Panasonic CS-C7GKD / CU-C7GKD / CS-C9GKD / CU-C9GKD / CS-C12GKD / CU-C12GKD Service Manual ▷ View online
45
13.3. Remote Control Button
13.3.1.
SET BUTTON
• To check current remote control transmission code.
- Press for more than 10 seconds.
• To change the air quality sensor sensitivity:
- Press and release with pointer.
- Press the Timer Decrement button to select sensitivity:
- Press the Timer Decrement button to select sensitivity:
1. Low Sensitivity
2. Standard (Default)
3. Hi Sensitivity
2. Standard (Default)
3. Hi Sensitivity
- Confirm setting by pressing Timer Set button, a “Beep” sound will be heard. LCD returns to original display after 2 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds.
- LCD returns to original display if remote control does not operate for 30 seconds.
13.3.2.
CLOCK BUTTON
• To change the remote control’s time format.
- Press for more than 5 seconds.
13.3.3.
RESET (RC)
• To clear and restore the remote control setting to factory default.
- Press once to clear the memory.
13.3.4.
TIMER
• To change indoor unit indicator’s LED intensity.
- Press continuously for 5 seconds.
13.3.5.
TIMER
• To change remote control display from Degree Celsius to Degree Fahrenheit.
- Press continuously for 10 seconds.
46
14 Troubleshooting Guide
14.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
47
14.1.1.
Relationship between the condition of the air conditioner and pressure and electric
current
current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.1.2.
Diagnosis methods of a malfunction of a compressor
Cooling Mode
Condition of the air
conditioner
Low Pressure
High Pressure
Electric current during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of the
outdoor unit
Inefficient compression
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90
°C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
48
15 Disassembly and Assembly Instructions
15.1. Indoor Electronic Controllers and Control Board Removal Procedures
WARNING
• Cautions! When handling electronic controller, be careful of electrostatic discharge.
• Be sure to return the wiring to its original position.
• There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after
• Be sure to return the wiring to its original position.
• There are many high voltage components within the heat sink cover so never touch the interior during operation. Wait at least two minutes after
power has been turned off.
Click on the first or last page to see other CS-C7GKD / CU-C7GKD / CS-C9GKD / CU-C9GKD / CS-C12GKD / CU-C12GKD service manuals if exist.