9.4. Heating mode operation
9.3.5. Dew form prevention control
 • During cool or dry operation, if outdoor temperature is less than 30°C, and indoor fan speed is low or auto setting, indoor heat
exchanger temperature become lower, dew form prevention control start to prevention dew form at indoor discharge grill.
 • Indoor evaporator temperature area is divided into 4 zones, which consist of, down zone, no change zone, up zone, and
recovery zone.
 • When indoor evaporator temperature is going into each zone, change compressor frequency and louver angle by following the
below table.
Recovery zone
Release dew form prevention operation
Up zone
Fix the indoor louver angle
Ceiling type : fix the manual 2nd position
No change zone
Continue check the indoor heat exchanger temperature
Down zone
Reduce the compressor frequency
(check for 3 min, max 3 times)
9.3.6. Cooling low temperature protection control
 • During cooling, or dry operation, if outdoor temperature is less than -15°C.
 − And thermostat on condition continue for 15 min, compressor stop.
 − After 3 min waiting (restart delay), if thermostat is on, compressor restart.
9.4.1. Heating indoor fan control
Fan speed manual
 • Fan speed [Hi] [Me] [Lo] set by remote controller.
 • However, when operation start, or during operation, fan speed control is limited to due to prevent a cold draft, for example, when
heating operation start.
21
CS-F18DTE5 CU-L34DBE5 /
Fan speed auto
 • When operation start, or during operation, fan speed control by detecting indoor heat exchanger as follows:
9.4.2. Hot start control
 • When heating operation start, hot start control carry out.
 • During hot start operation, [PREHEAT] displayed at the wired remote controller.
 • For wireless remote controller, [POWER LED] is blinking at the receiver of indoor unit. Indoor fan stop and louver angle fixed
to upper side in spite of any setting of remote controller. When indoor heat exchanger temperature increase, or 4 minutes past
after operation start, hot start control finish and shift to normal fan control.
9.4.3. Cold draught prevention control
 • This control is to prevent cold draught during heating mode operation.
 • The operation will start when the compressor is OFF (thermostat off) during heating operation.
 • Initially, the AC indoor fan motor will operate at Lo speed for 2 minutes.
 • After this, the AC indoor fan stops for 3 minutes and then operates at Lo speed for 10 seconds. And this operation repeats as
cold draught prevention control is on.
 • The cold draught prevention control stops when the compressor is ON (thermostat on).
9.4.4. Heating powerful operation
 • When heating mode operation start, temperature differences between setting temperature and room temperature is more than
5 K, setting temperature increase 2 K and operation start.
(however, setting temperature after shifting is more than 31°C, setting temperature fixed 31°C.)
 • Due to this control, micro computer judge indoor heat loss is big and increase compressor frequency compare to normal
condition, then heat up indoor room quickly.
 • This control will be finished after 60 min or thermostat is off.
9.4.5. Defrost control
 • During heating operation at outdoor low temperature condition, defrost operation start timely to melt the ice formed on outdoor
heat exchanger.
 • When heating operation accumulated time is time up, and both outdoor temperature and outdoor unit heat exchanger
temperature is less than setting temperature for 5 minutes. When defrost temperature is more than setting temperature, defrost
operation finish.
22
CS-F18DTE5 CU-L34DBE5 /
 • During defrost operation, in spite of any change of remote controller, indoor fan stop and louver angle fixed at upper side.
(for louver control : cassette and ceiling model only)
 • During defrost operation, [DEFROST] is displayed at wired remote controller (when using wireless controller, POWER LED is
blinking in receiver of indoor unit), hot start operate after defrost operation finish.
 • The defrost temperature (DEF_Th) depends on outdoor ambient temperature.
Outdoor air temp. (°C)
Maximum defrost time
DEF_Th (°C)
Tout
-3°C
10min 30sec
11°C
-3°C > Tout
-10°C
10min 30sec
5 °C
Tout < -10°C
10min 30sec
3°C
9.4.6. Heating high temperature protection
 • During heating operation, when outdoor temperature is more than 35°C for 15 minutes, compressor stop to protect compressor.
 • After 3 minutes (re-start delay control) waiting, if thermostat on condition, outdoor unit re-start.
23
CS-F18DTE5 CU-L34DBE5 /
9.5. Louver control
9.5.1. Ceiling type louver control
 • When power is on, at the same time, louver initialize 2 times.
 • During operation, stopping, thermostat is off condition, louver angle change as below table by manual setting or auto setting of
remote controller.
Remote controller setting
Manual
Auto
Operation mode
Display
Set 1
Set 2
Set 3
Set 4
Piping temp (heating)
A
B
C
Normal
20°
35°
50°
70°
70°
20° - 70°
Set 1
Heating
Defrost
20°
Hot start
20°
Thermostat off
20°
Fan
20°
35°
50°
70°
20° - 70°
Cooling
Normal
20°
35°
50°
70°
20° - 70°
(fan)
Dew control
35°
Thermostat off
20°
35°
50°
70°
20° - 70°
Normal
35°
Dry
Dew control
35°
Thermostat off
20°
35°
50°
70°
20° - 70°
Operation mode judge
20°
35°
50°
70°
20°
Stop mode
70°
24