61
Installation of supplemental plate for attaching indoor unit
• The rear of the unit can be fixed with screws at the points shown in the illustration as below. Be sure to install the supplemental
plate in accordance with the depth of the inner wall.
Refrigerant piping
See Refrigerant piping under Exposed Installation.
Indoor unit installation
1. Remove the front grille.
2. Remove 7 screws.
3. Remove the upper casing (2 tabs).
4. Remove the side casings (2 tabs on each side).
5. Attach the indoor unit to the wall and secure using screws in 6 locations (M4 x 25L).
Caution
• Use polyvinyl chloride adhesive agent for gluing. Failure to do so may cause water leakage.
Caution
1. Use drain pan edge for horizontal projection of the indoor unit.
2. Install the indoor unit flush against wall.
62
11.3.3.3. Concealed installation
• Only item peculiar to this installation method are given here. See Exposed installation for additional instructions.
Preparation
• Install the unit according to the instructions below. Failure to do so may cause lead to both cooling and heating failure
and the condensation inside the house.
1. Allow enough space between the main unit and ceiling not to obstruct the flow of cool/warm air.
2. Place a partition plate between outlet and inlet sections.
3. Place a partition plate on the right side.
4. Change the upward air flow limit dipswich.
5. Use a movable lattice at the air outlet to allow the adjustment of cool/warm air flow direction.
6. Lattice size should be 70% or more of open rate.
Refrigerant piping
Changing upward air flow limit dipswitch
Change the upward air flow limit dipswitch (SW2-4) to ON to limit the upward air flow.
1. Remove the front grille.
2. Switch the dipswitch (SW2-4) on the PCB in the electrical equipment box to ON.
63
11.3.4.
Connecting the Drain Hose
• Insert the supplied drain hose 
 into the socket of the drain pan. 
Fully insert the drain hose until it adheres to a seal of the socket.
Check the drainage
• Pour a glass of water into the drain pan.
• Ensure that water flows out from drain pipe.
11.3.5.
Connecting the Refrigerant Piping
1. Please make flare after inserting flare nut (locate at joint
point of tube assembly) onto the copper pipe.
2. Align the center of pipe and sufficiently tighten the flare
nut with fingers.
3. Further tighten the flare nut with torque wrench in
specified torque as stated in the table under
3. Connecting the Refigerant Piping in OUTDOOR UNIT.
Checking for gas leakage
• Check for leakage of gas after air purging.
Caution
Be sure to turn on the upward air flow limit dipswitch. Failure to do so may cause incomplete cooling/
heating and formation of condensation inside the house.
64
Insulating the refrigerant piping
• Attach the pipe after checking for gas leakage, described
above.
1. Cut the insulated portion of the on-site piping,
matching it up with the connecting portion.
2. Secure the slit on the auxiliary pipe side with the butt
joint on the connection pipe using the tape, making
sure there are no gaps.
3. Wrap the slit and the butt joint with the included
insulation sheet 
, making sure there are no gaps.
11.3.6.
Connecting the Indoor/Outdoor Connecting Cable
1. Leave the sensor securing plate, remove the front metal
plate cover.
2. Connecting the cable between indoor unit and outdoor
unit shall be approved polychloroprene sheathed
4 x 1.5 mm
2
 flexible cord. Type designation 245 IEC57 or
heavier cord.
• Ensure the colour of wires of indoor unit and the terminal
Nos. are the same to the outdoor's respectively.
• Earth lead wire shall be longer than the other lead wires as
shown in the figure for the electrical safety in case of the
slipping out of the cord from the anchorage.
• Secure the cable onto the control board with the holder
(clamper).
Caution
1. Insulate the joint of the pipes securely.
Incomplete insulation may lead to water leakage.
2. Push the pipe inside so it does not place undue force on the front grille .
Page of 94