Flare nut fastening torque N.m (kgf.cm)
ø6.35 mm
18 (180)
ø15.88 mm
65 (660)
ø9.52 mm
42 (430)
ø19.05 mm
100 (1020)
ø12.7 mm
55 (560)
 • Be sure to use the drain hose provided (accessory item.)
 • Drain piping must have down-slope (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reversal flow.
 • During drain piping connection, be careful not to exert extra
force on the drain port at the indoor unit.
 • The outside diameter of the drain connection at the indoor
unit is 20 mm.
Piping material: Polyvinyl chloride pipe VP-20 and pipe fittings
Heat insulation material: Polyethylene foam with thickness more
than 8mm (local supply).
Liquid side piping
Gas side piping
ø9.52 mm
ø15.88 mm
10.4.4. Refrigerant piping
Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit.(Additional charging,
etc.)
 1. Brazing for piping.
 a. Execute brazing before tightening the flare nut.
 b. Brazing must be executed while blowing nitrogen gas.
(This prevents generation of oxidized scale in copper pipe.)
 2. When there is a lot of brazing for long piping, install a strainer at the midway of the piping.
(The strainer is locally supplied.)
 3. Use clean copper pipe with inner wall surface free from mist and dust. Blow nitrogen gas or air to blow off dust in the pipe before
connection.
 4. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times.
(This will result in hardening of the pipe).
 5. After deforming the pipe, align centers of the union fitting of the indoor unit and the piping and tighten them firmly with wrenches.
 6. Connect pipe to the service valve or ball valve which is located below the outdoor unit.
 7. After completed the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection.
 • Confirm the red mark of the union (thin side) is always at lower direction after connecting piping.
Vacuum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.
CAUTION Use two wrenches and tighten with regular torque.
10.4.5. Indoor unit drain piping
45
Be sure to perform heat insulation on the drain piping.
Caution
If insulation is insufficient, dew may form.
This causes water leakage.
Prevent the drain hose from floating and hanging
Caution
down.
This causes water leakage. (down figure)
Wall seal
 • When the outdoor unit is installed on a higher position
than the indoor unit, install the trap so as not to instill
rain water into the wall by transmitted in piping.
 • Stuff the space among piping, the electric wire, and the
drain hose with “Putty” and seal the penetration wall
hole.
Make sure that rain water do not instill into the wall.
In the case of left piping
 1. Remove both the internal and external plugs.
 2. Use a wrench or pliers to remove the plugs.
 • Putting substitution of rubber plug.
Drain Test
Confirm the drain water flows smoothly after connecting the
drain piping.
 • Pour water to about 1.5 liters for the drain confirmation from
the air inlet part which should gradually flow into the drain
pan.
10.4.6. Heat insulation
Caution
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water
leakage.
 1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 100°C).
 2. Precautions in high humidity circumstance.
This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been confirmed that there
is no form of any faults. However, if it is operated for a long time in high humid atmosphere (dew point temperature: more than
23°C), water drops are liable to fall.
 • In addition to the normal heat insulation (thickness: more than 8 mm) for refrigerant piping (gas piping: thick piping) and
drain piping, add a further of 10 mm to 30 mm thickness material.
46
CONNECTING THE WIRES TO THE CONTROL BOX
 • Remove a two mounting screw, remove the control box
cover, and then connect the wires by following the
procedure given in the illustration.
Caution Make sure that screws of the terminal are securely
tightened.
10.4.7. Electrical wiring
As to the main power source and cable size of outdoor unit, read the installation manual attached to the outdoor unit.
Warning
The units must be connected to the supply cables for fixed wiring by qualified technician.
Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should disconnected all
poles with a contact separation of at least 3mm.
When the supply cable is damaged, it must be replaced by qualified technician.
Caution
Be sure to install a current leakage breaker, main switch and fuse to the main power supply, otherwise electric shocks may
result.
Caution
Be sure to connect the unit to secure earth connection.
If the earthing work is not carried out properly, electric shock may result.
Warning
Wiring shall be connected securely using specified cables and fix them securely so that external force of the cables may not
transfer to the terminal connection section. Imperfect connection and fixing leads to fire, etc.
 1. Select a power source that is capable of supplying the current required by the air conditioner.
 2. Be sure to connect the wires correctly to terminal board with connecting the crimp type ring terminal to the wires.
 3. Be sure to turn off the main power before installing and connecting the remote controller.
Note
If momentarily turning on the power supply for both the indoor and outdoor units, do not turn the power off after again until at
least 1 minute has passed. (for the system’s automatic setting.)
Turning off the power supply on the way may cause an abnormal operation.
 • Use the standard power cord for Europe (such as HO5RN-F or HO7RN-F which conforms to CENELEC (HAR) rating
specifications) or use the cable based on IEC standard. (245IEC57, 245IEC66)
47
10.4.8. Settings
Do not operate the remote controller within 1 minute after turning on the power of the indoor unit.
When using group control with the standard type, at least 1 unit must be set at No.1 at the indoor unit.
Check the settings of the indoor unit in a case where there are no display at remote controller. If there is no problem to the settings,
either group control or standard type should be set at No.16 at the indoor unit before turning the power on again.
 • All sets in the group which uses the same remote controller thermistor settings can be controlled by the same remote controller
thermistor.
 • Up to a maximum of 16 indoor units can be connected at the time of group control. (Do not connect heat pump unit with cooling
only unit.)
 • Indoor unit No. will be set automatically at the time of group control. However, which indoor unit uses which number is unknown.
Indoor unit No. is also possible to be set manually with DIP switches. Since manual address setting has priority to automatic
address setting. To perform automatic address settings after doing manual setting, turn off all DIP switches from No.1 to No.4,
and then stop the operation. Then press three switches such as [AIR SWING AUTO]. [MODE]. [A/C No.] at the same time. (Do
not use manual address setting and automatic address setting together.)
 • Centralized control is possible for master unit and slave unit at the time of group control.
(Remote Control Address Setting)
(Refer to the Operation Manual which is provided with the remote controller for details.)
 • Two remote controllers (including the wireless remote controller) can be connected. However, remote control thermistor
setting is not possible.
 • As for [master/slave] setting of remote controller, the automatic setting and manual setting are possible. Since manual
setting is priority.
 • Two remote controllers, which both are wireless, cannot be connected.
10.4.9. As for timer output
 • Connect the timer cord to connector (CN-TIMER) on print circuit board.
10.4.10. Precautions in test run
 • The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner may not operate.
 • Test operation can be carried out using the remote control unit or at the outdoor unit. (If carrying out test operation at the
outdoor unit, refer to “TEST OPERATION” in the outdoor unit installation manual.)
 • If using the remote control unit to carry out test operation, follow the procedure given below.
48