Panasonic CS-F18DTE5 / CU-L34DBE5 Service Manual ▷ View online

REMOTE
The OFF/ON button cannot be used.
LOCAL
All wired remote control buttons can be used.
Time/time setting display
Check display
Fan speed display
Operation mode selection display
FILTER RESET display
(Appears after the cumulative running time reaches
approximately 2,500 hours of operation.)
Temperature setting display (16°C - 31°C)
Airflow direction setting display
OFF/ON button
Used to start and stop the operation.
FAN SPEED button
Used to select the fan speed of high (HI), medium (MED), low
(LO) or auto (AUTO).
MODE button
Used to select the operation of AUTO, HEAT, FAN, COOL, or
DRY.
TEMP (UP/DOWN) buttons
Used to select the desired temperature.
AIR SWING (AUTO/MANUAL) buttons
Used to determined the air swing condition, either auto or
manual.
FILTER RESET button
Press to reset the “FILTER RESET” display after washing the
filter.
TEST RUN button*
VENTILATION button*
ECONOMY operation button
Provides Energy saving function
ODOUR WASH button
Provides deodorizing function.
CHECK button
Press this button if the check display is flashing.
TIMER/CLOCK SET buttons
Used to set the timer operation and the current time.
Operation indicator
Lights up when the unit in operation.
8 Remote Control Operating Instructions
8.1. Wired Remote Control
Name and function of each part
NOTES
 • Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 • The illustration above is for explanatory purposes only. The appearance will be different during actual operation.
 • Do not operate the remote control with wet hands. Otherwise, electric shock or malfunction may occur.
 • Do not press the remote control buttons with sharp object as this may damage the remote control.
 • Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same
button once more to cancel the operation.
 • When the power resumed after power failure, the unit will restart automatically with all the previous settings preserved by
the memory function. (Auto restart function)
17
CS-F18DTE5 CU-L34DBE5 /
Transmitter
Transmits the remote control signal.
Airflow direction setting display
Fan speed display
Temperature setting display (16°C - 31°C)
Time/time setting display
Shows the timer operation setting time or the current time.
Address number display
Operation selection display
OFF/ON button
Used to start and stop the operation.
ODOUR WASH button
FILTER RESET button
Press to cancel the “FILTER” indicator light on the control
panel.
FAN SPEED button
Used to select the fan speed of high (HI), medium (MED), low
(LO) or auto (AUTO).
SET button*
Local setting function.
ADDRESS SET button*
Used to change the address setting when using more than one
indoor unit.
RESET button
Pressing this button will clear all the settings from memory.
You will then need to make the settings again.
TIMER/CLOCK SET buttons
Used to set the timer operation and the current time.
AIR SWING (AUTO/MANUAL) buttons
Used to determine the air swing condition, either auto or
manual.
MODE button
Used to select the operation of AUTO, HEAT, FAN, COOL or
DRY.
TEMP (UP/DOWN) buttons
Used to select the desired temperature.
ECONOMY operation button
8.2. Wireless Remote Control
Name and function of each part
NOTES
 • Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 • The illustration above is for explanatory purpose only. The appearance will be different during actual operation.
 • If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote
control will appear on the wired remote control display (except when making timer settings).
 • Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same
button once more to cancel the operation.
 • When the power resumed after power failure, the unit will restart automatically with all previous settings preserved by the
memory function. (Auto restart function)
18
CS-F18DTE5 CU-L34DBE5 /
9 Operation Control
9.1. Operation mode
 1. Thermostat control
 2. Depend on differences between room temperature and setting temperature, Compressor running frequency will be decided and
start operation.
Temperature differences become same as below table, then thermostat is off.
Temperature Differences
Unit: °C
Indoor type
Cassette
Ceiling
Duct D1
Duct D2
Duct D3
Cool mode
-1.5
-1.5
-2.0
-2.0
-2.0
Dry mode
-2.5
-2.5
-3.0
-3.0
-3.0
Heat mode
3.5
2.5
2.5
2.5
2.5
 3. Select indoor temperature thermostat
When connected to wired remote controller, either indoor unit thermostat or remote controller thermostat is available, using
remote control setting.
9.2. Compressor start control
 • When the compressor start, compressor frequency will be fixed at lower level for certain time, to follow the below table, due to
avoid the compressor oil discharge.
 • Judging from compressor discharge temperature, decide the start condition to select either cool start control, or warm start
control.
Discharge temp. [°C]
>15°C
15°C
Start control
Warm start
Cool start
Warm start : set 1
→ *set 5 → normal control
Cool start : set 1
→ set 2 → set 3 → set 4 → *set 5 → normal control
 • Note
 − Frequency at *set 5 = frequency calculated by normal control
 − In case of frequency at set n (set 1, set 2 or set 3) excess the frequency at set 5 in cool condition, skip from set n (set 1,
set 2 or set 3) to set 4 and transfer to set 5.
9.3. Cooling operation
9.3.1. Cool indoor fan control
 • Fan speed manual
Operation start at hi speed, or medium speed, or low speed set by remote control.
 • Fan speed auto
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, odour cut operation (refer odour
cut operation page for detail), after thermostat ON condition, indoor fan operate as below control.
When 1st thermostat on condition from operation start, fan speed is hi (same as manual fan speed), after 2nd thermostat on
condition, fan speed change to medium speed (same as manual medium fan speed).
19
CS-F18DTE5 CU-L34DBE5 /
9.3.2. Odour cut control
 • When cool or dry mode operation start, select odour cut mode or fan auto mode, by remote control, operation start at odour
wash mode when compressor start or shift to thermostat on from thermostat off.
 • Odour cut operation is under below condition.
Operation mode
Cool or dry mode
Odour wash setting
Setting
No setting
Fan setting
Auto
Odour cut
Odour cut
Manual
Odour cut
-
 • Odour cut operation is to remove the odour generated at indoor heat exchanger to use the drain water come out from indoor
heat exchanger.
9.3.3. Cool powerful operation
 • When cool or dry mode operation start, temperature differences between room temperature and setting temperature is more
than 5 K, setting temperature shift to 2 K down.
 • (But when temperature after shifting is less than 16°C, setting temperature is 16°C = no change)
 • Micro computer judge that required indoor load is bigger than calculation base from temperature differences between room
temperature and setting temperature, then increase the compressor frequency compared to normal to cool down indoor side
immediately.
 • Those kind of operation complete after 30 minutes when cool mode operation start.
9.3.4. Freezing prevention control
 • During cool or dry mode operation, if indoor evaporator temperature is going down, freezing prevention control is operated.
 • Detail of Freezing prevention control is as follows;
Indoor evaporator temperature area is divided into 5 zones, which consist of stop zone, down zone, no change zone, up zone,
and recovery zone. When indoor evaporator temperature is going into each zone, compressor frequency change by following
the below table.
Recovery zone
Release freezing prevention operation
Up zone
Fan motor speed step up
No change zone
Operation no change
Down zone
Reduce the compressor frequency
(check for 3 min, max 3 times)
Stop zone
If continue for 6 min, compressor stop
(for 3 min after stop, compressor can be started due to restart delay control)