DOWNLOAD Panasonic WH-SDC03H3E5-1 / WH-SDC05H3E5-1 / WH-SDC07H3E5-1 / WH-SDC09H3E5-1 / WH-UD03HE5-1 / WH-UD05HE5-1 / WH-UD07HE5-1 / WH-UD09HE5-1 Service Manual ↓ Size: 17.29 MB | Pages: 127 in PDF or view online for FREE

Model
WH-SDC03H3E5-1 WH-SDC05H3E5-1 WH-SDC07H3E5-1 WH-SDC09H3E5-1 WH-UD03HE5-1 WH-UD05HE5-1 WH-UD07HE5-1 WH-UD09HE5-1
Pages
127
Size
17.29 MB
Type
PDF
Document
Simplified Service Manual
Brand
Device
Air Conditioner / AIR-TO-WATER HEATPUMP
File
wh-sdc03h3e5-1-wh-sdc05h3e5-1-wh-sdc07h3e5-1-wh-sd.pdf
Date

Panasonic WH-SDC03H3E5-1 / WH-SDC05H3E5-1 / WH-SDC07H3E5-1 / WH-SDC09H3E5-1 / WH-UD03HE5-1 / WH-UD05HE5-1 / WH-UD07HE5-1 / WH-UD09HE5-1 Simplified Service Manual ▷ View online

61 
2.  Gently pull the lower section of the front plate 
towards you to remove the front plate from left and 
right hooks. 
3.  Hold the left edge and right edge of front plate to 
lift up front plate from hooks. 
 
Hook
Lift up
Screws
 
11.1.4.2  Install the indoor unit 
1.  Engage the slots on the indoor unit to the hooks of 
installation plate. Ensure the hooks are properly 
seated on the installation plate by moving it left 
and right. 
2.  Fix the screws 5 to the holes on the hooks of 
installation plate 4, as illustrated below. 
 
Installation plate
Indoor unit back
Slots
Wall
Hooks
Installation plate
Screws
Note: Do not lift the
Indoor Unit by holding the
refrigerant and water pipes
to prevent damage of the
pipes.
 
11.1.4.3  Water Piping Installation 
  The minimum requirement of water in the system 
is 30 litres. If this value could not be achieved, 
please install additional buffer tank (field supply). 
  Water inlet and water outlet in indoor unit are used 
for connection to water circuit. Please request a 
licensed technician to install this water circuit. 
  This water circuit must comply with all relevant 
European and national regulations, i.e. IEC/EN 
61770. 
  Be careful not to deform the piping to excessive 
force when doing piping connection job. 
  Use Rp 1 ¼" nut for both water inlet and outlet 
connection and clean all pipings with tap water 
before connecting to the indoor unit. 
  Cover the pipe end to prevent dirt and dust when 
inserting it through a wall. 
  Choose proper sealer which can withstand the 
pressures and temperatures of the system. 
  If an existing tank is to be connected to this indoor 
unit, ensure the pipes are clean before water pipe 
installation is carried out. 
  Be sure to use two spanners to tighten the 
connection. Tighten the nuts with torque wrench: 
117.6N•m. 
 
Torque wrench
Indoor unit
Spanner
 
 
  If non-brass metallic piping is used for installation, 
make sure to insulate the pipes to prevent 
galvanic corrosion. 
  Make sure to insulate the water circuit pipes to 
prevent reduction of heating capacity. 
  After installation, check the water leakage 
condition in connection area during test run. 
 
Water Inlet
Water Outlet
 
 
 
CAUTION
 
Do not over tighten, over tightening cause water leakage. 
11.1.4.4  Refrigerant Pipe Installation 
1  Please make flare after inserting flare nut (located 
at joint portion of tube assembly) onto the copper 
pipe. (In case of using long piping) 
2  Do not use pipe wrench to open refrigerant piping. 
Flare nut may be broken and cause leakage. Use 
proper spanner or ring wrench. 
3  Connect the piping: 
  Align the center of piping and sufficiently 
tighten the flare nut with fingers. 
  Be sure to use two spanners to tighten the 
connection. 
 
 
62 
Further tighten the flare nut with torque 
wrench in specified torque as stated in the 
table. 
Torque wrench
Spanner or
Wrench
 
 
WH-SDC03H3E5-1  WH-SDC05H3E5-1 
Piping size (Torque) 
Gas Liquid 
ø12.7 mm (1/2”) [55 N•m] 
ø6.35 mm (1/4”) [18 N•m] 
 
WH-SDC07H3E5-1  WH-SDC09H3E5-1 
Piping size (Torque) 
Gas Liquid 
Ø15.88mm (5/8”) [65 N•m] 
ø6.35 mm (1/4”) [18 N•m] 
 
Liquid Refrigerant Pipe Gas Refrigerant Pipe
 
 
 
CAUTION
Do not over tighten, over tightening cause water leakage. 
 
 
CAUTION
Please take extra precaution when open the control board cover 
and control board for indoor unit installation and servicing. Failure 
to do so may cause injury. 
 
