Panasonic CS-CE9JKE / CU-CE9JKE / CS-CE12JKE / CU-CE12JKE Service Manual ▷ View online
49
15.4.5.
H19 (Indoor Fan Motor - DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of
rotation > 2550rpm or < 50rpm)
rotation > 2550rpm or < 50rpm)
Malfunction Caused
• Operation stops due to short circuit inside the fan motor winding.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty indoor unit PCB.
• Operation stops due to breaking of wire inside the fan motor.
• Operation stops due to breaking of fan motor lead wires.
• Operation stops due to Hall IC malfunction.
• Operation error due to faulty indoor unit PCB.
Troubleshooting
50
15.4.6.
H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature
sensor are used to determine sensor errors.
sensor are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
51
15.4.7.
H27 (Outdoor Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used
to determine sensor errors.
to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
52
15.4.8.
H28 (Outdoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are
used to determine sensor errors.
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
Click on the first or last page to see other CS-CE9JKE / CU-CE9JKE / CS-CE12JKE / CU-CE12JKE service manuals if exist.