Heating in operation according to Remote Control setting.
Time Delay Safety Control
30 minutes Time Save Control
Overload Protection Control
(b) Compressor high pressure protection
Compressor Reverse Rotation Protection Control
4-way Valve Control
Outdoor Fan Motor Control
Indoor Fan Motor Control
8.3. Heating Mode Operation
  • When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
  • When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.
  • The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
(a) Outdoor Fan Control
  • If the temperature of the indoor heat exchanger rises to 51°C (123.8°F), Outdoor Fan stops.
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C (120.2°F).
  • If the indoor heat exchanger becomes 65°C (149°F) or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
  • If the compressor is operating continuously for 5 minutes or longer and temperature difference between intake air and indoor
heat exchanger is 5°C (41°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid).
▲ T = Indoor heat exchanger temperature - intake air temperature.
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
  • 4-way valve always ON during Heating operation. (Except Deicing operation)
  • When the unit is switched to “OFF” during Heating operation, 4-way valve stay at Heating position for 5 minutes.
  • When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds.
(30 seconds Forced Operation).
  • When compressor stops (reaches room temperature), indoor fan will stop for 1 minutes, operate for 3 minutes, if still not yet
reaches the room temperature, indoor fan Lo- for 40 sec. after that operate at SLo speed.
21
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Hot Start Control
Anti Cold Draft Control
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C (86°F) as diagram shown.
Hot Start is completed when indoor heat exchanger rises to 39°C (102.2°F) or over 4 minutes.
  • This operation is to prevent the Cold Draft during Heating mode operation.
  • The operation will start when compressor OFF (Thermo OFF) during Heating operation.
  • For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat
exchanger temperature as shown below:
  • After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run at SSLo speed only.
  • Anti Cold Draft Control will stop when:
  − Intake temperature < set temperature. (Time Delay Safety Control 4 minutes waiting is valid)
  − After 30 minutes time saved control.
(refer to next page).
22
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Automatic Fan Speed Mode
Heating Operating Time Diagram
When Automatic Fan Speed is selected at Remote Control during heating operation.
  • Fan speed rotates in the range of Me → SLo according to the heat exchanger temperature.
  • If use Manual Fan Speed,
at above diagram will operate with setting Fan Speed.
23
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
  • Normal Deicing
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (26.6°F) (TRS CLOSE)
or less for 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
  • Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
  • Deicing ends when
 1. 12 minutes after deicing operation starts;
 2. TRS senses the outdoor piping temperature rises to 4°C (39.2°F) (TRS OPEN).
 3. Deicing will not end immediately as time delay (Td) is valid as shown below.
  • Once deicing operation starts, it will not end for 60 seconds.
  • After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
24