DOWNLOAD Panasonic CS-E7GKEW / CS-E7GKDW / CS-E9GKEW / CS-E9GKDW / CS-E12GKEW / CS-E12GKDW / CS-E15GKEW / CS-E15GKDW / CS-E18GKEW / CS-E18GKDW / CU-2E15GBE Service Manual ↓ Size: 5.54 MB | Pages: 77 in PDF or view online for FREE

Model
CS-E7GKEW CS-E7GKDW CS-E9GKEW CS-E9GKDW CS-E12GKEW CS-E12GKDW CS-E15GKEW CS-E15GKDW CS-E18GKEW CS-E18GKDW CU-2E15GBE
Pages
77
Size
5.54 MB
Type
PDF
Document
Simplified Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-e7gkew-cs-e7gkdw-cs-e9gkew-cs-e9gkdw-cs-e12gkew.pdf
Date

Panasonic CS-E7GKEW / CS-E7GKDW / CS-E9GKEW / CS-E9GKDW / CS-E12GKEW / CS-E12GKDW / CS-E15GKEW / CS-E15GKDW / CS-E18GKEW / CS-E18GKDW / CU-2E15GBE Simplified Service Manual ▷ View online

2. Specifications 
2.1 Indoor 
unit 
Model CS-E7GKEW 
CS-E7GKDW 
CS-E9GKEW 
CS-E9GKDW 
CS-E12GKEW 
CS-E12GKDW 
CS-E15GKEW 
CS-E15GKDW 
CS-E18GKEW 
CS-E18GKDW 
Item Unit 
Wall 
Mounted 
dB (A) 
Hi: 37 
Lo: 24 
Hi: 39 
Lo: 25 
Hi: 42 
Lo: 28 
Hi: 43 
Lo: 32 
Hi: 44 
Lo: 37 
Cooling 
Power level 
dB 
48 50 53 54 57 
dB (A) 
Hi: 38 
Lo: 25 
Hi: 40 
Lo: 27 
Hi: 42 
Lo: 33 
Hi: 43 
Lo: 35 
Hi: 44 
Lo: 37 
Noise Level 
Heating 
dB 
49 51 53 54 57 
l/h 
1.3 1.6 2.0 2.4   
Moisture Removal 
(pt/h)  2.7 3.4 4.2 5.1   
Lo m
3
/m (ft
3
/m) 
C: 6.3 (220) 
H: 6.5 (230) 
C: 6.6 (230) 
H: 7.1 (250) 
C: 7.0 (250) 
H: 8.5 (300) 
C: 7.4(260) 
H: 9.0 (320) 
C: 12.3 (430) 
H: 13.0 (460) 
Me m
3
/m (ft
3
/m) 
C: 8.0 (280) 
H: 8.4 (300) 
C: 8.5 (300) 
H: 9.1 (320) 
C: 9.1 (320) 
H: 10.1 (360) 
C: 9.2 (330) 
H: 10.8 (380) 
C: 13.9 (490) 
H: 14.6 (520) 
Hi m
3
/m (ft
3
/m) 
C: 9.8 (350) 
H: 10.3 (360) 
C: 10.4 (370) 
H: 11.0 (390) 
C: 11.2 (400) 
H: 11.7 (410) 
C: 11.0 (390) 
H: 11.8 (420) 
C: 15.2 (540) 
H: 16.7 (590) 
Air Volume 
SHi m
3
/m (ft
3
/m) 
C: 10.1 (360) 
H: 10.7 (380) 
C: 10.7 (380) 
H: 11.4 (400) 
C: 11.5 (410) 
H: 12.1 (430) 
C: 11.7 (410) 
H: .11.5 (410) 
Height 
mm (inch) 
280 (11 – 1/32) 
275 (10 – 13/16)
Width 
mm (inch) 
799 (31 – 15/32) 
998 (39 – 9/32) 
Dimension 
Depth 
mm (inch) 
183 (7 – 7/32) 
230 (9 – 1/16) 
Net Weight 
kg (lbs) 
9 (20) 
10 (22) 
Gas 
mm (inch) 
9.52 (3/8) 
12.7 (1/2) 
Pipe Diameter 
Liquid 
mm (inch) 
6.35 (1/4) 
6.35 (1/4) 
Inner diameter 
mm 
16 
12 
Drain Hose 
Length mm 
650 
650 
Type  
Cross-flow 
fan 
Material  
ASG20K1 
Motor Type 
 