CUTTING AND FLARING THE PIPING 
1.  Please cut using pipe cutter and then remove 
the burrs. 
2.  Remove the burrs by using reamer. If burrs is 
not removed, gas leakage may be caused. 
Turn the piping end down to avoid the metal 
powder entering the pipe. 
3.  Please make flare after inserting the flare nut 
onto the copper pipes. 
 
When properly flared, the internal surface
of the flare will evenly shine and be of even
thickness. Since the flare part comes into
contact with the connections, carefully check
the flare finish.
Improper flaring
Inclined Surface
damaged
CrackedUneven
thickness
1. To cut
2. To remove burrs
3. To flare
Bar
Red arrow mark
Handle
Core
Yoke
Clamp handle
Bar
0 – 0.5 mm
Copper
pipe
Reamer
Point down
Pipe
 
 
 
 
 
11.1.4.5  Drain Elbow and Hose 
Installation 
  Fix the drain elbow and packing to the bottom of 
indoor unit, as shown in below illustration. 
  Use inner diameter 17 mm drain hose in the 
market. 
  This hose must to be installed in a continuously 
downward direction and in a frost-free 
environment. 
  Guides this hose’s outlet to outdoor only. 
  Do not insert this hose into sewage or drain pipe 
that may generate ammonia gas, sulfuric gas, etc. 
  If necessary, use hose clamp to further tighten the 
hose at drain hose connector to prevent leakage. 
  Water will drip from this hose, therefore the outlet 
of this hose must be installed in an area where the 
outlet cannot become blocked. 
 
Packing
Drain Elbow
 
11.1.4.6 Pressure 
Relief Valve Drainage 
Pipework 
  Connect a drain hose to the pressure relief valve 
hose outlet. 
  This hose must to be installed in a continuously 
downward direction and in a frost-free 
environment. 
  Guides this hose’s outlet to outdoor only. 
  Do not insert this hose into sewage hose or 
cleaning hose that may generate ammonia gas, 
sulfuric gas, etc. 
  If necessary, use hose clamp to further tighten the 
hose at drain hose connector to prevent leakage. 
  Water will drip from this hose, therefore the outlet 
of this hose must be installed in an area where the 
outlet cannot become blocked. 
 
Pressure relief valve
hose outlet
 
 
 
 
 
 
 
 
 
63 
11.1.4.7  Air-Tightness Test on the 
Refrigerating System 
Before system charged with refrigerant and before the 
refrigerating system in put into operation, below site 
test procedure and acceptance criteria shall be 
verified by the certified technicians, and/or the 
installer:- 
 
Step 1: Pressure test for refrigerant leak detection: 
1.  Steps for pressure test, in accordance to ISO 
5149. 
2.  Evacuate the system from refrigerant before the 
leak test, attach the gauge manifold set correctly 
and tightly. Charging hose of Low side connect to 
Gas side. (Charging hose of High side connect to 
Liquid side if applicable.) 
3.  Adjust the knob on the service valves, and 
regulator on the gauge set, so that test gas can be 
inserted through the centre manifold of the gauge 
set. 
4.  Insert Nitrogen gas into the system through the 
centre manifold and wait until the pressure within 
the system to reach about 1MPa (10 BarG) wait 
for a few hours and monitor the pressure reading 
on the gauges. 
5.  Please note that the system’s pressure may rise 
slightly if the test is carried out on mid day, due to 
temperature rise. The inverse may happen when 
there is temperature drop at night. However, this 
variation will be minimal. 
6.  Waiting time depends on the size of the system. 
Larger systems may require 12 hours of waiting 
time. Leak detection within smaller system can be 
achieved in 4 hours. 
7.  Check if there is a constant pressure drop. Move 
to next step “Step 2: Refrigerant leak detection...” 
if there is any pressure drop. Otherwise, release 
the Nitrogen gas and, move to “Step 3: Vacuum 
test”. 
8.  Next, insert a small amount of same refrigerant 
into the system through the centre hose, until the 
pressure reaches about 1MPa (10 BarG). 
 
2
2
N
2
R-###
(Low/Gas)
pressure gauge
(High/Liquid) pressure gauge
An example illustrations of setup for
refrigerant leak detection.
3
7
4
8
 
 
 
 
 
 
 
Step 2: Refrigerant leak detection through Electronic 
halogen leak detector and/or ultrasonic leak detector: 
1.  Use any one of below detector to check leaking. 
  Electronic halogen leak detector. 
  Switch on the unit. 
  Cover the test area from direct draft. 
  Pass the detection probe near test area 
and wait for audible and visible signals. 
  Ultrasonic Leak Detector 
  Make sure the area is quiet. 
  Switch on the ultrasonic leak detector. 
  Move the probe along your air 
conditioning system to test for leaks, and 
mark for repair. 
2.  Any leak detected at this level shall be repaired 
and retested, starting from “Step 1: Pressure test”. 
 
NOTE: 
  Always recover the refrigerant and Nitrogen gas 
into recovery cylinder after completion of a test. 
  You must use the detection equipment with 
Detectable Leak Rate of 10
-6
 Pa. m
3
/s or better. 
  Do not use refrigerant as test medium for system 
with total refrigerant charge more than 5kg. 
  Test shall be performed with dry Nitrogen or 
another non-flammable, non-reactive, dried gas. 
Oxygen, air or mixtures containing them shall not 
be used. 
 
