3. Evacuation 
(All amount of refrigerant leaked)
• Procedure 
(1) Connect the vacuum pump to the center hose
of charge set center hose 
(2) Evacuation for approximately one hour.  
–  Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).  
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump. 
–  Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed. 
Lo
Open
Open
Vacuum pump
2-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
–50–
4. Gas Charging 
(After Evacuation)
• Procedure 
(1) Connect the charge hose to the charging
cylinder. 
–  Connect the charge hose which you dis-
connected from the vacuum pump to the valve
at the bottom of the cylinder. 
– If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid. 
(2) Purge the air from the charge hose.   
–  Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air. (Be careful of the liquid
refrigerant).  The procedure is the same if
using a gas cylinder. 
(3) Open the valve (Lo side on the charge set and
charge the system with liquid refrigerant.
–  If the system can not be charged with the
specified amount of refrigerant, it can be
charged with a little at a time (approximately
150g each time) while operating the air
conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1
minute and then repeat the procedure
(pumping down-pin).
(4) Immediately disconnect the charge hose from
the 3-way valve’s service port. 
–  Stopping partway will allow the gas to be
discharged.
– If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose. 
(5) Mount the valve stem nuts and the service
port nut. 
– Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.
– Be sure to check for gas leakage. 
\
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner. 
Lo
Charging
cylinder 
Outdoor unit
Indoor unit
Liquid side
Gas side
CLOSE
Open
2-Way
valve
3-Way
valve
OPEN
Open
Check valve
(1)
–51–
Cycle Troubleshooting Guide 
Trouble analysis 
1. Check temperature difference between intake and discharge air and operating current. 
Temp. Difference 
Temp. difference   :   approx. 0°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   approx. 8°C
Current                  :   less than 80% of 
rated current  
Temp. difference   :   less than 8°C
Current                  :   over the rated
current 
Temp. difference   :   over 8°C 
Operating Current 
All amount of refrigerant leaked out
Check refrigeration cycle
Refrigerant leakege
Clog of refrigeration cycle
Defective compressor 
Excessive amount of refrigerant
Normal 
Notice : 
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger. 
2. Check temperature and pressure of refrigeration cycle. 
Notice : 
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition. 
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty. 
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
Defective compressor
Current is low
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of 
operation
Insufficient amount of 
Current is low
Lower 
Higher
refrigerant (Leakage)
Clogging
Current is low 
High 
Higher  
–52–
Product Specifications (Cooling Only) 
Model Name
Item
Unit
Cooling Capacity
Btu/h(kcal/h)
18,000(4,536)
24,000(6,048)
Moisture Removal
§⁄
/h
2.5
3.5
Power Source
ø, V, Hz
,
220-240V, 50Hz
Indoor
14.0
16.0
Outdoor
50
50
Input
W
1,935
2,500
Running Current
A
9.0
11.9
E.E.R.
Btu/h-W
9.3
9.6
Indoor
1,200 x 205 x 615
Outdoor
870 x 655 x 320
Indoor
30
Outdoor
57
57
Refrigerant (R-22)
g
880
1,550
Airflow Direction Control (Up & Down)
§
§
Remocon Type
L.C.D Wireless
Liquid
1/4" (6.35)
1/4" (6.35)
Gas
1/2" (12.7)
5/8" (15.88)
Sleeping Operation
§
§
Drain Hose
§
§
Connecting Wire
0.75mm
2
¤C
Main Power Cable
1.5mm
2
¤C
2.5mm
2
¤C
(
2.0mm
2
:for the Middle East)
Time Delay Safety Function
§
Air Circulation
§
Soft Dry
§
Fan Speed (Indoor)
3 (Hi, Med, Low)
Timer
24Hrs
Self-Diagnosis
§
Auto-Restart
§
Air Circulation
m
3
/min
Dimensions
(W
¡¿
H
¡¿
D)
Net. Weight
mm
kg
LV-B1861CL
LV-B2461CL
–5–
Service Valve & 
Connecting Tube
Page of 61
Display

Click on the first or last page to see other LV-B1861HL service manuals if exist.