Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
ƒU
Auto Operation for Heating.
- Compressor ON temperature; Setting temperature 
- Compressor OFF temperature; Setting temperature +3°C
ƒU
1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button,
louver moves as following cycle.
–16–
Intake Air temp.
below 20°C 
over 20
¡
~below 21°C
Setting temp.
20°C 
Intake air temp. +0.5°C
21.5°C
20°C
20°C
Intake-Air temp.
Setting temp.
20.5°C
21°C
MODE0
MODE1
MODE2
MODE3
MODE4
MODE5
MODE6
MODE9
(CLOSED)
End
Start
6. Natural wind by CHAOS logic
–17–
For more fresh feeling than other fan speed mode, press
the indoor fan Speed Selector and set to CHAOS mode.
In this mode, the wind blows like natural breeze by auto-
matically changing fan speed according to the CHAOS
logic.
Intake Air temp.
OUTDOOR FAN/COMP.
INDOOR FAN
: Setting fan speed
: LOW 
Cooling on temp.
(Setting temp.+0.5)
Setting CHAOS Natural wind
Setting temp.
Cooling off temp.
(Setting temp.-0.5)
: CHAOS Natural wind
: COMP ON
: COMP OFF 
GRAPH of Natural wind by the CHAOS logis (During Cooling operation)
Intake Air temp.
30sec
OUTDOOR FAN/COMP.
INDOOR FAN
: Setting fan speed
: LOW 
Heating off temp.
(Setting temp.+3.0)
Setting CHAOS Natural wind
Heating on temp.
(Setting temp.)
: CHAOS Natural wind
: COMP ON
: COMP OFF 
GRAPH of Natural wind by the CHAOS logis (During Heating operation)
LOW OR STOP 
–18–
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.
• For Heating Model
INDOOR FAN
4-WAY VALVE
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
26
°
C
28
°
C
Indoor piping temp.
Intake Air temp.
Setting temp. +3.0˚C
(Compressor OFF)
Setting temp.
(Compressor ON)
minimum
1min.
minimum
3min.
Fan
Stops
Low
Fan
Low Fan
Low Fan
Fan Stop
Selected Fan
Selected
Fan
Low
Fan
Selected
Fan
minimum
3min.
minimum
30sec.
minimum
1min.
OUTDOOR FAN
COMPRESSOR
8. Hot-Start Control
ƒU
The indoor fan stops until the evaporator piping temperature will be reached to 28
¡
.
ƒU
During heating operation, if piping temperatures falls below 26°C fan stops.
ƒU
The operation diagram is as following.
PIPING
TEMPERATURE
1min
COMPRESSOR
INDOOR FAN
ON
26
°
C
: Selected Fan
: Low Fan
: Fan Stop
28
°
C
–19–
9. Deice Control  
(  ); LV-B2461HL
• Deicing operation is controlled by  timer and sensing the outdoor piping temperature.
• The first deicing starts only when the outdoor pipe temperature falls below -6°C after 45(30) minutes passed
from starting of heating operation.
• Deicing ends after 10(6) minutes passed from starting of deice operation or when the outdoor pipe temperature
rises over 12°C even if before 10(6) minutes.
• The second deicing starts only when the outdoor pipe temperture falls below -6°C after 45(30) minutes passed
from ending of the first deicing.
More than 45(30) minutes 
of heating operation
Within 
10(6) minutes
Deicing
Deicing
ON
OFF
ON
ON
ON
ON
OFF
OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6
°
C
DEICE ON
12
°
C
DEICE OFF
The outdoor
piping Temp.
ON
More than 45(30) minutes 
of heating operation
HOT-
START
ON
OFF
ON
INDOOR FAN
Low Fan
Low Fan
Intake Air temp.
Setting temp. +1.0˚C
(Compressor ON)
Setting temp. -0.5˚C
(Compressor OFF)
Setting temp.
2min.58sec.
2min.58sec.
10min.
10min.
7min.
Within 7min. Cooling
Cooling
OUTDOOR FAN
COMPRESSOR
Selected
Fan
Selected
Fan
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
10. Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the opera-
tion mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In micom dehumidify mode, control of fan speed is as following. 
Page of 61