6 Block Diagram
13
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
7 Wiring Diagram
14
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Starting Current Control
Anti-Freezing Control
  • If the temperature of the indoor heat exchanger falls
continuously below 2°C (35.6°F) for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
  • Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (50°F) (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
8 Operation Details
8.1. Cooling Mode Operation
  • When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
  • When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
  • The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
  • When the compressor outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will operate 1.6
second later.
  • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (36.5°F) or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
▲ T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
15
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Compressor Protection Control
Automatic Fan Speed Mode
  • After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
  • If the above phenomenon is repeated for 3 times, the compressor will stop totally.
  • The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
  • Fan speed rotates in the range of Hi to Me.
  • Deodorizing Control.
16
CS-A9CKPG CU-A9CKP6G / CS-A12CKPG CU-A12CKP6G
Page of 82
Display