DOWNLOAD Panasonic CS-A18CKE / CU-A18CKE / CS-A24CKE / CU-A24CKE Service Manual ↓ Size: 11.68 MB | Pages: 89 in PDF or view online for FREE

Model
CS-A18CKE CU-A18CKE CS-A24CKE CU-A24CKE
Pages
89
Size
11.68 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
cs-a18cke-cu-a18cke-cs-a24cke-cu-a24cke.pdf
Date

Panasonic CS-A18CKE / CU-A18CKE / CS-A24CKE / CU-A24CKE Service Manual ▷ View online

Automatic Fan Speed Mode
 2. QLo fan speed (Transistor Motor)
 3. QLo fan speed (Induction Motor)
When Automatic Fan Speed is selected at Remote Control during cooling operation.
     • 
• 
• 
• Fan speed rotates in the range of Hi to Me.
     • 
• 
• 
• Deodorizing Control.
17
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
Cooling Operation Time Diagram
Quiet Operation Control
(For Cooling Mode or cooling region of Soft Dry Mode)
     • 
• 
• 
• Purpose of this operation is to provide quite cooling operation compare to normal operation.
     • 
• 
• 
• When the Quiet Mode is set at the remote control, Quiet Mode LED illuminates, the sound level will be automatically decreased
3 dB, against the present sound level operation.
     • 
• 
• 
• Quiet setting of fan speed rpm refer to Indoor Fan Speed Control.
     • 
• 
• 
• Dew formation become severe at Quiet Lo cool, therefore:
i) For Transistor Motor
Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+100). After that, it goes back to QLo+180 rpm. (However
quiet LED remains on).
ii) For Induction Motor
Quiet Lo Cool is operated only 1h 30 minute (1h QLo, 30 min QLo+80). After that, it goes back to QLo+170 rpm. (However quiet
LED remains on).
18
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
     • 
• 
• 
• Manual Fan Speed:-
     − 
− 
− 
− RPM control during Lo cool
     − 
− 
− 
− RPM control during Hi & Me cool
     • 
• 
• 
• Auto Fan Speed:-
     • 
• 
• 
• Quiet Mode Operation will stop if:-
     − 
− 
− 
− Quiet mode button is pressed again.
     − 
− 
− 
− Stopped by ON/OFF switch.
     − 
− 
− 
− Timer OFF activates.
     − 
− 
− 
− Powerful mode button is pressed.
19
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
Time Delay Safety Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
Automatic Fan Speed Mode
8.3. Soft Dry Mode Operation
     • 
• 
• 
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
     • 
• 
• 
• During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
     • 
• 
• 
• Once room temperature reaches below Soft Dry OFF temperature. Indoor Fan, Compressor and Outdoor Fan stop for 6
minutes.
     • 
• 
• 
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.
     • 
• 
• 
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
     • 
• 
• 
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
     • 
• 
• 
• Same as Anti-Dew Formation Control for Cooling Mode operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
     • 
• 
• 
• Fan speed off and on at Lo- speed.
     • 
• 
• 
• Deodorizing Control.
20
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE
Page of 89
Display

Click on the first or last page to see other CS-A18CKE / CU-A18CKE / CS-A24CKE / CU-A24CKE service manuals if exist.