20 Floor Standing Type Air Conditioner
Operation details
12. Off Timer Function
This function is to set the time of stopping the unit operation.
The procedure is as the following.
1st: Press the timer set button on the Remocon.
2nd: The buzzer sounds and then the display window shows the Off-Time to be set as 1:00
...
7:00
0:00.
- The Off-Time is shifted as the following by each press.
- If you select '0:00', the Off-Timer function will be cancelled.
- During Off-Timer Operation, if you repress the timer set button, the rest time will be displayed.
- During Off-Timer Operation, if you repress the timer set button, the rest time will be displayed.
13. Alarm mode display / only displayed while operating.
CH 0
: The sensor for sensing room temperature is open or short.
CH 1
: The sensor for sensing piping temperature of evaporator is open or short.
14. Function for test operation.
This function shall be operated while the set not operating and start while set temperature set button(
▼
) down
and start/stop buttons pressing continuously for 3 seconds.
If you press start/stop button continuously for 3 seconds while set temp down button pressing once more test
operation and the set shall be stopped.
After test operation operating and 18 minutes, test operation and the set shall be stopped.
If you press start/stop button while test operation operating, test operation shall be stopped and the set shall
start.
If you press start/stop button continuously for 3 seconds while set temp down button pressing once more test
operation and the set shall be stopped.
After test operation operating and 18 minutes, test operation and the set shall be stopped.
If you press start/stop button while test operation operating, test operation shall be stopped and the set shall
start.
When test operation operating, the display of
88:88
shall be shifted to tESt
4-way valve is always off when test operation.
Fan speed is high, air purifying system and auto air flow operations are off when test operation.
Regardless of outside temperature, the set operates when test operation.
All but start/stop and air purifying system buttons cannot be set.
Fan speed is high, air purifying system and auto air flow operations are off when test operation.
Regardless of outside temperature, the set operates when test operation.
All but start/stop and air purifying system buttons cannot be set.
15. Function of changing set temperature when re-operation after stop.
Heating operation is set to the previous set temperature when re-operation after stop. Cooling operation is set
to the previous set temperature when re-operation with start/stop button.
to the previous set temperature when re-operation with start/stop button.
1.Operation mode.
Cooling/soft dry mode
→
Cooling mode
Heating mode
→
Heating mode
2. Setting the set temperature when cooling operation.
Room temperature > Set temperature: to be set to the previous set temperature.
Room temperature
Room temperature
≤
Set temperature
a) Room temperature
≥
26°C: to be set to 24°C
b) 22°C
≤
Room temperature
≤
25°C: to be set to 21°C
c) Room temperature
≤
21°C:to be set to -1°C less than room temperature.
3. Setting the set temperature when heating operation.
Set the previous set temperature when stopped.
16. Auto Restart
In case the power comes on again a power failure, Auto Restarting Operation is the function to operate proce-
dures automatically to the previous operating conditions.
dures automatically to the previous operating conditions.
1:00
2:00
3:00
4:00
5:00
6:00
7:00
0:00
Service Manual 21
Installation
1) Select the best location
Indoor unit
• There should not be any heat source or steam near
the unit.
• There should not be any obstacles to prevent the air
circulation.
• The place where air circulation in the room will be
good.
• The place where drainage can be easily obtained.
• The place where noise prevention is taken into con-
• The place where noise prevention is taken into con-
sideration.
• Do not install the unit near the door way.
• Ensure the space indicated by arrows from the wall,
• Ensure the space indicated by arrows from the wall,
ceiling, fence, or the obstacles.
Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat radia-
tion from the condenser is not restricted.
tion from the condenser is not restricted.
• There should not be any animals or plants which
could be affected by discharged hot air.
• Ensure the space indicated by arrows from the wall,
ceiling, fence, or other obstacles.
Piping length and the elevation.
MODEL
MAX. Piping length
A (m)
5HP
30
25
MAX.
elevation
B (m)
A
B
Indoor unit
Outdoor unit
Wall
More
than
50cm
than
50cm
More than
50cm
50cm
More than
50cm
50cm
More than
100cm
100cm
Outdoor
unit
unit
5cm
5cm
40cm
100cm
Indoor unit
Installation
Installation of indoor, Outdoor Unit
22 Floor Standing Type Air Conditioner
Installation
2) Indoor Unit installation
The mounting floor should be strong and solid
enough to prevent it from vibration.
Drill the piping hole with 70mm diameter hole-core
drill at either the right or the left of indoor unit. The
hole should be sightly slant to the outdoor side.
enough to prevent it from vibration.
Drill the piping hole with 70mm diameter hole-core
drill at either the right or the left of indoor unit. The
hole should be sightly slant to the outdoor side.
Insert the plastic tube through the hole.
Cut the extruded outside part of the plastic tube, if
necessary.
necessary.
3) Outdoor unit Installation
Install the outdoor unit on the concrete or any solid
base securely and horizontally by securing it with
bolts (Ø12mm) and nuts.
If there is any vibration transmitted to the building,
mount the rubber underneath the outdoor unit.
base securely and horizontally by securing it with
bolts (Ø12mm) and nuts.
If there is any vibration transmitted to the building,
mount the rubber underneath the outdoor unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with the
rated amount of refrigerant including additional
amount required for air-purging, subject to 5m piping
length. (The rated amount of refrigerant is indicated
on the name plate.) But when the piping length
exceeds 5 meters, additional charge is required
according to the following table.
rated amount of refrigerant including additional
amount required for air-purging, subject to 5m piping
length. (The rated amount of refrigerant is indicated
on the name plate.) But when the piping length
exceeds 5 meters, additional charge is required
according to the following table.
(Unit: g)
Example) In case of 10m long pipe(one-way), the
amount of refrigerant to be replenished is:
(10 – 5)
(10 – 5)
×
50 = 250g
Wall
Core Drill
Tilt
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
(Bushing)
INSIDE
OUTSIDE
200mm
70mm
70mm
89mm
REFRIGERANT CHARGE
50g per 1 m
MODEL
5HP
Service Manual 23
Installation
1) Procedure
No.
Installation works
Descriptions
1
Preparation of tools and installation parts
Preparation of installation
2
Flaring the pipes
To insert the flare nuts, mounted on the connection
parts of both indoor and outdoor unit, onto the
copper pipes.
parts of both indoor and outdoor unit, onto the
copper pipes.
3
Pipe bending
To reduce the flow resistance of refrigerant.
4
Connection of installation parts
Connection of long piping
(elbows, socket etc)
5
Tighten the flare nut (outdoor)
Connecting the pipings of the outdoor unit.
6
Blowing the pipings
To remove dust and scale in working.
7
Tighten the flare nut (indoor)
Connecting the pipings of the indoor unit.
8
Check the gas-leakage of the connecting
part of the pipings.
part of the pipings.
9
Air purging of the piping and indoor unit
The air which contains moisture and which
remains in the refrigeration cycle may cause malfunction
on the compressor
remains in the refrigeration cycle may cause malfunction
on the compressor
10
Open the 3-way (liquid side) and
3-way (gas side) valves.
3-way (gas side) valves.
11
Form the pipings
To prevent heat loss and sweat
12
Checking the drainage (indoor unit)
To ensure if water flows drain hose of indoor unit.
13
Connecting the cable between outdoor and
Preparation of the operating
indoor unit
14
Connecting the main cable to outdoor unit
15
Supply the power to the crankcase heater
To prevent the liquid back to the compressor.
(before the operating the unit)
(Heat pump only)
16
Cooling operation, Heating operation
To confirm the operation of the unit.
(Use the remote controller or display of the indoor unit)
Installation Method