Transistor (8-pole) 
Input power 
Fan 
Output power 
 
30 
Fin material 
 
Aluminum (Pre Coat) 
Fin type 
 
Slit Fin 
Row x Stage x FPI 
 
2 x 15 x 19 
2 x 15 x 21 
2 x 15 x 19 
Heat Exchanger 
Size (W x H x L) 
mm (inch) 
610 x 315 x 25.4 
810 x 315 x 25.4
Material  
Polypropelene 
 
Air Filter Type 
Style  
One-Touch 
 
 
1.  Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19°C Wet Bulb (66.2°F Wet Bulb) and outdoor air  
     temperature of 35°C Dry Bulb (95.0°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb). 
2.  Heating capacities are based on indoor temperature of 20°C Dry Bulb (80.6°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F 
     Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb). 
 
Item Unit 
 
Power Source (Phase, Voltage, Cycle) 
 
Single 
 V 
230 
 Hz 
50 
 
 
2.2 Outdoor 
Unit 
Model Name 
 
CU-2E15GBE 
Indoor Unit Combination 
 
2.2kW + 2.2kW 
Power Source 
 
1 Phase, 230V, 50Hz (Power supply from outdoor unit) 
Capacity 
kW 
4.5 (1.50 – 5.0) 
Running Current 
5.75 
Power Input 
kW 
1.230 (250 -1350) 
Electrical 
Data 
EER W/W 
3.66 
Sound Pressure Level 
dB 
47 
Cooling Operation 
Noise 
Sound Power Level 
dB 
62 
Capacity 
kW 
5.4 (1.1 – 7.0) 
Running Current 
5.20 
Power Input 
kW 
1.170 (210 – 1670) 
Electrical 
Data 
COP W/W 
4.62 
Sound Pressure Level 
dB 
49 
Heating Operation 
Noise 
Sound Power Level 
dB(A)
64 
Maximum Current 
12.0 
Starting Current 
5.75 
Circuit Breaker Capacity 
15 
Dimension Height 
mm 
540 
 Width 
mm 
780 
(+70) 
 Depth 
mm 
289 
Net Weight 
kg 
38 
Connection Cable 
 
3 + 1 (Earth) ø1.5 mm
2
 
Pipe Length Range (1 room) 
3 – 20 
Maximum Pipe Length (Total Room) 
30 
Refrigerant Pipe Diameter 
Liquid Side 
mm 
6.35 
 Gas 
Side  mm 
9.52 
Compressor Type 
 
Scroll 
Type 
 
Motor Type 
 
DC Brushless (4-poles) 
 Rated 
Output 
 
1200 
Air Circulation 
Type 
 
Propeller Fan 
 
Motor Type 
 
DC Brushless (8-poles) 
 Rated 
Output 
 
40 
Fan Speed 
Low 
RPM 
690 
 High 
RPM 
860 
Heat Exchanger 
Type 
 
Plate fin configuration forced draft type 
 Tube 
Material 
 
Copper 
 Fin 
Material  
Aluminum 
 Row/Stage 
  
2/20 
 FPI 
  
19 
Air Volume 
High 
Cooling 
(Heating) 
  
33.3 
(28.5) 
Refrigerant Control Device   
 
 
Expansion Valve 
Refrigerant Oil 
 
 
 
POE (RB-68A) 
Refrigerant (R410A) 
 
 
1450 
 
 
Indoor unit combination 
Capacity 
Power Input (kW) 
Outdoor Unit 
Operation Class 
(kW) 
Operation 
Mode 
Rating 
Min - Max 
Rating 
Min - Max 
Current (A) 
Cooling 
2.20 
1.1 – 2.9 
0.52 
0.22 – 0.75 
2.45 
2.2 
Heating 
3.20 
0.7 – 4.8 
0.85 
0.17 – 1.41 
3.75 
Cooling 
2.80 
1.1 – 3.5 
0.75 
0.22 – 1.00 
3.50 
2.8 
Heating 
4.00 
0.7 – 5.5 
1.15 
0.17 – 1.70 
5.10 
Cooling 
3.20 
1.1 – 4.0 
0.92 
0.22 – 1.22 
4.30 
One-room 
Operation 
3.2 
Heating 
4.50 
0.7 – 6.2 
1.25 
0.17 – 1.81 
5.55 
Cooling 
4.50 
1.5 – 5.0 
1.23 
0.25 – 1.35 
5.75 
2.2 + 2.2 
Heating 
5.40 
1.1 – 7.0 
1.17 
0.21 – 1.67 
5.20 
Cooling 
4.50 
1.5 – 5.2 
1.23 
0.25 – 1.52 
5.75 
2.2 + 2.8 
Heating 
5.40 
1.1 – 7.0 
1.17 
0.21 – 1.67 
5.20 
Cooling 
4.50 
1.5 – 5.2 
1.25 
0.25 – 1.53 
5.80 
CU-2E15GBE 
Two-room 
Operation 
2.2 + 3.2 
Heating 
5.40 
1.1 – 7.0 
1.23 
0.21 – 1.72 
5.45 
 
