Horizontal Airflow Direction Auto-Control
     • 
• 
• 
• When set a Airflow Direction Auto-Control with remote
control, the vanes swings left and right as shown in the
diagram.
     • 
• 
• 
• The vanes does not swing when the Indoor Fan Motor stops
during operation at 22° angle.
     • 
• 
• 
• When stopped with remote control, the discharge vent is
reset, and stopped at the reset position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 44° to 14° - 30° under
Cooling and Soft Dry operation mode.
Horizontal Airflow Direction manual Control
     • 
• 
• 
• When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction vane move left and right in the range shown in the
diagram.
The louver can be adjusted by pressing the button to the
desired vane position.
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
2. In Heating operation, when the piping air temperature reaches 38°C, the airflow direction is Auto Swing left and right (8°-36°). When the
piping air temperature falls to 35°C, the airflow direction is stop at 22° angle.
     • 
• 
• 
• When the remote control is used to stop the operation, the vanes is reset, and stopped at reset position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 0°, 11°, 22°, 33°, 44° to 14°, 18°,
22°, 26°, 30° under Cooling and Soft Dry operation mode.
8.8. Delay ON Timer Control
     • 
• 
• 
• When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
     • 
• 
• 
• For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
     • 
• 
• 
• For Heating mode, the operation will start 30 minutes before the set time.
     • 
• 
• 
• For Automatic mode, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
8.9. Remote Control Signal Receiving Sound
     • 
• 
• 
• Long beep sound will be heard when:-
     − 
− 
− 
− Stopping the Air Conditioner using ON/OFF switch.
     − 
− 
− 
− Stopping the Quiet Mode.
     − 
− 
− 
− Stopping the Powerful Mode.
     − 
− 
− 
− Stopping the Ion Mode.
     • 
• 
• 
• Short beep sound will be heard for others.
     • 
• 
• 
• To switch off the beep sound:-
Press the “Automatic Operation Button” continuously for 10 seconds or more (“beep” “beep” will be heard at the 10th second).
Repeat the above if you want to switch ON the beep sound.
However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated.
If you do not require this operation, you may change it by using the remote control.
29
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
8.10. Powerful Mode Operation
Purpose of this operation is to be obtain the setting temperature quickly.
 1. Cooling and Soft Dry Mode
     • 
• 
• 
• When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C). This operation automatically will be running under SHi Fan Speed (Cooling), Lo-
Fan Speed (Soft Dry).
     • 
• 
• 
• Vertical Airflow Direction:-
In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
In “Auto” setting, the vane will automatically swing up and down. However the upper and lower limit will be shifted 10°
downward.
 2. Heating Mode
     • 
• 
• 
• When the Powerful Mode is set, the set temperature will be automatically increased 3°C against the present setting
temperature (Higher temperature: 30°C).
     • 
• 
• 
• The Fan Speed will shift as shown below:
     • 
• 
• 
• Vertical Airflow Direction:-
In “Manual” setting, the vane will automatically shift down 5° lower than previous setting.
In “Auto” setting, the vane will automatically shift between upper and lower limit depending on the intake air temperature as
Heating Mode, Airflow Direction Auto-Control. However the upper and lower limit will be shifted 5° downward.
 3. Powerful mode will operate for 15 minutes only.
 4. Powerful Mode will stop if:
     • 
• 
• 
• Powerful mode button is pressed again.
     • 
• 
• 
• Stopped by ON / OFF switch.
     • 
• 
• 
• Timer-off activates.
     • 
• 
• 
• Quiet mode button is pressed.
     • 
• 
• 
• Operating mode button is changed.
30
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
8.11. Ionizer Operation
Purpose
To provide fresh air effect to user by discharging minus Ion to air.
Control Condition
a. Ionizer Only Operation.
 1. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed.
Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1
→ 2)
However, fan speed can be adjusted later by customer during this operation.
Airflow direction (Horizontal Vane) control:
Follow vane direction control at cooling mode.
Horizontal vane can be changed by customer during ion only operation.
 2. Ion only operation can be off by pressed ION button again. (2
→ 1)
 3. It can be changed to previous operated mode (Auto, Cool, Dry, Heat) + ion operation by OFF/ON switch. (2
→ 4)
 4. During ion only operation, if power failure occur, after power resume, ionizer & air-conditioner resumes immediately.
 5. After error = 24 times, (about 11h 30 min.), ion & fan off with Ion LED blinks continuously.
(Detail refer to Ionizer Error detection control.)
b. Operation Mode + Ionizer Operation.
 1. Ionising Operation Start Condition
When air-conditioner unit is in “ON” condition (Cool, Dry, Heat, Auto mode) and ION operation button at remote control is
pressed. Ionizer on & ION LED illuminates. (3
→ 4)
Power LED also illuminates.
 2. Ionising Operation Stop Condition
When one of the following condition is satisfied, ION operation stops.
 a. Stopped by ON/OFF switch.
 b. Timer OFF activates.
 c. 
ION operation button is pressed again.
 d. ION feedback signal shows error.
31
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
 3. Ionizer operation status is not memorised by Micon. After OFF, when operation is “ON” again, air-conditioner operates
without ionizer operation.
However, during Cool mode etc + ionizer operation, if there is a power failure & then power resume, air conditioner shall on
at that mode + ionizer operation.
c. Timer during ionizer operation
Refer to case study in next for detail.
8.11.1. Ionizer Operation case study
8.11.2. Ionizer Error Detection Control
A. Purpose
To inform user that error occurs at ionizer system so that repairing job can be carried out.
B. Two type of error detection control:
(a) When Ionizer is ON (example case: Ionizer shorted, ionizer over current protection)
     • 
• 
• 
• During ionizer ON operation, when feed back voltage = Lo (micon input) is detected, Ion is OFF. If feedback = Lo for 11
hrs 30 min, ION LED blinks continuously.
     • 
• 
• 
• To cancel ion LED blinking, press ion button at remote control (or Auto operation switch at air conditioner unit). If ion
button is pressed again, ion LED blinks again.
     • 
• 
• 
• The error can be reset by:
i) Operation ON/OFF button press to operation OFF.
ii) Auto operation switch press to operation OFF.
iii) Operation OFF due to Timer OFF reach.
iv) Timer set ON & operation from ON to OFF.
(b) When Ionizer is OFF (example case: ionizer connecting wire loose)
     • 
• 
• 
• During air conditioner is at standby or ON operation and ionizer at OFF condition, if ionizer feed back voltage = Hi (micon
input) is detected, Ionizer breakdown detection control is activated and ion LED immediately blinks.
     • 
• 
• 
• To cancel Ion LED blinking, press ion button at remote control (or Auto operation switch at air conditioner unit). If ion
button is pressed again, ion LED blinks again.
     • 
• 
• 
• During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become OK), ion LED will stop blinking.
32
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
Page of 89