17
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
20.
Diagnosis procedure at indoor unit
When indoor fan motor is out of order or compressor lock occurs, the compressor, indoor fan motor, outdoor
fan motor, and louver are all stopped and the operation LED(red) turns on or off synchronously with the timimg
of the timer LED.
When the thermistor for room temperature or pipe temperature is open or short state, the operation LED turns
on or off synchronously with the timing of the timer LED by pushing continously for more than 5 seconds
"AUX." button during suspension of operation.
Timing chart of Timer LED and Operation LED of DIAGNOSIS PROCEDURE.
When "OI" button the remote controller or "AUX." button in the unit is pushed, the unit is free from
DIAGNOSIS PROCEDURE.
When the louver unit is not properly installed, all lamps on the indicator panel will blink, operation are all stop
and remote signal is not accept.
Indoor 
fan motor
Comp.-lock
Thermistor 
short state
Thermistor 
open state
Timer 
LED
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Operation 
LED
Operation 
LED
Operation 
LED
Operation 
LED
1sec.
1sec.
4sec.
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
18
TROUBLESHOOTING GUIDE OF CONTROL CIRCUIT
measure the secondary voltage
of transformer.
YES
NO
YES
NO
The machine does not function
at all with remote controller and
switch on the indoor unit. 
Using a tester, measure the 
voltage between anodes of D1 
and D2 on PWB ass'y.
Is the measured value 
approx. 17.5 Vac ?
Replace the PWB with a new 
one.
Is the WPE1
open  circuit ?
Replace the fuse and varistor 
with new ones.
Replace the transformer with
a new one.
OK
FAIL
Check  the  cleaning
switch  2(1), the connector 
CN9(8) and lead  wires.
Replace the cleaning switch  2(1).
(or  reset  connector)
19
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
YES
NO
NO
YES
The machine does not function
with remote controller 
Push button "O/I" on the 
wireless remote controller.
Is transmitting
indicator of the remote 
controller active ?
Is indicator lamp of
indoor unit proper ?
Replace the 
PWB  with a 
new one.
Does beep sound
from the indoor unit ?
Using a tester,
measure the voltage
between terminals
of resistor R26
on the PWB ass'y.
Push the button "O/I".
Are batteries of the
wireless remote controller 
proper ?
Replace the batteries 
with new ones.
Replace the wireless
remote controller.
When the signal is
received, does the voltage
change ?
Replace the PWB with a new 
one.
PWB is normal.
Inspect the outdoor unit.
NO
YES
NO
YES
Replace the photo 
detector unit with a new 
one.
NO
YES
AY-AP18CS
AY-AP24CS
AE-A18CS
AE-A24CS
20
For AY-AP18CS / AE-A18CS
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
The control circuit is normal.
   The compressor may be defective.
   The running capacitor may be defective.
   Refrigerant may be leaked.
   The outdoor fan motor may be defective.
   The outdoor fan motor capacitor may be defective.
Push the button "AUX." on 
the  indoor unit, for more than 5 sec.
Is the voltage
between terminal "N" and
"1" of the terminal board the
power supply voltage ?
Are the resistances
conformed Fig. 1 ?
Replace the thermistor ass'y with a new one.
NO
YES
YES
NO
Replace the PWB ass'y with a new one.
Fig. 1
Using a tester, measure voltage at
the terminals on the terminal board.
100
80
60
40
20
0
-10
0
10
20
30
40
Resistance
Thermistor
Room temperature
Heat exchange
Color
Yellow
Orange
To measure the resistance, first remove 
the connector as shown at right.
Room temperature 
thermistor TH1
Tester
Connector
No. 3 to 4
No. 1 to 2
Fig. 1 Temperature properties of  indoor thermistors
K
Heat exchange thermistor 
TH2 (orange)
25
°C resistance 15 K 
Room temperature 
thermistor TH1 (yellow)
25
°C resistance 10 K
Heat exchange 
thermistor TH2
Tester
4
1 CN4
Page of 44
Display