Step 3: Vacuum test: 
1.  Perform Vacuum test to check leak / moisture if 
present. 
2.  Refer to section “EVACUATION OF THE 
EQUIPMENT” to vacuum gas out of the air 
conditioning system. 
3.  Wait for a few hours, depending on the size of the 
refrigerating system and monitor the pressure rise. 
If the pressure rises until 1 bar absolute, then 
there is leak. 
If the pressure rises, but it is lower than 1 bar 
absolute, then moisture is present. 
 
Next, remove the moisture, or repair, and redo the 
refrigerant leak testing, starting from “Step 1: Pressure 
test”. 
 
2
2
3
Vacuum pump
Handle
(Low/Gas)
pressure gauge
(High/Liquid) pressure gauge
An example illustrations of setup for
refrigerant leak detection.
 
 
 
 
64 
11.1.5  Connect The Cable To The Indoor 
Unit 
 
WARNING
This section is for authorised and licensed electrician only. Work 
behind the Control Board Cover secured by screws must 
only be carried out under supervision of qualified contractor, 
installation engineer or service person. 
11.1.5.1  Open the Control Board Cover 
Please follow the steps below to open control board 
cover. Before opening the control board cover of 
indoor unit, always switch off all power supply (i.e. 
indoor unit power supply, heater power supply and 
Tank Unit power supply). 
1.  Remove the 6 mounting screws at the control 
board cover. 
2.  Swing the control board cover to the right hand 
side. 
 
Screws
Screws
 
11.1.5.2  Fixing of Power Supply Cord 
and Connecting Cable 
1.  Connecting cable between Indoor Unit and 
Outdoor Unit shall be approved polychloroprene 
sheathed 4 × 1.5 mm
2
 flexible cord, type 
designation 60245 IEC 57 or heavier cord. 
  Ensure the colour of wires of Outdoor Unit and 
the terminal no. are the same to the Indoor 
Unit respectively. 
  Earth wire shall be longer than other wires as 
shown in the figure for the electrical safety in 
case of the slipping out of the cord from the 
Holder (Clamper). 
2.  An isolating device must be connected to the 
power supply cable. 
  Isolating device (disconnecting means) should 
have minimum 3.0 mm contact gap. 
  Connect the approved polychloroprene 
sheathed power supply 1 cord and power 
supply 2 cord and type designation 60245 IEC 
57 or heavier cord to the terminal board, and 
to the other end of the cord to isolating device 
(Disconnecting means). See below table for 
cable size requirement. 
 
 
 
 
 
 
WH-SDC03H3E5-1  WH-SDC05H3E5-1 
Power Supply 
Cord 
Cable Size 
Isolating 
Devices 
Recommended 
RCD 
3 × 1.5 mm
2
 
15/16A 
30mA, 2P, type A 
3 × 1.5 mm
2
 
15/16A 
30mA, 2P, type AC 
 
WH-SDC07H3E5-1  WH-SDC09H3E5-1 
Power Supply 
Cord 
Cable Size 
Isolating 
Devices 
Recommended 
RCD 
3 × min  
2.5 mm
2
30A 
30mA, 2P, type A 
3 × min  
2.5 mm
2
30A 
30mA, 2P, type A 
 
3.  To avoid the cable and cord being damaged by 
sharp edges, the cable and cord must be passed 
through a bushing (located at the bottom of 
Control Board) before terminal board. The bushing 
must be used and must not be removed. 
 
Terminals on the Outdoor Unit
1
2
3
1
2
3
Colour of wires (Connecting cables)
Terminals on the Indoor Unit
L
N
L
N
L
1
N
1
(Power Supply Cord)
Terminals on the isolating
devices from power supply
(Disconnecting means)
L
1
N
1
Indoor Unit/
Outdoor Unit
connection
Power Supply 1
Power Supply 2
 
 
Power Supply Cord
Holder (Clamper)
Terminal Board
RCCB/ELCB
*1
*1
Connecting Cable
 
 
Terminal screw 
Tightening torque N•m {kgf•cm} 
M4 157~196 
{16~20} 
M5 196~245 
{20~25} 
*1 - Earth wire must be longer than other cables for safety reasons 
11.1.5.3  Wire Stripping and Connecting 
Requirement 
 
Wire stripping
5mm or
more
(gap between
wires)
No loose strand
when insert
Indoor/outdoor
connecting
terminal board
10
 ±
 1
m
m
ACCEPT
PROHIBITED
Conductor
over insert
Conductor not
fully insert
Conductor
fully insert
PROHIBITED
 
 
Page of 127
Display

Click on the first or last page to see other WH-SDC03H3E5-1 / WH-SDC05H3E5-1 / WH-SDC07H3E5-1 / WH-SDC09H3E5-1 / WH-UD03HE5-1 / WH-UD05HE5-1 / WH-UD07HE5-1 / WH-UD09HE5-1 service manuals if exist.