21
11 Installation Instruction
11.1. Select The Best Location
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over the rated length, additional refrigerant
should be added as shown in the table.
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Indoor Unit
Outdoor Unit
Piping size
Rated
Length
(m)
Max
Elevation
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Model
Gas
Liquid
C7GK/
C9GK
3/8”
1/4”
7.5
5
10
10
A9GK
3/8”
1/4”
7.5
5
10
20
RS-C7GK/
C9GK
3/8”
1/4”
7.5
5
10
10
C12GK
1/2”
1/4”
7.5
5
15
10
A12GK
1/2”
1/4”
7.5
5
15
20
RS-
C12GK
1/2”
1/4”
7.5
5
15
10
Indoor/Outdoor Unit Installation Diagram
22
11.2. Indoor Unit
11.2.1.
How To Fix Installation Plate
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 450 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit's left side is 74 mm.
From installation plate right edge to unit's right is 94 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side edge of the instal-
lation plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting measur-
ing tape at position as shown in the diagram above. The
hole centre is obtained by measuring the
distance namely 150 mm and 125 mm for left and right
hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.2.2.
To Drill A Hole  In  The  Wall  And
Install A Sleeve Of Piping
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.2.3.
Indoor Unit Installation
For the right rear piping
For the right and right bottom piping
:
:
:
For left side piping, piping connection for liquid should be
about 15 mm from this line.
For left side piping, piping connection for gas should be
about 45 mm from this line.
For left side piping, piping connection cable should be
about 800 mm from this line.
Caution
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting cable.
23
For the embedded piping
Pull out the piping and drain hose
How to keep the cover
Insert the connecting cable
Install the Indoor unit
Secure the Indoor Unit
(This can be used for left rear piping & left bottom piping 
also.)
24
• How to pull the piping and drain hose out, in case of the
embedded piping.
• In case of left piping how to insert the connecting cable and
drain hose.
11.2.4.
Connect The Cable To The Indoor
Unit
1. The inside and outside connecting cable can be
connected without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7GK,
C9GK, C12GK, RS-C7GK, RS-C9GK, RS-C12GK) or 5
(A9GK, A12GK) × 1.5mm
2
 flexible cord, type designation
245 IEC 57 or heavier cord.
• Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
• Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
• Secure the cable onto the control board with the holder
(clamper).
11.3. Outdoor Unit
11.3.1.
Install The Outdoor Unit
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and
horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly
with bolt or nails.
11.3.2.
Connecting The Piping
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut
with fingers.
• Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
Model
A
B
C
D
C7GK, C9GK, A9GK
474
87
18.5
261
A12GK, RS-C12GK,
C12GK
570
105
18.5
320
Page of 64