor discharge grill.
 • Indoor evaporator temperature area is divided into 4 zones, which consist of, down zone, no change zone, up zone, and
recovery zone.
 • When indoor evaporator temperature is going into each zone, change compressor frequency and louver angle by following the
below table.
Recovery zone
Release dew form prevention operation
Up zone
Fix the indoor louver angle
Ceiling type : fix the manual 2nd position
No change zone
Continue check the indoor heat exchanger temperature
Down zone
Reduce the compressor frequency
(check for 3 min, max 3 times)
9.3.6. Cooling low temperature protection control
 • During cooling, or dry operation, if outdoor temperature is less than -15°C.
 − And thermostat on condition continue for 15 min, compressor stop.
 − After 3 min waiting (restart delay), if thermostat is on, compressor restart.
9.4.1. Heating indoor fan control
Fan speed manual
 • Fan speed [Hi] [Me] [Lo] set by remote controller.
 • However, when operation start, or during operation, fan speed control is limited to due to prevent a cold draft, for example, when
heating operation start.
31
Fan speed auto
 • When operation start, or during operation, fan speed control by detecting indoor heat exchanger as follows:
9.4.2. Hot start control
 • When heating operation start, hot start control carry out.
 • During hot start operation, [PREHEAT] displayed at the wired remote controller.
 • For wireless remote controller, [POWER LED] is blinking at the receiver of indoor unit. Indoor fan stop and louver angle fixed
to upper side in spite of any setting of remote controller. When indoor heat exchanger temperature increase, or 4 minutes past
after operation start, hot start control finish and shift to normal fan control.
9.4.3. Cold draught prevention control
 • This control is to prevent cold draught during heating mode operation.
 • The operation will start when the compressor is OFF (thermostat off) during heating operation.
 • Initially, the AC indoor fan motor will operate at Lo speed for 2 minutes.
 • After this, the AC indoor fan stops for 3 minutes and then operates at Lo speed for 10 seconds. And this operation repeats as
cold draught prevention control is on.
 • The cold draught prevention control stops when the compressor is ON (thermostat on).
9.4.4. Heating powerful operation
 • When heating mode operation start, temperature differences between setting temperature and room temperature is more than
5 K, setting temperature increase 2 K and operation start.
(however, setting temperature after shifting is more than 31°C, setting temperature fixed 31°C.)
 • Due to this control, micro computer judge indoor heat loss is big and increase compressor frequency compare to normal
condition, then heat up indoor room quickly.
 • This control will be finished after 60 min or thermostat is off.
9.4.5. Defrost control
 • During heating operation at outdoor low temperature condition, defrost operation start timely to melt the ice formed on outdoor
heat exchanger.
 • When heating operation accumulated time is time up, and both outdoor temperature and outdoor unit heat exchanger
temperature is less than setting temperature for 5 minutes. When defrost temperature is more than setting temperature, defrost
operation finish.