DOWNLOAD Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ↓ Size: 15.68 MB | Pages: 127 in PDF or view online for FREE

Model
WH-SXC09H3E5 WH-SXC12H6E5 WH-UX09HE5 WH-UX12HE5
Pages
127
Size
15.68 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR-TO-WATER HEATPUMP
File
wh-sxc09h3e5-wh-sxc12h6e5-wh-ux09he5-wh-ux12he5.pdf
Date

Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online

13 
3. Features 
 
  Inverter Technology 
 
- Energy saving 
 
  High Efficiency 
 
  Environment Protection 
 
- Non-ozone depletion substances refrigerant (R410A) 
 
  Long Installation Piping 
 
- Long piping up to 30 meter with height difference 20 meter 
 
- Flexible 4-way piping for outdoor unit 
 
  Easy to use control panel 
 
- Auto mode 
 
- Holiday mode 
 
- Dry concrete function 
 
- Weekly timer setting 
 
 
  A-class energy efficiency pump 
 
- Water pump speed can be set by selection at control panel 
 
  Improved deice cycle 
 
  Protection Feature 
 
- Random auto restart after power failure for safety restart operation 
 
- Gas leakage protection 
 
- Prevent compressor reverse cycle 
 
- Inner protector to protect compressor 
 
  Serviceability Feature 
 
- Breakdown Self Diagnosis function 
 
- System Status Check Buttons for servicing purpose 
 
- System Pumpdown Button for servicing purpose 
 
- Front maintenance design for outdoor unit 
 
14 
4. Location of Controls and Components 
4.1 Indoor 
Unit 
4.1.1  Location of Control 
 
 
Buttons / Indicator
Water pressure gauge
• Do not press or hit the glass cover using hard
and sharp objects. Failure to do so may cause
damage to the unit.
• Ensure that the water pressure is between 0.05
and 0.3 MPa (0.1 MPa = 1 bar).
• In case the water pressure is out of the above
range, consult an authorised dealer.
1
Quick Menu button
(For more details, refer to the separate
Quick Menu Guide.)
Back button
Returns to the previous screen
LCD Display
Main Menu button
For function setup
ON/OFF button
Starts/Stops operation
6
Operation indicator
Illuminates during operation, blinks during
alarm.
Press centre
No glove
No pen
2
1
4
5
6
3
Cross key buttons
Selects an item.
Enter button
Fixes the selected content.
Up
Down
t
h
g
i
R
tf
e
L
0.2
0.4
0.3
0.1
MPa
bar
2
3
1
4
23
1
44
40
10:34am, Mon
18
˚
c
˚
c
˚
c
˚
c
2
 
15 
Display
Mode selection
AUTO
• Depending on the preset outdoor
temperature, the system selects
HEAT or *
1
 COOL operation mode.
Auto Heat
Auto Cool
*
1,
*
2
COOL
• The fan coil unit is either turned
ON or OFF.
• The outdoor unit provides cooling
to the system.
AUTO
+ TANK
• Depending on the preset outdoor
temperature, the system selects
HEAT + TANK or *
1
 COOL + TANK
operation mode.
Auto Heat
Auto Cool
*
1,
*
2
COOL
+ TANK
• The outdoor unit provides cooling
to the system.
• The system controls the booster
heater in the water tank.
HEAT
• The panel/floor HEAT operation is
either turned ON or OFF.
• The outdoor unit provides heat to
the system.
TANK
• The water tank is either turned
ON or OFF.
• The outdoor unit provides heat to
the water tank.
HEAT
+ TANK
• The outdoor unit provides heat to
the water tank and the system.
• This mode can be selected only
when the water tank is installed.
* The direction icons point to the currently
active mode.
• Room operation / Tank operation.
• Deice operation.
Operation icons
The status of operation is displayed.
Icon will not display (under operation OFF screen) whenever operation is OFF except weekly timer.
Holiday operation status
Weekly Timer operation status
Quiet operation status
Zone:Room Thermostat
→Internal sensor status
Powerful operation status
Demand Control or
SG ready or SHP status
Room Heater status
Tank Heater status
Solar status
Bivalent status
(Boiler)
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service  partners.
*2 Only displayed when COOL mode is unlocked (This means when COOL mode is available).
Temperature of each zone
Time and day
Water Tank temperature
Outdoor temperature
Sensor type/Set temperature type icons
Water Temperature
→Compensation curve
Water Temperature
→Direct
Pool only
Room Thermostat
→External
Room Thermostat
→Internal
2
4
1
5
6
7
23
1
44
40
10:34am, Mon
18
˚
c
˚
c
˚
c
˚
c
2
3
 
16 
4.1.2 Initialization 
 
Before starting to install the various menu settings, please initiate the Remote Controller by selecting the language of
operation and installing the date and time correctly.
It is recommended that the installer conducts the following initialization of the Remote Controller.
Selecting the language
LCD blinking
Press
 and wait while the display is
initializing.
Scroll with
 and
 to select the language.
Press
 to confirm the selection.
Setting the clock
1
h
ti
w
t
c
e
l
e
S
 or
 how to display the time,
either 24h or am/pm format (for example, 15:00
or 3 pm).
Press
 to confirm the selection.
Use
 and
 to select year, month, day,
hour and minutes. (Press
 to confirm the
selection each time.)
Once the time is set, time and day will appear
on the display even if the Remote Controller is
turned OFF.
 
4.1.3 Quick 
Menu 
 
After the initial settings have been completed, you can select a quick menu from the following options and edit the setting.
Press
 to display the quick menu.
Force DHW
Powerful
Quiet
Force Heater
Weekly Timer
Force Defrost
Error Reset
R/C Lock
Use
 to select menu.
Press
 to turn on/off the select menu.
Select
ON/OFF
 
Page of 127
Display

Click on the first or last page to see other WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 service manuals if exist.