DOWNLOAD Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Service Manual ↓ Size: 28.51 MB | Pages: 127 in PDF or view online for FREE

Model
CS-F24DTE5 CU-L24DBE5 CS-F28DTE5 CU-L28DBE5 CS-F34DTE5 CU-L34DBE5 CS-F43DTE5 CU-L43DBE5 CS-F50DTE5 CU-L50DBE8
Pages
127
Size
28.51 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-f24dte5-cu-l24dbe5-cs-f28dte5-cu-l28dbe5-cs-f34.pdf
Date

Panasonic CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 Service Manual ▷ View online

This mark means “Caution” or “Warning”.
This mark means “Earth”.
10.4. Indoor unit installation
CEILING TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS
Precautions in terms of safety
Carry out installation work with reliability after throughout reading of this “Precautions in terms of safety”.
 • Precautions shown here are differentiated between
Warnings
and
Cautions . Those that have much chance for
leading to significant result such as fatality or serious injury if wrong installation would have been carried out are listed compiling
them especially into the column of
Warnings .
However, even in the case of items which are listed in the column of
Cautions , such items also have a chance for leading
to significant result depending on the situations.
In either case, important descriptions regarding the safety are listed, then observe them without fail.
 • As to indications with illustration
 • After installation work has been completed, do not only make sure that the unit is free from any abnormal condition through the
execution of trial run but also explain how to use and how to perform maintenance of this unit to the customer according to the
instruction manual.
In addition, request the customer to keep this manual for installation work together with instruction manual.
Warnings
The appliance must be installed by technician, who takes into
account the requirements given by ISO5149 or eventual
equivalent requirements.
If installing inside a small room, measures should be taken to
prevent refrigerant levels from building up to critical
concentrations in the event of a refrigerant leak occurring.
Please discuss with the place of purchase for advice on what
measures may be necessary to prevent critical concentrations
being exceeded. If the refrigerant leaks and reaches critical
concentration levels, there is the danger that death from
suffocation may result.
As to installation, request the distributor or vendor to perform it.
Imperfection in installation caused by that having been carried
out by the customer himself may leads to water leakage, electric
shock, fire, etc.
Securely attach the protective covers for the outdoor unit
connection cables and power cord so that they do not lift up
after installation. If the covers are not properly attached and
installed, the terminal connections may overheat, and fire or
electric shock may result.
Carry out the installation work with reliability according to this
manual for installation work.
Imperfection in installation leads to water leakage, electric shock,
fire, etc.
Switch off all supplies before accessing any electrical part.
Carry out the installation work with reliability on the place that
can bear the weight of this unit sufficiently. Insufficient strength
leads to injury due to falling of the unit.
If refrigerant gas escapes during installation, ventilate the
affected area. If the refrigerant gas comes into contact with
sparks or naked flames, it will cause toxic gases to be
generated.
Carry out predetermined installation work in preparation for
strong wind such as typhoon, earthquake. Imperfection in
installation work may lead to accidents arisen from overturn, etc.
Once installation work is completed, check that there are no
refrigerant gas in the room that can come into contact with
sparks or flames from a fan heater, stove or kitchen range,
which will cause toxic gases to be generated.
The unit must be installed in accordance with applicable national
and local regulations. Any electrical work should only be carried
out by qualified technician and use exclusive circuits without fail.
Presence of insufficient capacity in power circuit or imperfection
in execution leads to electric shock, fire, etc.
When performing piping work do not mix air except for specified
refrigerant (R410A) in refrigeration cycle. it causes capacity
down, and risk of explosion and injury due to high tension inside
the refrigerant cycle.
Wiring shall be connected using specified cables and fix them
securely so that external force of the cables may not transfer to
the terminal connection section.
Imperfect connection and fixing leads to fire, etc.
41
Cautions
Carry out Earthing work.
Do not connect the Earth return to the gas pipe,
water line pipe, lightning rod and telephone lines.
Imperfection in Earth return may lead to electric
shock.
Drain piping should be made to ensure secure drainage
according to the manual for installation work and carry out the
thermal insulation to prevent the occurrence of condensation.
Imperfection in piping work lead to water leakage and may
