12.5. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.5.1.
Fan Speed Rotation Chart
12.5.2.
Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi and Me.
- Deodorizing Control will be activated.
Speed
Fan Speed (rpm)
CS-C7GKD
CS-C9GKD
CS-C12GKD
S Hi
1240
1320
1320
Hi
1150
1250
1270
Me
1000
1040
1060
H Lo
940
890
960
C Lo
850
800
900
Lo-
780
750
850
S Lo
750
700
820
Q Hi
1040
1150
1170
Q Me
900
940
960
Q Lo
750
700
800
34
• Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 3 minutes to prevent higher volume of refrigerant
in liquid form returning to the compressor.
5. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise
environment, after 70 seconds from the restart of compressor.
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
12.5.3.
Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
12.6. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
35
12.7. Vertical Airflow Direction Control
12.7.1.
Auto Control
• When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the
diagram.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the
louver will stop swinging and rest at the upper limit.
12.7.2.
Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
12.8. Horizontal Airflow Direction Control
• The horizontal airflow direction louvers can be adjusted manually by hand.
12.9. Powerful Operation
• To achieve the setting temperature quickly.
• When Powerful operation is set, the setting temperature will be automatically decreased 3
°C internally against the present
setting temperature (Lower temperature limit: 16
°C).
• This operation automatically will be running under SHi fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10
° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10
° downward.
• Powerful operation stops when:-
- Quiet/Powerful button is pressed again.
- Powerful operation has operate for 15 minutes.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
Operation mode is changed.
36
12.10. Quiet Operation
(For Cooling Operation or cooling region of Soft Dry Operation)
• To provide quiet cooling operation condition compare to normal operation.
• Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce around 2 dB(A)
for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present operation sound level.
• Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo + 50
rpm). After that, it goes back to Lo cool (However Quiet LED remains on).
• Manual Airflow Direction:-
- RPM control during Lo cool
- RPM control during Hi & Me cool
• Auto Fan Speed:-
• Quiet operation stops when:-
- Quiet button is pressed again.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operation mode button is changed.
Page of 64