Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls
continuously below 2°C (35.6°F) for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
• Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (50°F) (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
• When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
• When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (36.5°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
(Time Delay Safety Control is valid)
▲ T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
15
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Compressor Protection Control
Automatic Fan Speed Mode
• After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
• If the above phenomenon is repeated for 3 times, the compressor will stop totally.
• The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
• The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.