Panasonic CS-E9CKP / CU-E9CKP5 / CS-E12CKP / CU-E12CKP5 Service Manual ▷ View online

Freq.
(Hz)
E9CKP
Free
0
47
58
35
35
0
Free
E12CKP
Free
0
62
67
40
40
0
Free
Indoor fan motor
Free
Free
OFF
OFF
OFF
OFF
OFF
Free
Outdoor fan motor
ON
ON
OFF
OFF
OFF
OFF
ON
ON
4-way valve
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
8.2.21.  Auto Clean Deice Control
This control is applicable for Heating Mode operation only and before operation starting time set by ON Timer control to improve
heating start-up operation if residual ice on outdoor heat exchanger detected.
Fifteen minutes before Standby operation, pre-deice heating operation will be performed to determine the operation decision as
shown in below figure. Auto Clean Deice operation starts to operate as soon as the pre-deice operation if all the below conditions
occur.
(a) Outdoor air temperature
0°C,
(b) Outdoor heat exchanger temperature < 0°C for 14 minutes, and
(c) Outdoor heat exchanger temperature < -8°C for 10 minutes.
The Auto Clean Deice is operated for a maximum of 12 minutes as normal Deice operation, and the period of Standby operation
is maintained including the 12-minute Auto Clean Deice operation.
33
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
8.2.22. Indication Panel
Led
POWER MONITOR
POWER
QUIET
TIMER
POWERFUL
ION
Color
Green
Green
Orange
Orange
Orange
Green
Light ON
Operation ON
Operation ON
Quiet Mode ON
Timer Setting ON
Powerful Mode ON
Ion Mode ON
Light OFF
Operation OFF
Operation OFF
Quiet Mode OFF
Timer Setting OFF Powerful Mode OFF
Ion Mode OFF
Note:
  •  If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode
judgment, or delay ON timer sampling.
  •  If Timer LED is blinking, there is an abnormality operation occurs.
LED Control Frequency
Lighting of 3 LED base on instructed running frequency from indoor unit to compressor at cool, dry & heating operation.
Position of LED
Cool, Dry
Instructed Hz No
1 ~ 6
7 ~ 12
Fc ~ Fc max
Heat
Instructed Hz No
1 ~ 7
8 ~ 16
Fh above
Ion only operation
8.2.23.  Auto Operation Switch
 1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
 2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
 3. When the switch is pressed between 8 to 11 seconds, the unit is forced to operate in Heating Mode.
 4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control, the unit can be
changed to different controlling setting (A-B mode).
 5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote controller´s
signal receiving sound can be cancelled or turned on.
34
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
8.2.24. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Basic Policy
a.
There shall be some difference between actual listening of normal operation & quiet operation.
For Hi & Me, Sound level at quiet operation is set -3dB vs normal operation.
b.
For Lo Cool, if fan speed of quiet Lo is too low, refrigerant sound become obvious, therefore sound level of Quiet Lo is set -2dB vs Lo Cool.
c.
For Lo Heat, to prevent compressor overload, fan speed is not set too low, sound level at quiet Lo operation is set -2dB vs normal Lo
operation.
B. Purpose
To provide quiet cooling operation compare to normal operation.
C. Control condition
a. Quiet operation start condition
  • When “quiet” button at remocon is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Quiet powerful, button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. When change mode to fan only mode.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
Quiet LED off.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
D. Control contents
a. Air flow volume manual
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi & Me for 3dB & Lo for 2dB.
 2. Quiet setting of fan speed is as shown in the following table. (Cool and fan mode)
E9CKP
E12CKP
RPM
1.0 HP
1.5 HP
Quiet Hi
Hi-100
Hi-100
Quiet Me
Me-100
Me-100
Quiet Lo
Lo-100
Lo-100
b. Air flow volume Auto
 1. Odor cut control at normal operation, except selected fan speed is the quiet setting of the respective speed.
Normal Operation
35
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Quiet Operation
8.2.25. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Manual and Air Volume automatic (Normal operation)
8.2.26. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remocon is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Quiet & Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. When change mode to fan only mode.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
Quiet LED off.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
36