DOWNLOAD Panasonic CS-E9CKP / CU-E9CKP5 / CS-E12CKP / CU-E12CKP5 Service Manual ↓ Size: 12.93 MB | Pages: 94 in PDF or view online for FREE

Model
CS-E9CKP CU-E9CKP5 CS-E12CKP CU-E12CKP5
Pages
94
Size
12.93 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / ROOM AIR CONDITIONER
File
cs-e9ckp-cu-e9ckp5-cs-e12ckp-cu-e12ckp5.pdf
Date

Panasonic CS-E9CKP / CU-E9CKP5 / CS-E12CKP / CU-E12CKP5 Service Manual ▷ View online

 2. Manual horizontal airflow direction can be set using remote controller; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Controller
Vane Angle (°)
90
55
70
110
125
8.1.8. 
Automatic Mode Operation
This mode can be set using remote controller and the operation is decided by remote controller setting temperature, indoor intake
air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 20 seconds to detect
the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.
Values of T1, T2, and T3 depend on remote controller setting temperature, as shown in below table. After the adjustment of T1,
T2 and T3 values, the operation mode for that particular environment and remote controller setting is judged and performed, based
on the above operation mode chart, every 30 minutes. Heating mode operation will be performed, however, if deice operation is
detected.
Remote Controller Setting Temperature (°C)
T1
T2
T3
16 ~ 18
+10
+8
-5
19 ~ 22
+8
+7
-7
23 ~ 26
+7
+6
-7
27 ~ 30
+6
+5
-8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from
Temperature shifts (°C)
Cooling/Soft Dry
→ Heating
-2
Heating
→ Cooling/Soft Dry
+2
Example of operation mode chart adjustment:
From the above table, if remote controller setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
25
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
8.2. Protection Control Features
8.2.1. Delay ON Timer Control
This control is applicable to all kinds of operation mode.
Delay ON timer can be set using remote controller, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 20 seconds to determine
the indoor intake air temperature and outdoor air temperature in order to judge the operation mode.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
8.2.2. OFF Timer Control
This control is applicable to all kinds of operation mode.
OFF timer can be set using remote controller, the unit with timer set will stop operate at set time.
26
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
8.2.3. Indoor Power Relay Control
Power relay will turn on during operation or in progress of stopping operation. Although operation stops, the power relay continues
on for three minutes.
However, during instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 3 minutes after power recover
and the unit will operate as previous operation condition.
8.2.4. Time Delay Safety Control
This control is applicable to all kinds of operation mode.
 1. The compressor will not start for three minutes after stop of operation.
 2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
8.2.5. 30 Seconds Forced Operation
This control is applicable to all kinds of operation mode.
 1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
 2. However, it can be stopped using remote control or Auto Switch at indoor unit.
8.2.6. Total Running Current Control
This control is applicable to all kinds of operation mode.
 1. When the total outdoor unit running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased a step to smaller frequency number.
 2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased a step at one time
to bigger frequency number.
 3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
Operation Mode
E9CKP
E12CKP
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (I)
4.5
17.0
6.5
17.0
Cooling/Soft Dry (II)
4.0
17.0
6.0
17.0
Heating
6.1
17.0
9.2
17.0
 4. The first 30 minutes of cooling operation, (I) will be applied.
27
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
8.2.7. IPM (Power transistor) Prevention Control
This control is applicable to all kinds of operation mode.
A. DC Peak Current Control
 1. When electric current to IPM exceeds set value of 22.5 ± 3.5 A, the compressor will stop operate. Then, operation will restart
after three minutes.
 2. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
B. Overheating Prevention Control
 1. When the IPM temperature rises to 110°C, compressor operation will stop immediately.
 2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
8.2.8. Compressor Overheating Prevention Control
This control is applicable to all kinds of operation mode.
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
8.2.9. Low Pressure Control (Gas Leakage Detection)
This control is applicable to all kinds of operation mode.
 1. When the conditions listed in below table occur, the compressor stops and restarts after three minutes.
 2. If this phenomenon is continuously occurring for twice within 20 minutes, all indoor and outdoor relays will be cut off.
 3. This control is not applicable for deice operation.
Conditions
E9CKP
E12CKP
Cooling/Soft Dry
Heating
Cooling/Soft Dry
Heating
1. Compressor frequency (Hz)
47
56
67
68.5
2. Outdoor total running current (A)
1.21
1.21
1.21
1.21
3. Indoor heat exchanger temperature
25
25
25
25
Note: Conditions 1 and 2 needed to be happened continuously for 5 minutes.
28
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Page of 94
Display

Click on the first or last page to see other CS-E9CKP / CU-E9CKP5 / CS-E12CKP / CU-E12CKP5 service manuals if exist.