DOWNLOAD Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ↓ Size: 15.68 MB | Pages: 127 in PDF or view online for FREE

Model
WH-SXC09H3E5 WH-SXC12H6E5 WH-UX09HE5 WH-UX12HE5
Pages
127
Size
15.68 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR-TO-WATER HEATPUMP
File
wh-sxc09h3e5-wh-sxc12h6e5-wh-ux09he5-wh-ux12he5.pdf
Date

Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online

 
WARNING 
18. 
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not 
properly done, the set will drop and cause injury. 
 
19. 
This equipment is strongly recommended to be installed with Residual Current Device (RCD) on-site according to the respective 
national wiring rules or country–specific safety measures in terms of residual current. 
 
20. 
During installation, install the refrigerant piping properly before run the compressor. Operation of compressor without fixing 
refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in 
explosion, injury etc. 
 
21. 
During pump down operation, stop the compressor before remove the refrigeration piping. Removal of refrigerant piping while 
compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigerant cycle and result in 
explosion, injury etc. 
 
22. 
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over tightened, after a long period, the flare 
may break and cause refrigerant gas leakage. 
 
23. 
After completion of installation, confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts 
with fire. 
 
24. 
Ventilate the room if there is refrigerant gas leakage during operation. Extinguish all fire sources if present. It may cause toxic gas 
when the refrigerant contacts with fire. 
 
25.  Only use the supplied or specified installation parts, else, it may cause unit vibrate loose, water leakage, electrical shock or fire. 
 
26. 
The unit is only for use in closed water system. Utilization in an open water circuit may lead to excessive corrosion of water piping and 
risk of incubating bacteria colonies, particularly Legionella, in water. 
 
27.  If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and information. 
 
28.  Select a location where in case of water leakage, the leakage will not cause damage to other properties. 
 
29. 
When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no 
electrical contact between equipment and building is allowed. Insulator must be installed in between. 
 
30. 
Any work carried out on the Indoor Unit / Outdoor Unit after removing any panels which is secured by screws, must be carried out 
under the supervision of authorized dealer and licensed installation contractor. 
 
31. 
This unit must be properly earthed. The electrical earth must not be connected to a gas pipe, water pipe, the earth of lightening rod or 
a telephone. Otherwise there is a danger of electrical shock in the event of an insulation breakdown or electrical earth fault in the 
outdoor unit. 
 
32. 
Do not use joint cable for outdoor connection cable. Use specified outdoor connection cable, refer to instruction CONNECT THE 
CABLE TO THE OUTDOOR UNIT 
and connect tightly for outdoor connection. Clamp the cable so that no external force will be acted 
on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection. 
 
 
 
CAUTION 
1. 
Do not install the Indoor Unit / Outdoor Unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates 
at surrounding of the unit, it may cause fire. 
 
2. 
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the 
liquid refrigerant, it may cause frostbite. 
 
3.  Do not install this appliance in a laundry room or other high humidity location. This condition will cause rust and damage to the unit. 
 
4.  Make sure the insulation of power supply cord does not contact hot part (i.e. refrigerant piping) to prevent from insulation failure (melt).
 
5. 
Do not apply excessive force to water pipes that may damage the pipes. If water leakage occurs, it will cause flooding and damage to 
other properties. 
 
6.  Do not touch the sharp aluminium fin, sharp parts may cause injury. 
 
 
7. 
Do not release refrigerant into the atmosphere. The product contains fluorinated greenhouse gases and that its functioning relies upon 
such gases. 
 
8.  Select an installation location which is easy for maintenance. 
 
9. 
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage 
the furniture. 
 
 
 
 
 
 
 
 
CAUTION 
10. 
Power supply connection to Indoor Unit. 
 
Power supply point should be in easily accessible place for power disconnection in case of emergency. 
 
Must follow local national wiring standard, regulation and this installation instruction. 
 
Strongly recommended to make permanent connection to a circuit breaker. 
Power supply 1: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
Power supply 2: Use approved 30A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. 
 
11.  Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire. 
 
12. 
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other 
properties. 
 