cause the house and property, etc. to become wet
Do not install the unit at the place where the possibility of
inflammable gas leakage exists. If gas leakage should arise and
the gas builds up around the unit, such situation may lead to
ignition.
Position the indoor unit and outdoor unit, power cords and
indoor/outdoor unit connection cables in a way so that they are
at least 1 meter away from televisions and radios.
This is to avoid problem such as interference with picture and/or
sound. (However, note that depending on the electromagnetic
wave conditions, interference may still occur even if the
separation distance is more than 1 meter.)
Mounting of the earth leakage circuit breaker is required.
Omission in mounting of the earth leakage circuit breaker may
lead to electric shock.
10.4.1. Accessories packed in the indoor unit container
Name
Q’ty
Appearance
Purpose
Name
Q’ty
Appearance
Purpose
Band
2
For fastening the heat
insulator
Drain hose
1
For drain piping
Edge protection
cover
1
To protect the end surface
of the piping holes
Heat insulator
1
For insulating refrigerant
pipe joint
10.4.2. Selecting the location for indoor unit
Provide a check port on the piping side ceiling for repair and maintenance.
 • Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
 1. The indoor unit must keep a maintenance space.
 2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air throughout
the room.
 3. The installation position must be able to support a load four times the indoor unit weight.
Warnings
 4. The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
 5. The indoor unit must allow easy draining.
 6. The indoor unit must allow easy connection to the outdoor unit.
 7. The indoor unit must allow easy connection to the outdoor unit.
 8. The indoor unit must be at least 3m away from any noise-generating equipment. The electrical wiring must be shielded with
a steel conduit.
 9. If the power supply is subject to noise generation, add a suppressor.
 10. Do not install the indoor unit at a laundry. Electric shocks may result.
NOTE
 • Study throughly the following installation locations.
 1. In places such as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, and the fin of the heat
exchanger may result in heat exchange reduction, spraying or dispersing of water drops, etc.
In these cases, take the following actions:
42
 1. Open the inlet grille, and remove the side cover fixing screw
(right and left) from the internal part of the unit.
 2. Move the side cover to about 15mm forward to remove it.
Use the packing material (Styrene foam) to support, when
you reverse the top and bottom of the indoor unit.
 3. Remove the hanging bracket
 a. Remove the slip prevention screws of the brackets (right
and left).
 b. Loosen the hanging bracket fastening bolts to about
10mm, and remove the hanging bracket.
 • Make sure the ventilation fan for smoke-collection hood on a cooking table has sufficient capacity so that it draws oily steam
which should not flow into the suction of the air conditioner.
 • Make enough distance from cooking room to install the air conditioner in such place where it may not suck in oily steam.
 2. Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist especially in factories, etc.
 3. Avoid places where inflammable gas can be generated, flows-in, contaminated, or leak.
 4. Avoid places where sulphurous acid gas or corrosive gas can be generated.
 5. Avoid places near high frequency generators.
10.4.3. Installation of indoor unit
The paper template for installation may expand or shrink according to temperature and humidity. Check the dimensions before using it.
CEILING OPENING DIMENSIONS AND HANGING BOLT LOCATION
Caution
During the installation, care must be taken not to damage the electric wires.
REMOVING THE SIDE COVER AND HANGING BRACKET
43
* Use either W3/8 or M10 bolts and nuts (local supplied)
 • Fastening the hanging bracket
Warning
Be sure to tighten the nut and bolt to prevent the
unit from falling.
Fastening the hanging bracket
Piping hole positions
 • The refrigerant piping can be installed on the right, right upper or right rear.
 • The drain piping can be installed on the right, right rear, left or left rear (there are connection ports on both right and left sides.)
 • Thermally insulate the drain and refrigerant piping to prevent dew condensation.
 • After cutting the piping holes, use the edge protection cover (accessory) to protect the end surfaces.
Installing the unit
 1. Insert the hanging bracket fastening bolts and both sides of the unit into the hanging brackets, and slide the unit to the rear.
Fasten the bolts.
 2. Tighten the slip prevention screws (M5) for brackets to prevent the unit from shifting.
 3. To ensure correct drainage, after hanging the unit, use a level gauge to check the installation angle.
44
Page of 127
Display

Click on the first or last page to see other CS-F24DTE5 / CU-L24DBE5 / CS-F28DTE5 / CU-L28DBE5 / CS-F34DTE5 / CU-L34DBE5 / CS-F43DTE5 / CU-L43DBE5 / CS-F50DTE5 / CU-L50DBE8 service manuals if exist.