Sharp AY-AP24 (serv.man12) Service Manual ▷ View online
21
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
AY-AP24CS
AE-A18CS
AE-A24CS
For AY-AP24CS / AE-A24CS
The room is not cooled at all
or not cooled.
The compressor does not operate.
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The running capacitor may be defective.
Refrigerant may be leaked.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
Push the button "AUX." on
the indoor unit, for more than 5 sec.
the indoor unit, for more than 5 sec.
Is the
voltage between
terminal of black lead
wire on the relay in the out door
unit and terminal "N"on the
terminal board the power
supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
YES
NO
NO
Replace the PWB ass'y with a new one.
Replace the relay in the outdoor unit
with a new one.
with a new one.
Using a tester, measure voltage at
the terminals on the terminal board.
the terminals on the terminal board.
Is the voltage
between terminal "N" and
"4" in the outdoor unit the power
supply voltage ?
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
AY-AP24CS
AE-A18CS
AE-A24CS
22
The room is not heated at all or not heated.
The compressor does not operate.
The compressor does not operate.
The control circuit board is normal.
Refrigerant may be leaked.
The running capacitor may be defective.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The thermistor may be defective.
Refrigerant may be leaked.
The running capacitor may be defective.
The outdoor fan motor may be defective.
The outdoor fan motor capacitor may be defective.
The compressor may be defective.
The thermistor may be defective.
Is the voltage
between terminal "N" and
"4"("1" ..... AY-AP18CS) of the
terminal board the power
supply voltage ?
NO
Replace the PWB ass'y with a new one.
Push the button of "AUX" on the indoor
unit, for more than 5 sec.
unit, for more than 5 sec.
Using a tester, measure voltages at the
terminals on the terminal board.
terminals on the terminal board.
Select HEAT MODE with remote controller.
And then start operation.
And then start operation.
Is the voltage
between terminal "N" and
"2" of the terminal board the
power supply voltage ?
Is the voltage
between terminal "N" and
"3" of the terminal board the
power supply voltage ?
YES
YES
YES
NO
NO
23
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
AY-AP24CS
AE-A18CS
AE-A24CS
REFRIGERATION CYCLE
Figure R-1. Flow of Refrigerant for AY-AP18CS
Figure R-2. Flow of Refrigerant for AY-AP24CS
s
1
4
C
2
Capillary
tube A
tube A
Capillary
tube B
tube B
Capillary
tube D
(Lower row)
tube D
(Lower row)
Capillary
tube C
(Upper row)
tube C
(Upper row)
Accumulator
3
Strainer
Heating
Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling
Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
Sub
Accumula
-tor
Accumula
-tor
s
1
4
C
2
Capillary
tube A
tube A
Capillary
tube B
tube B
Capillary
tube C
(2 pieces)
tube C
(2 pieces)
Accumulator
3
Strainer
Heating
Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling
Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
AY-AP24CS
AE-A18CS
AE-A24CS
24
Cycle temperature and service port pressure
SASO 385 condition
Dimension of Capillary tube
O.D.
I.D.
L
Capillary tube A
ø 3.2
ø 2.0
500
Capillary tube C
(Upper row)
ø 2.7
ø 1.6
150
Capillary tube D
(Lower row)
ø 2.7
ø 1.6
244
O.D.
I.D.
L
Capillary tube A
ø 3.5
ø 2.4
600
Capillary tube B
ø 3.5
ø 2.4
400
Capillary tube C
(2 pieces)
ø 3.6
ø 1.8
100
For AY-AP18CS
For AY-AP24CS
Indoor side
Outdoor side
Temperature (˚C)
Temperature (˚C)
Relative humididity (%)
Relative humididity (%)
29
39
46
15
Cooling
21
-
7
87
Heating
Cooling
Heating
NO. Condition
Model
AY-AP18CS
1
2
3
4
Service port pressure
100˚C
81C
56˚C
2˚C
15˚C
41˚C
4˚C
0.51MPa
1.73MPa
Cooling
Heating
AY-AP24CS
97˚C
88˚C
54˚C
31˚C
14˚C
45˚C
4˚C
-2˚C
-3˚C
0.51MPa
1.80MPa
Based on 'SASO 385 / 1983'
(at 220V refrigerant pipes length 7.5m)
(at 220V refrigerant pipes length 7.5m)
Click on the first or last page to see other AY-AP24 (serv.man12) service manuals if exist.