13. 
Installation work. 
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried 
by one person. 
 
2. Specifications 
2.1 WH-SXC09H3E5 
WH-UX09HE5 
 
Item 
Unit 
Outdoor Unit 
Performance Test Condition 
EN 14511 
Condition 
(Ambient/Water) 
A35W7 
kW 7.00 
BTU/h 23900 
Cooling Capacity 
kcal/h 6020 
W/W 3.17 
Cooling EER 
kcal/hW 2.72 
Condition 
(Ambient/Water) 
A7W35 A2W35 
kW 9.00 
9.00 
BTU/h 30700 
30700 
Heating Capacity 
kcal/h 7740 
7740 
W/W 4.84 
3.59 
Heating COP 
kcal/hW 4.16 
3.08 
Low Temperature Application (W35) 
Application Climate 
Warmer Average  Colder 
Pdesign kW 
9.0 
9.0 
11.0 
Tbivalent / TOL 
°C 
2 / 2 
-10 / -10 
-15 / -22 
SCOP / ns 
(W/W) / % 
5.95 / 235 
4.59 / 181 
4.08 / 160 
Annual Consumption 
kWh 
2020 
4049 
6651 
Class 
 
A++ A++ A++ 
Medium Temperature Application (W55) 
Application Climate 
Warmer Average  Colder 
Pdesign kW 
9.0 
9.0 
11.0 
Tbivalent / TOL 
°C 
2 / 2 
-10 / -10 
-15 / -22 
SCOP / ns 
(W/W) / % 
4.02 / 158 
3.32 / 130 
3.20 / 125 
Annual Consumption 
kWh 
2991 
5596 
8468 
Heating ErP 
Class 
 
A++ A++ A++ 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
dB (A) 
Cooling: 49 
Heating: 51 
— 
Noise Level 
Power Level dB 
Cooling: 67 
Heating: 68 
— 
Air Flow 
m
3
/min (ft
3
/min) 
Cooling: 89.5 (3160) 
Heating: 76.8 (2710) 
Refrigeration Control Device 
 
Expansion Valve 
Refrigeration Oil 
cm
3
 FV50S 
(1200) 
Refrigerant (R410A) 
kg (oz) 
2.85 (100.6) 
GWP 2088 
F-GAS 
CO2eq (ton) (Precharged / Maximum) 
5.951 / 8.039 
Height 
mm (inch) 
1340 (52-3/4) 
Width 
mm (inch) 
900 (35-7/16) 
Dimension 
Depth 
mm (inch) 
320 (12-19/32) 
Net Weight 
kg (lbs) 
101 (223) 
Liquid 
mm (inch) 
9.52 (3/8) 
Pipe Diameter 
Gas 
mm (inch) 
15.88 (5/8) 
Standard Length 
m (ft) 
7 (23.0) 
Pipe Length Range 
m (ft) 
3 (9.8) ~ 30 (98.4) 
I/D & O/D Height Difference 
m (ft) 
20 (65.6) 
Item 
Unit 
Outdoor Unit 
Additional Gas Amount 
g/m (oz/ft) 
50 (0.5) 
Refrigeration Charge Less 
m (ft) 
10 (32.8) 
Type  
Hermetic 
Motor 
Motor Type 
 
Brushless (4-poles) 
Compressor 
Rated Output 
kW 
3.00 
Type  
Propeller 
Fan 
Material  
PP 
Motor Type 
 
DC (8-poles) 
Input Power 
— 
Output Power 
60 
Fan 
Fan Speed 
rpm 
Cooling: 550 (Top), 590 (Bottom) 
Heating: 490 (Top), 530 (Bottom) 
Fin material 
 
Aluminium (Pre Coat) 
Fin Type 
 
Corrugated Fin 
Row × Stage × FPI 
 
2 × 51 × 18 
Heat Exchanger 
Size (W × H × L) 
mm 
903.7 × 1295.4 × 38.1 
ø Single 
V 230 
Power Source (Phase, Voltage, Cycle) 
Hz 50 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Input Power 
kW 
Cooling: 2.21 
Heating: 1.86 
Heating: 2.51 
Maximum Input Power For Heatpump System 
kW 
6.27 
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 29.0 / 6.27k 
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
1Ø / 13.0 / 3.00k 
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 
— / — / — 
Starting Current 
10.2 
Condition 
(Ambient/Water) 
A35W7 A7W35 A2W35 
Running Current 
Cooling: 10.4 
Heating: 8.8 
Heating: 11.8 
Maximum Current For Heatpump System 
29.0 
Power Factor 
Power factor means total figure of compressor and 
outdoor fan motor. 
Cooling: 92 
Heating: 92 
Number of core 
 
— 
Power Cord 
Length m 
(ft) 
— 
Thermostat  
Electronic 
Control 
Protection Device 
 
Electronic Control 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 service manuals if exist.