24 Floor Standing Type Air Conditioner
Installation
No.
Installation Parts, Tools
Use
1
Flaring tool (Ø 6,35 - Ø 19,05)
Flaring the pipes
2
Reamer
Remove burrs from cut edges of pipes.
3
Pipe cutter (Max 35mm Copper pipe)
Cutting the pipings
4
Wrench (H5, H4 hexagonal wrench)
To open the service valve
5
Pipe bender
Bending the pipings
6
Leak detector
Check the gas-leakage of connecting part of the pipings
7
Manifold gauge
To measure the pressure, to charge the refrigerant
8
Charge-nipple
To connect the bombe
9
Vacuum pump
To remove the air in the pipe.
10
Charge cylinder balance 
To measure the refrigerant amount
11
Bombe (Freon-22)
Gas charge
Air purge
Cleaning the pipe
12
Spanner
To tighten the connecting parts of the pipings
13
Monkey spanner
14
Driver(   ,    )
15
Benchi (150mm)
Cutting the wires
16
Tapeline
To measure the length
17
Core drill
To make holes through the concrete to wall and blocks
18
Voltmeter, Amperemeter, Clampmeter 
To measure the current and voltage
19
Insulation resistance tester
To measure the insulation resistance
20
Glass thermometer
To measure the intake and outlet air temperature of 
the indoor unit
21
Copper tubes
To use the connecting pipings
22
Insulation material
To cover the connecting pipings
23
Tape
To finish the connecting pipings
24
Electrical leakage Breaker
To shut off the main power
25
Cable
To connect the cable from outdoor unit to indoor unit
26
Drain hose sockets, elbows
To remote the condensing water
2) Preparation of installation parts and tools
Service Manual  25
Installation
1) Preparation of pipings
Cut the pipes and the cable
• Use the accessory piping kit or the pipes 
purchased locally.
• Measure the distance between the indoor and the
outdoor unit.
• cut the pipes a little longer than measured 
distance.
• Cut the cable 1.5m longer than the pipe length.
Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end down to avoid the metal powder
entering the pipe.
Caution:
If burrs are not removed, they may cause gas 
leakage.
Flaring the pipes.
• Insert the flare nuts, mounted on the connection
ports of both indoor and outdoor unit, onto the 
copper pipes. Some refrigerant gas may leak,
when the flare nuts are removed from the indoor
unit, as some gas is charged to prevent the inside
of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool
about 0~0.5mm higher. (See illustaration)
• Flare the pipe ends.
Tape the flaring part to protect it from dust or 
damages.
4
3
2
1
= Improper flaring =
Inclined
Cracked
 Surface
damaged
 Uneven
thickness
Bar
0~0.5mm
Copper
pipe
Clamp handle
Bar
Handle
Yoke
Cone
Red arrow mark
Pipe
Point down
Reamer
90
°
Pipe cutter
Slanted
Rough
Piping of indoor unit
26 Floor Standing Type Air Conditioner
Installation
2) Connection of pipings
Move the indoor tubing and drain hose to the hole
• Remove tubing holder and pull the tubing out of the
chassis.
Replace the tubing holder into original position 
Route the tubing and the drain hose staight 
backwards.
Insert the connecting cable into the indoor unit
through the hole.
• Do not connect the cable to the indoor unit
• Make a small loop with the cable for easy 
connection later.
Tape the tubing and the connecting cable.
Indoor unit installation.
Connecting the pipings to the indoor unit.
• Align the center of the pipings and suffciently 
tighten the flare nut with fingers.
• Finally, tighten the flare nut with troque wrench until
the wrench clicks.
When tightening the flare nut with troque wrench,
ensure the direction for tightening follows the arrow
on the wrench.
3) Pre-cautions in bending
If it is necessary to bend or stretch the tubing,
use the Spring which is attached to the tubing
instead of pipe bender.
• Please make a careful notice to make a smooth line.
• Hold the tubing with your two hands closely and then
bend or stretch it slowly not to make any crack.
• Remember that the radius (R) should not exceed 70
mm (Refer to Fig. 1).
Do not repeat the bending process to prevent the
tubing from cracking or curshing.
Keep in mind that the bending part should not be
cracked, and make the radius (R) as long as possi-
ble (Refer to Fig.2)
Spring
R70mm
Fig. 1
Fig. 2
R
Indoor unit tubing
Flare nut
Pipings
Torque wrench
Spanner
Pipe Size
Torque
3/8"
4.2 Kg.m
3/4"
6.5 Kg.m
Service Manual  27
Installation
The inside and outside connecting cable can be connected after opening the inlet grille.
Open the inlet grille manually.
Open the control cover with Driver (      )
Connect the wire to the housing on the control board.
Secure the cable onto the control board with clamp.
Secure the control cover to the original position with 
the screw.
Close the inlet grille.
Connecting the cable to indoor unit
Page of 127