(1) REMOVE POWER PLUG OR DISCONNECT FROM THE MAINS BEFORE SERVICING THIS APPLIANCE.
(2) THIS APPLIANCE MUST BE EARTHED.
(3) THE APPLIANCE IS NOT INTENDED FOR USE BY YOUNG CHILDREN OR INFIRM PERSONS WITHOUT
SUPERVISION
(4) YOUNG CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE
APPLIANCE.
IMPORTANT
1. WHEN THE POWER CORD IS CONNECTED TO THE MAINS THROUGH A MULTI POLAR SWITCH
THERE MUST BE A MULTI POLAR SWITCH (DISCONNECTING MEANS) WITH A MINIMUM 3 mm
 CONTACT GAP IN THE FIXED INSTALLATION CIRCUIT.
2. WHEN THE POWER PLUG IS CONNECTED TO THE RECEPTACLE
The wires in this main lead are coloured in accordance with the following code :
                       Green-and-yellow  :  Earth
                       Blue                       :  Neutral
                       Brown                    :  Live
If the colours of the wires in the main lead of this appliance do not correspond with the coloured markings
indentifying the terminals in your plug, proceed as follows :
The green-and-yellow wire must be connected to the terminal in the plug which is marked with letter E or by
the earth symbol 
!
 or coloured green or green-and-yellow.
The blue wire must be connected to the terminal which is marked with the letter N or coloured black.
The brown wire must be connected to the terminal which is marked with the letter L or coloured red.
NOTE
IF THE SUPPLY CORD IS DAMAGED, IT MUST BE REPLACED WITH A SPECIAL CORD OR ASSEMBLY
AVAILABLE FROM THE MANUFACTURER OR IT’S SERVICE AGENT.
!
 
 
WARNING
Fuse Specifications
Indoor
T3.15(A), L250(V)
Outdoor
T3.15(A), L250(V)
41
CS-A28
BKP5
/CU-A28
BKP5
Replacement or installation of power plugs shall be performed only by authorised/qualified personnels.
10 Installation Instructions
Required tools for Installation Works
1.
Phillips screw driver
5.
Spanner
9.
Gas leak detector
13. Multimeter
2.
Level gauge
6.
Pipe cutter
10. Measuring tape
14. Torque wrench
18 N.m (1.8 kgf.m)
65 N.m (6.5 kgf.m)
3.
Electric drill, hole core drill
(ø70 mm)
7.
Reamer
11. Thermometer
15. Vacuum pump
4.
Hexagonal wrench (4 mm)
8.
Knife
12. Megameter
16. Gauge manifold
10.1. Safety Precautions
  • 
Read this following “SAFETY PRECAUTIONS” carefully before installation.
  • 
Electrical work must be installed by all licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
  • 
The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the
following indication.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with white background  denotes item that is PROHBITED from doing.
  • 
Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instruction. Please remind the customer to keep the operating instructions for future reference.
1.
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or
fire.
2.
Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5.
For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6.
Use the specified cable (2.5 mm
2
) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8.
When carrying out piping connection, take care not to let air or other substances other than the specified refrigerant go into refrigeration
cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigerant cycle, explosion and injury.
9.
Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.
10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical appliances. Otherwise, it will cause fire or electrical shock.
42
CS-A28
BKP5
/CU-A28
BKP5
1.
Grounding is necessary. It may cause electrical shock if grounding is not perfect.
2.
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
1.
Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2.
Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.In some
countries, permanent connection of this room air conditioner to the power supply is prohibited.
 1. Power supply connection to the receptacle using a power plug. Use an approved 20A power plug with earth pin for the connection to
the receptacle.
 2. Power supply connection to a circuit breaker for the permanent connection. Use an approved  circuit breaker as shown in the table
below for  the permanent connection. It must be a double pole switch with a minimum 3 mm contact gap.
3.
Do not release refrigerant.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4.
Installation work.
It may need two people to carry out the installation work.
5.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
43
CS-A28
BKP5
/CU-A28
BKP5
Circuit Breaker
CS/CU-W28BKP5
CS/CU-A28BKP5
30 A
20 A
Attached accessories
Applicable: Flaring piping kit CZ-52F
SELECT THE BEST LOCATION
INDOOR UNIT
  • 
There should not be any heat source or steam near the
unit.
  • 
There should not be any obstacles blocking the air
circulation.
  • 
A place where air circulation in the room is good.
  • 
A place where air drainage can be easily done.
  • 
A
place
where
noise
prevention
is
taken
into
consideration.
  • 
Do not install the unit near the door way.
  • 
Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
  • 
Indoor unit of this room air conditioner shall be installed
on the wall in a height of at least 2.5 m.
OUTDOOR UNIT
  • 
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
  • 
There should not be any animal or plant which could be
affected by hot discharged air.
  • 
Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
  • 
Do not place any obstacles which may cause a short
circuit of the discharged air.
  • 
If piping length is over 10 m, additional refrigerant
should be added as shown in the table.
Piping length and the elevation
Pipe size
Max.
Piping
Length
A (m)
Max.
Elevation
B (m)
Rated
Additional
Refrigerant
(g/m)
Model
Gas Liquid
Length Elevation
W28BKP5
5/8”
1/4”
30
25
7.5
5
40
Example:
If the unit will be installed at a 12 m distance, the quantity of
Indoor/Outdoor unit installation diagram
  • 
This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
44
CS-A28
BKP5
/CU-A28
BKP5
additional refrigerant should be 80 g...(12-10 m) × 40 g/m = 80g
A28BKP5
 5/8” 1/4” 30 25 7.5 5 40