3. Features 
• Product 
o
  A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15GBE,  
CU-2E18CBPG. 
o
  A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18EBE,  
CU-3E23CBPG.  
o
  A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27CBPG 
 
 
  
Outdoor 
Unit 
 
  
CU-2E15GBE 
CU-2E18CBPG
CU-3E18EBE 
CU-3E23CBPG 
CU-4E27CBPG 
 
 
 
A B A B A B C A B C A 
2.2 kW  CS-E7GKEW 
CS-E7GKDW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.8 kW  CS-E9GKEW 
CS-E9GKDW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2 kW  CS-E12GKEW 
CS-E12GKDW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0 kW  CS-E15GKEW 
CS-E15GKDW 
_ _ _ _  ● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Wall 
5.0 kW  CS-E18GKEW 
CS-E18GKDW 
_ _ _ _  ● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.8 kW  CS-ME10DD3EG 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0 kW  CS-ME15DD3EG 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Duct 
5.0 kW  CS-ME18DD3EG 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.8 kW  CS-ME10DTEG 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0 kW  CS-E15DTEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Ceiling 
Floor 
5.0 kW  CS-E18DTEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0 kW  CS-E15DB4EW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Mini- 
Cassette 
5.0 kW  CS-E18DB4EW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.2 kW  CS-ME7EB1E 
● 
● _ _  ● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.8 kW  CS-ME10EB1E 
● 
● _ _  ● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2 kW  CS-ME12EB1E 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Cassette 
4.0 kW  CS-ME14EB1E 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.8 kW  CS-E9GFEW 
● 
● _ _  ● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2 kW  CS-E12GFEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Floor  
Standing  5.0 kW  CS-E18GFEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
Capacity range of 
connectable indoor units 
From 4.4kW to 5.0kW  From 4.4kW to 6.4kW From 5.0kW to 9.0kW From 5.0kW to 10kW 
From 5.0 to 13.6kW 
1 room maximum 
pipe length (m) 
20 20 25 25 25 
Allowable elevation 
(m) 
10 10 15 15 15 
Total allowable pipe 
length (m) 
30 30 50 50 70 
Total pip e length for 
maximum chargeless 
length (m) 
20 20 30 30 40 
Piping length 
Additional gas 
amount over 
chargeless length (m) 
20 20 20 20 20 
  
Note: 
“●” : Available 
Remarks for CU-2E15GBE / CU-2E18CBPG 
1. 
At least two indoor units must be connected. 
2. 
The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within connectable capacity range of indoor 
unit. (as shown in the table above) 
Example: The indoor units’ combination below is possible to connect to CU-2E15GBE. (Total nominal capacity of indoor units is between 
4.4kW to 5.0kW) 
1)  Two CS-E7GKEW only. (Total nominal cooling capacity is 4.4kW) 
2)  One CS-E7GKEW and one CS-E9GKEW. (Total nominal cooling capacity is 5.0kW) 
Remarks for CU-3E18EBE / CU-3E23CBPG / CU-4E27CBPG 
1. 
At least two indoor units must be connected. 
2. 
The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within connectable capacity range of indoor 
unit. (as shown in the table above) 
Example: The indoor units’ combination below is possible to connect to CU-3E23CBPG. (Total nominal capacity of indoor units is between 
5.0kW to 10.0kW) 
1)  Two CS-E9GKEW only. (Total nominal cooling capacity is 5.6kW) 
2)  Three CS-E9GKEW. (Total nominal cooling capacity is 9.6kW) 
 
4. Location of Controls and Components 
4.1 Indoor 
Unit 
4.1.1 CS-E7GKEW, 
CS-E9GKEW, CS-E12GKEW, CS-E15GKEW 
CS-E7GKDW, CS-E9GKDW, CS-E12GKDW, CS-E15GKDW 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
4.1.2 CS-E18GKEW, 
CS-E18GKDW 
 
 
Page of 77
Display