37 
13.2.5 Automatic 
operation 
•  This mode can be set using remote control and the operation is decided by remote control setting temperature, 
remote control operation mode, indoor intake temperature and outdoor air temperature. 
•  During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 
seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below 
chart. 
 
Indoor intake air 
Temperature (°C) 
 
 
 
 
 
 
 
 
 Heating 
mode 
36 
 
 
 
 
 
  
 
Soft 
dry 
mode 
 
 
 
 
 
 
 
 
 Cooling 
mode 
 
 
       T1 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 T2  
 
 
 
Remote control  
setting temperature 
 
 
 
 
 
T3 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
16 
 
 
 
 
 
 
 
 
 
 
                       13                                  19         21         23       25
 
 
 
 
 
 
 
 
Outdoor air 
temperature (°C) 
 
 
 
Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the 
adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is 
judged and performed, based on the above operation mode chart, every 30 minutes. 
 
Remote control setting temperature (°C) 
T1 
T2 
T3 
16 ~ 18 
+10 
-2 
-5 
19 ~ 22 
+8 
-3 
-7 
23 ~ 26 
+7 
-3 
-7 
27 ~ 30 
+6 
-3 
-8 
 
There is a temperature shifting on T1, T2 and T3 if the operation mode judged is changed from cooling/ soft dry to 
heating or vice versa. 
 
Operation mode change from 
Temperature shifts (°C) 
Cooling/ Soft dry → Heating 
-2 
Heating → Cooling/ Soft dry 
+2 
 
 
Example of operation mode chart adjustment: 
From the above table, if remote control setting temperature = 25,  
T1 = 25 + 7 = 32; T2 = 25 – 3 = 22; T3 = 25 -7 =18 
 
The operation mode chart for this example is shown in below figure and the operation mode to be performed will 
depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made. 
 
Indoor intake air 
Temperature (°C) 
 
 
 
 
 
 
 
 
 Heating 
mode 
36 
 
 
 
 
 
  
 
Soft 
dry 
mode 
32 
 
 
 
 
 
 
 
 Cooling 
mode 
 
 
 
 
 
 
 
 
 
 
 
    +7 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
25 
 
 
 
 -3 
 
 
  -7 
 
 
 
 
 
Remote control setting 
temperature 
22 
 
 
 
 
 
 
 
 
 
18 
 
 
 
 
 
 
 
 
 
16 
 
 
 
 
 
 
 
 
 
 
13 
19 
21 
  23 
25 
 
 
 
 
 
 
 
 
Outdoor air 
temperature (°C)
 
 
 
38 
55°C 
50°C 
45°C 
30°C 
35°C 
40°C 
45°C 
50°C 
40°C 
30°C 
35°C 
25°C 
Me+
Me- 
Me- 
Lo 
Lo 
Lo 
Lo- 
Indoor Pipe Temp. 
13.2.6  Indoor fan motor operation 
•  Basic Rotation speed (rpm) 
o
 Manual 
fan 
speed 
 
[Cooling, Dry] 
ƒ
  Fan motor’s number of rotation is determined according to remote control setting. 
 
Remote control 
Tab (rpm) 
SHi 
Me+ 
Me 
Me- 
Lo 
 
[Heating] 
ƒ
  Fan motor’s number of rotation is determined according to remote control setting. 
 
Remote control 
Tab 
(rpm) Hi 
Me+ Me  Me- Lo 
 
o
  Auto fan speed 
[Cooling, Dry] 
ƒ
  According to room temperature and setting temperature, indoor fan speed is determined automatically. 
ƒ
  The indoor fan will operate according to pattern below. 
 
 
       
[1 
pattern:10s] 
 
Fan 
Speed 
          
 a b c d e  f  g h a b 
Higher  
 
 
 
 
 
 
 
 
 
Medium 
          
Lower 
          
 
 [Heating] 
ƒ
  According to indoor pipe temperature, automatic heating fan speed is determined as follows. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
• Feedback 
control 
o
  Immediately after the fan motor started, feedback control is performed once every second. 
o
  During fan motor is stop and then restart. If the fan motor counter becomes 7 times, then H19 – fan motor 
error is detected. Operation stops and cannot on back. 
39 
1
0° 
145° 
Close position
Side view 
Figure 2 
50°C 
30°C 
16°C 
58°C 
37°C 
36°C 
Indoor heat  
exchanger temperature 
Figure 1 
13.2.7   Airflow direction 
•  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by 
vertical vanes). 
•  Control of airflow direction can be automatic (angles off direction is determined by operation mode, heat 
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using 
remote control). 
 
