15.4. Self-diagnosis Method
15.4.1.
H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
46
15.4.2.
H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are
used to determine sensor errors.
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
47
15.4.3.
H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor
are used to determine sensor errors.
are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
48
15.4.4.
H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
A current transformer (CT) is detected by checking the compressor running frequency ( rated frequency) and CT detected
input current (less than 0.65A) for continuously 20 seconds.
input current (less than 0.65A) for continuously 20 seconds.
Malfunction Caused
• CT defective
• Outdoor PCB defective
• Compressor defective (low compression)
• Outdoor PCB defective
• Compressor defective (low compression)
Troubleshooting