Automatic Fan Speed Mode
Cooling Operation Time Diagram
When Automatic Fan Speed is selected at Remote Control during cooling operation.
  • 
Fan speed rotates in the range of Hi to Me.
  • 
Deodorizing Control.
13
CS-A28
BKP5
/CU-A28
BKP5
Time Delay Safety Control
Anti-Freezing Control
Automatic Fan Speed Mode
8.2. Soft Dry Mode Operation
  • 
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
  • 
During Soft Dry operation, the Indoor Fan operates with Lo speed.
  • 
Once room temperature reaches below Soft Dry OFF temperature, Indoor Fan, Compressor and Outdoor Fan Stop for 6
minutes.
  • 
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
  • 
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
  • 
Fan speed rotates at Lo speed.
  • 
Deodorizing Control.
14
CS-A28
BKP5
/CU-A28
BKP5
Soft Dry Operation Time Diagram
15
CS-A28
BKP5
/CU-A28
BKP5
  • 
Heating in operation according to Remote Control setting.
Time Delay Safety Control
30 minutes Time Saved Control
Overload Protection Control
4-way Valve Control
Hot Start Control
Hot Start is completed when indoor heat exchanger reaches
42°C.
Maximum Hot start duration = 4 minutes. After 4 minutes, Hot
start operation will be shifted to normal Heating operation.
8.3. Heating Mode Operation
  • 
When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes when
the Power Switch, Remote Control is turned ON or the power supply is resumed.
  • 
When the setting temperature is reached during heating operation, the compressor stops and it will not start for 4 minutes.
  • 
The compressor will start automatically if it has stopped for 30 minutes even if the room temperature is below the compressor
OFF temperature.
  • 
If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop, when Outdoor
Heat Exchanger temperature is T
b
or more according to Outdoor Air Temperature region as table below:
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
  • 
If the Indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting)
  • 
4-way valve ON during Heating operation, except deicing operation.
  • 
When the unit is switched to “OFF” during Heating operation, 4-way valve stay at Heating position for 5 minutes.
When Heating operation starts, Indoor Fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
16
CS-A28
BKP5
/CU-A28
BKP5