13.2.7.1 Vertical 
airflow 
 
Vane Angle (°) 
Operation 
mode 
Airflow direction 
1 2 
4 5 
CU-E7,9,12,15GK
A Upward 
fix 
CU-E18GK 16 
CU-E7,9,12,15GK
45 
B Downward 
fix
CU-E18GK 50 
CU-E7,9,12,15GK
C Upward 
fix 
CU-E18GK 8 
CU-E7,9,12,15GK
Auto with heat 
exchanger 
temperature 
D Downward 
fix
CU-E18GK 8 
CU-E7,9,12,15GK
12 25 37 49 60 
Heating 
Manual 
CU-E18GK  8  17 33 49 60 
CU-E7,9,12,15GK
10 ~ 32 (22 ~ 30) 
Auto (Anti-Dew Control) 
CU-E18GK 
8 ~ 38 
CU-E7,9,12,15GK 12 (22) 
18 
25 
31 
37 (30) 
Cooling and 
ion 
Manual (Anti-Dew Control) 
CU-E18GK  8  17 33 49 60 
CU-E7,9,12,15GK
10 ~ 32 (22 ~ 30) 
Auto (Anti-Dew Control) 
CU-E18GK 8 
CU-E7,9,12,15GK 12 (22) 
18 
25 
31 
37 (30) 
Soft Dry 
Manual (Anti-Dew Control) 
CU-E18GK  8  17 25 33 38 
 
•  Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the 
angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat 
exchanger temperature as figure 1 below. When the air conditioner is stopped using remote control, the vane 
will shift to close position. 
•  Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and 
the positions of the vane are as figure 2 below. When the air conditioner is stopped using remote control, the 
vane will shift to close position. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
40 
40°C 
43°C 
A: Swing 
B: fix front 
Indoor heat  
exchanger temperature 
Figure 1 
1
3 4 
0° 
Top view 
Figure 2
13.2.7.2 Horizontal 
airflow 
•  For CS-E7, 9, 12, 15GKD/GKE, the horizontal airflow direction louvers can be adjusted manually by hand. 
•  For CS-E18GKD/GKE, automatic airflow direction can be set using remote control; the vane swings left and right 
within the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor 
heat exchanger temperature as Figure 1 below. 
 
Operation Mode 
Vane angle (°) 
68 ~ 112 
Heating, with heat exchanger temperature 
B 90 
Cooling and soft dry 
 
68 ~ 112 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
•  For CS-E18GKD/GKE, manual vertical airflow direction can be set using remote control; the angles of the vane 
are as stated below and the positions of the vane are as Figure 2 above. 
 
Pattern 
1 2 3 4 5 
Airflow direction 
patterns at remote 
control 
 
 
 
 
 
Vane angle (°) 
90 
68 
79 
101 
112 
 
13.2.8  Quiet operation (Cooling mode/Cooling area of Dry mode) 
Purpose 
•  To provide quiet cooling operation compare to normal operation. 
 
Control condition 
•  Quiet operation start condition 
1.  When “quiet” button at remote control is pressed. Quiet LED illuminates. 
 
•  Quiet operation stop condition 
1.  When one of the following conditions is satisfied, quiet operation stops: 
o
 
Powerful button is pressed. 
o
 
Stop by OFF/ON switch. 
o
 
Timer “off” activates. 
o
 
Quiet button is pressed again. 
2.  When quiet operation is stopped, operation is shifted to normal operation with previous setting. 
3.  When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed. 
4.  When operation mode is changed, quiet operation is shifted to quiet operation of the new mode. 
5.  During quiet operation, if timer “on” activates, quiet operation maintains. 
6.  After off, when on back, quiet operation is not memorized. 
 
Control content 
•  Fan speed is changed from normal setting to quiet setting of respective fan speed. This is to reduce sound of Hi, 
Me, Lo for 3dB. 
•  Fan speed for quiet operation is -1 step from setting fan speed. 
 