Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online
14
4. Location of Controls and Components
4.1 Indoor
Unit
4.1.1 Location of Control
Buttons / Indicator
Water pressure gauge
• Do not press or hit the glass cover using hard
and sharp objects. Failure to do so may cause
damage to the unit.
• Ensure that the water pressure is between 0.05
and 0.3 MPa (0.1 MPa = 1 bar).
• In case the water pressure is out of the above
range, consult an authorised dealer.
1
Quick Menu button
(For more details, refer to the separate
Quick Menu Guide.)
2 Back button
Returns to the previous screen
3 LCD Display
4 Main Menu button
For function setup
5 ON/OFF button
Starts/Stops operation
6
Operation indicator
Illuminates during operation, blinks during
alarm.
Press centre
No glove
No pen
2
1
4
5
6
3
Cross key buttons
Selects an item.
Enter button
Fixes the selected content.
Up
Down
t
h
g
i
R
tf
e
L
0.2
0.4
0.3
0.1
MPa
bar
2
3
1
4
23
1
44
40
10:34am, Mon
18
˚
c
˚
c
˚
c
˚
c
2
15
Display
1 Mode selection
AUTO
• Depending on the preset outdoor
temperature, the system selects
HEAT or *
1
COOL operation mode.
Auto Heat
Auto Cool
*
1,
*
2
COOL
• The fan coil unit is either turned
ON or OFF.
• The outdoor unit provides cooling
to the system.
AUTO
+ TANK
• Depending on the preset outdoor
temperature, the system selects
HEAT + TANK or *
1
COOL + TANK
operation mode.
Auto Heat
Auto Cool
*
1,
*
2
COOL
+ TANK
• The outdoor unit provides cooling
to the system.
• The system controls the booster
heater in the water tank.
HEAT
• The panel/floor HEAT operation is
either turned ON or OFF.
• The outdoor unit provides heat to
the system.
TANK
• The water tank is either turned
ON or OFF.
• The outdoor unit provides heat to
the water tank.
HEAT
+ TANK
• The outdoor unit provides heat to
the water tank and the system.
• This mode can be selected only
when the water tank is installed.
* The direction icons point to the currently
active mode.
• Room operation / Tank operation.
• Deice operation.
2 Operation icons
The status of operation is displayed.
Icon will not display (under operation OFF screen) whenever operation is OFF except weekly timer.
Holiday operation status
Weekly Timer operation status
Quiet operation status
Zone:Room Thermostat
→Internal sensor status
Powerful operation status
Demand Control or
SG ready or SHP status
Room Heater status
Tank Heater status
Solar status
Bivalent status
(Boiler)
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service partners.
*2 Only displayed when COOL mode is unlocked (This means when COOL mode is available).
*2 Only displayed when COOL mode is unlocked (This means when COOL mode is available).
3 Temperature of each zone
4 Time and day
5 Water Tank temperature
6 Outdoor temperature
7 Sensor type/Set temperature type icons
Water Temperature
→Compensation curve
Water Temperature
→Direct
Pool only
Room Thermostat
→External
Room Thermostat
→Internal
2
4
1
5
6
7
23
1
44
40
10:34am, Mon
18
˚
c
˚
c
˚
c
˚
c
2
3
16
4.1.2 Initialization
Before starting to install the various menu settings, please initiate the Remote Controller by selecting the language of
operation and installing the date and time correctly.
It is recommended that the installer conducts the following initialization of the Remote Controller.
Selecting the language
LCD blinking
Press
and wait while the display is
initializing.
1 Scroll with
and
to select the language.
2 Press
to confirm the selection.
Setting the clock
1
h
ti
w
t
c
e
l
e
S
or
how to display the time,
either 24h or am/pm format (for example, 15:00
or 3 pm).
2 Press
to confirm the selection.
3 Use
and
to select year, month, day,
hour and minutes. (Press
to confirm the
selection each time.)
4 Once the time is set, time and day will appear
on the display even if the Remote Controller is
turned OFF.
4.1.3 Quick
Menu
After the initial settings have been completed, you can select a quick menu from the following options and edit the setting.
1 Press
to display the quick menu.
Force DHW
Powerful
Quiet
Force Heater
Weekly Timer
Force Defrost
Error Reset
R/C Lock
2 Use
to select menu.
3 Press
to turn on/off the select menu.
Select
ON/OFF
17
4.1.3.1 Before
Use
This Quick Guide explains how to use the Quick Menu.
Please read the Operating Instructions thoroughly before using the Quick Menu.
Please read the Operating Instructions thoroughly before using the Quick Menu.
4.1.3.2
How to use the Quick Menu
After the initial settings have been completed, you can select a quick menu from the
following options and edit the setting.
following options and edit the setting.
Select each setting and confirm the setting
according to the instructions displayed at the
bottom of the screen. (The icons refer to each
selection key.)
according to the instructions displayed at the
bottom of the screen. (The icons refer to each
selection key.)
Quick Menu
To return to the Main Screen,
Press
or
.
Force DHW
Powerful
Quiet
Force
Heater
Weekly
Timer
Force
Defrost
Error Reset
R/C Lock
■
Note:
• If the system is not
connected to the tank
(Tank Connection is
OFF), the Quick Menu
screen will be displayed
as right. Make sure the
Tank Connection is ON.
1 Press
.
2 Use
to select menu.
3 Press
to turn on/off the select
menu.
Select
Change
Select
ON/OFF
Select
ON/OFF
23
1
44
40
10:34am, Mon
18
˚
c
˚
c
˚
c
˚
c
2
Click on the first or last page to see other WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 service manuals if exist.