DOWNLOAD Panasonic CS-C7GKD / CU-C7GKD / CS-C9GKD / CU-C9GKD / CS-C12GKD / CU-C12GKD Service Manual ↓ Size: 5.69 MB | Pages: 64 in PDF or view online for FREE

Model
CS-C7GKD CU-C7GKD CS-C9GKD CU-C9GKD CS-C12GKD CU-C12GKD
Pages
64
Size
5.69 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-c7gkd-cu-c7gkd-cs-c9gkd-cu-c9gkd-cs-c12gkd-cu-c.pdf
Date

Panasonic CS-C7GKD / CU-C7GKD / CS-C9GKD / CU-C9GKD / CS-C12GKD / CU-C12GKD Service Manual ▷ View online

25
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove
burrs from cut edge. Make flare after inserting the flare nut
(locate at valve) onto the copper pipe. Align center of piping to
valves and then tighten with torque wrench to the specified
torque as stated in the table.
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused. Turn the piping
end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.
11.3.3.
Evacuation Of The Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to -
76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
Model
Piping size (Torque)
Gas
Liquid
C7GK, C9GK, RS-C7GK,
RS-C9GK
3/8” [42 N•m]
1/4” [18 N•m]
C12GK, A12GK, 
RS-C12GK
1/2” [55 N•m]
1/4” [18 N•m]
26
11.3.4.
Connect The Cable To The Outdoor
Unit
1. Remove the control board cover from the unit by
loosening the screw.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7GK,
C9GK, C12GK, RS-C7GK, RS-C9GK, RS-C12GK) or 5
(A9GK, A12GK) × 1.5 mm
2
 flexible cord, type designation
245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder
(clamper).
4. Attach the control board cover back to the original
position with the screw.
11.3.5.
Pipe Insulation
1. Please carry out insulation at pipe connection portion as
mentioned in Indoor/Outdoor Unit Installation Diagram.
Please wrap the insulated piping end to prevent water
from going inside the piping.
2. If drain hose or connecting piping is in the room (where
dew may form), please increase the insulation by using
POLY-E FOAM with thickness 6mm or above.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure: 
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite. 
27
12 Operation and Control
12.1. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16
°C to
30
°C.
• During cooling operation, the compressor will stop running and restart as shown in below figure.
12.1.1.
Cooling Operation Time Diagram
28
12.2. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown in
below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
12.2.1.
Soft Dry Operation Time Diagram
Page of 64
Display

Click on the first or last page to see other CS-C7GKD / CU-C7GKD / CS-C9GKD / CU-C9GKD / CS-C12GKD / CU-C12GKD service manuals if exist.