9.10. Auto Restart Control
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after
power supply resumes. 
2. This type of control is not applicable during ON/OFF Timer setting.
9.11. Indication Panel
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
9.12. Auto Operation Switch
1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
3. When the switch is pressed between 8 to 11 seconds, the unit will enter forced Heating Mode standby. Press timer decrement
button for 5s for the unit to operate in Heating Mode.
4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control (timer decrement
button for 5s), the unit can be changed to different controlling setting (4 type of transmission codes).
5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control
signal receiving sound can be cancelled or turned on.
9.13. Freeze Prevention Control
1. When indoor heat exchanger temperature is lower than 2
°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10
°C.
3. At the same time, indoor fan speed increase +20 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10
°C for five minutes, the fan speed will return to its normal operation.
LED
POWER
TIMER
QUIET
POWERFUL
AIR SWING
Color
Green
Orange
Orange
Orange
Orange
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
Auto Air Swing ON
Light OFF
Operation OFF
Timer Setting OFF
Quiet Mode OFF
Powerful Mode OFF Auto Air Swing OFF
46
9.14. Dew Prevention Control
a. Purpose
To prevent dew.
b. Control start conditions
When indoor units are ceiling floor, duct and mini-cassette.
c. Control contents
Hz control is carried out according to the dew prevention status transmitted from indoor.
Change is once to 10 seconds.
* Once the stand-up went into the down domain by Fcmax as for the Fcmax domain, it shifts to relative changes control domain.
When the higher rank of relative control has this control and the status signal od 2-3 has come out.
Relative change control is stopped and follows directions of spray control.
Priority is given to the which is larger when freeze prevention down status and dew prevention down status are transmitted
simultaneously.
In the case of dew prevention status   0, it is referred to as maxFc.
9.15. Protection Control Features
9.15.1.
Protection Control For All Operations
9.15.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off for 20 seconds and on again or after 4-way valve deices condition.
9.15.1.2. 30 Seconds Forced Operation
1. Once compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
9.15.1.3. Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
Dew prevention                               
status (transmitted indoor)
Control contents
Relative control domain
MAX domain
0 (it usually controls)
Usually, control
Usually, control
1 (rise)
Relative change control priority
On tap up/10 seconds
2 (changeless)
Changeless
Changeless
3 (down)
-2 Hz/10 seconds
-2 Hz/10 seconds
Model
CU-E9GFE
CU-E12GFE
CU-E18GFE
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling/Dry (A)
4.0
16.8
5.4
16.8
8.74
17
Cooling/Dry (B)
3.6
16.8
5.0
16.8
7.70
17
Heating
5.5
16.8
8.4
16.8
10.71
17
47
9.15.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 100
°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 22.33 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minutes.
3. If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
9.15.1.5. Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
9.15.1.6. Low Pressure Prevention Control (Gas Leakage Detection)
a. Control start conditions
Control will perform when (1) - (3) condition continues operation for 5 minute and (4) is fulfill.
1. During cooling and dry operation: Frequency more than normal Fcmax.
During heating operation: Frequency more than normal Fh
2. Outdoor total current I cooling: Ib I<Ia
Heating: Ib I<Ic
Ic = Ia = 1.65 A
Ib = 0.65 A
3. It is not during deice operation.
During heating operation: Frequency more than normal Fh
4. During cooling and dry operation: indoor suction-indoor piping temperature is below 4
°C.
During of heating operation: Indoor piping temperature-indoor suction is under 5
°C.
Control contents:
• compressor stops (restart after 3 minutes)
• if happen 2 times within (20 minutes), perform the following operation
1) Unit stop operation
2) 7 segment “F91” indicated
9.15.1.7. Compressor Tank Temperature Rise Protection Control
a. Control start conditions
Control will perform when (1) - (3) condition continues operation for 5 minute and (4) is fulfill.
1. During cooling and dry operation: Frequency more than normal Fc.
Air-temperature: Indoor and outdoor 30±5 degrees C
Remote control Hi; 16 degrees C
During Heating operation: Frequency more than Fh
Air temperature: Indoor and outdoor 20±2 degrees C
Remote control Hi; 30 degrees C
48
2. Outdoor total current I Air conditioning: 0.65<=I<1.65.
Heating: 0.65<=I<1.65
It is not during deice operation
3. During cooling and dry operation: indoor suction-indoor piping temperature is below 4
°C.
During heating operation: Indoor piping temperature-indoor suction is under 5
°C.
Control contents:
• compressor stops (restart after 3 minutes)
• if happen 2 times within (20 minutes), perform the following operation
1) Unit stop operation
2) 7 segment “F91” indicated
9.15.1.8. Low Frequency Protection Control 1
When the compressor operate at frequency lower than 25 Hz continued for 20 minutes, the operation frequency will be increased
to 20 Hz for two minutes.
9.15.1.9. Low Frequency Protection Control 2
When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz
for cooling mode operation and 20 Hz for heating mode operation.
9.15.1.10. DC Current Protection Control (E9FGE, E12GFE)
Purpose
In order to control DC current rise in a compressor low frequency region, load is detected with from indoor/outdoor heat
exchanger temperature, Hz control is performed.
Control contents
1. During cooling and dry except test mode
2. During heating compressor operation, except test mode.
Temperature, T, for:
Cooling/Dry
Heating
Indoor intake air (
°C)
T < 15 or T   30
Outdoor air (
°C)
T < 16 or T   38
T < 4 or T   24
Indoor heat exchanger (
°C)
T < 30
T   0
Page of 94