Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M Service Manual ▷ View online
2 - 17
2
Mini VRF SYSTEM
Outdoor Unit Repair Procedures
7. Compressor
8. High Pressure Sensor
(1)
(2)
(3)
(1)
8. High Pressure Sensor
The high pressure sensor connection port on the outdoor unit
includes a Schrader-type, push-to-release valve. It is not necessary
to recover the refrigerant when removing and installing the sensor.
includes a Schrader-type, push-to-release valve. It is not necessary
to recover the refrigerant when removing and installing the sensor.
8-1. Removing the High Pressure Sensor
Refer to “1. Removing Panels” and remove the front panel.
Disconnect the high pressure sensor connector (3P - BLK) from
terminal CN-HPS on the outdoor unit control PCB of the outdoor unit
where the high pressure sensor will be removed.
terminal CN-HPS on the outdoor unit control PCB of the outdoor unit
where the high pressure sensor will be removed.
Use 2 adjustable wrenches in combination to remove the high
pressure sensor.
pressure sensor.
The high pressure sensor connection port on
the outdoor unit includes a Schrader-type
valve. When removing the high pressure
sensor, internal pressure will be applied from
the refrigerant in the outdoor unit.
the outdoor unit includes a Schrader-type
valve. When removing the high pressure
sensor, internal pressure will be applied from
the refrigerant in the outdoor unit.
8-2. Installing the High Pressure Sensor
Use 2 adjustable wrenches in combination to install the high
pressure sensor.
pressure sensor.
CAUTION
Installation
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
Prepare for installation.
• Remove the rubber stopper and tube cap (welded) from the new compressor.
Install the crankcase heater onto the compressor.
Place the cushioning rubber in the designated positions on the compressor.
(There are 3 pieces for an inverter compressor.)
(There are 3 pieces for an inverter compressor.)
Set the new compressor into the unit.
Shape the tubes and insert them at the 2 welding locations.
Use nitrogen to replace the air inside the compressor. Perform brazing at all parts.
Increase the pressure to the nitrogen airtightness test pressure of 3.80 MPa. Check that no leakage occurs.
Re-install all components that were removed. Re-install the electrical component box in the original position
as it was before.
as it was before.
After the airtightness test is completed, apply vacuum until a pressure of –101 kPa {–775 mm Hg, 5 Torr} or
less is reached at the indoor and outdoor units and in the tubing.
less is reached at the indoor and outdoor units and in the tubing.
After applying vacuum, charge with refrigerant.
For the refrigerant charging methods, refer to “Installation
Instructions.”
Charge with the total of the “refrigerant amount at time of
shipment” plus the “additional charge amount.” (Listed on
the nameplate and description label.)
For the refrigerant charging methods, refer to “Installation
Instructions.”
Charge with the total of the “refrigerant amount at time of
shipment” plus the “additional charge amount.” (Listed on
the nameplate and description label.)
• Be sure to perform refrigerant charge using liquid refrigerant.
Never use any refrigerant other than R410A.
Connection port
(Schrader-type)
(Schrader-type)
High pressure
sensor
Fig. 2-12
Front side
SM830195-03_Mini VRF SYS.indb 17
SM830195-03_Mini VRF SYS.indb 17
2014/09/04 18:20:12
2014/09/04 18:20:12
2 - 18
– MEMO –
SM830195-03_Mini VRF SYS.indb 18
SM830195-03_Mini VRF SYS.indb 18
2014/09/04 18:20:13
2014/09/04 18:20:13
3 - 1
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
3. OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER
1. Overview
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
2. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3. Ordinary Display Controls and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
4. Monitoring Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
5. Outdoor Unit Alarm History Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
6. Mode Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Contents
SM830195-03_Mini VRF SYS.indb 1
SM830195-03_Mini VRF SYS.indb 1
2014/09/09 13:52:02
2014/09/09 13:52:02
3 - 2
3
Mini VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
OUTDOOR UNIT MAINTENANCE REMOTE
CONTROLLER (CZ-RTC2) for MINI VRF SYSTEM
CONTROLLER (CZ-RTC2) for MINI VRF SYSTEM
n About the outdoor unit maintenance remote controller
The outdoor unit utilizes nonvolatile memory (EEPROM) on
its PCB. This allows EEPROM data to replace the setting
switches that were present on previous PCBs. The outdoor
unit maintenance remote controller is used to set and change
these EEPROM data.
In addition to setting and checking the outdoor unit EEPROM
data, this remote controller can also be used to monitor the
outdoor unit alarm history, monitor the various indoor and
outdoor temperatures, and check the indoor unit connection
status (number of units, operating mode, etc.).
its PCB. This allows EEPROM data to replace the setting
switches that were present on previous PCBs. The outdoor
unit maintenance remote controller is used to set and change
these EEPROM data.
In addition to setting and checking the outdoor unit EEPROM
data, this remote controller can also be used to monitor the
outdoor unit alarm history, monitor the various indoor and
outdoor temperatures, and check the indoor unit connection
status (number of units, operating mode, etc.).
NOTE
Outdoor unit maintenance remote controller does not function as an
ordinary remote controller. It is therefore only used for test runs and
during servicing.
ordinary remote controller. It is therefore only used for test runs and
during servicing.
l
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller
to the outdoor unit PCB.
l
Ordinary remote controllers or other controller are still required for the indoor units, even when the outdoor unit
maintenance remote controller is connected.
CZ-RTC2
[Service Checker Section]
System diagram
(Servicing No.: CV6231785082)
Special service checker wiring
Remote controller Ass’y
Operation manual included in package.
Outdoor unit
Inter-unit control wiring
Outdoor unit
control PCB
Indoor
unit
Indoor
unit
Remote
controller
Remote
controller
Outdoor unit maintenance
remote controller
1. Overview
SM830195-03_Mini VRF SYS.indb 2
SM830195-03_Mini VRF SYS.indb 2
2014/09/09 13:52:21
2014/09/09 13:52:21
Click on the first or last page to see other U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 / S-15M / S-22M / S-28M / S-36M / S-45M / S-60M / S-73M / S-90M / S-106M / S-140M / S-160M service manuals if exist.